Whether a heat pump suits a house comes down to two questions: will it heat for less, and will it keep up when it's cold out? Both turn on numbers you can look up, your local energy prices and the unit's rated efficiency, so this guide works through them with figures from ENERGY STAR, the DOE, EIA, the IRS and REMDB, the National Laboratory of the Rockies' cost database, each cited where it's used.

A heat pump moves heat instead of burning fuel, so ENERGY STAR says it can deliver up to three times more heat energy[1] than the electricity it uses. At EIA's U.S. average prices it heats for less than electric resistance, propane and heating oil, and it ties a 95% gas furnace at a seasonal COP of about 3.42 (53.31 ÷ 15.58, worked below). About 13% of U.S. homes[2] already heat mainly with a central heat pump.

A heat pump moving heat from outdoor air into a house, beside bars of the seasonal COP it needs to tie each fuel at EIA prices: 1.09 for oil, 1.64 for propane, 2.88 for an 80% gas furnace and 3.42 for a 95% one.
A bar left of the green band means the heat pump heats for less.

How a heat pump works

A heat pump runs the same refrigerant cycle as an air conditioner, in either direction. In winter it pulls heat out of the outdoor air and releases it indoors; in warmer months, ENERGY STAR notes, the system works in reverse to provide air conditioning[3].

Cold air still carries usable heat. Natural Resources Canada puts it in numbers: air at −18°C, about 0°F, still holds 85%[4] of the heat it holds at 21°C, about 70°F[4].

Moving that heat costs far less electricity than making it, which is why ENERGY STAR says a heat pump can deliver up to three times more heat energy than the electricity it consumes[1]. A furnace can't beat its fuel: ENERGY STAR defines its efficiency (AFUE) as "the percentage of the heat in the incoming fuel which is converted to space heat instead of being lost"[5].

Against electric furnaces and baseboard heaters, the DOE says a heat pump "can reduce your electricity use for heating by approximately 50%"[6]. Inverter-driven compressors add to that by adjusting their output instead of cycling on and off: the DOE's Building America Solution Center says most ductless units turn down to about 30% of rated capacity[7].

For the full refrigeration cycle, see how a mini split works; the cycle is the same for every heat pump. The efficiency math is in COP explained.

How common heat pumps are

EIA's 2020 Residential Energy Consumption Survey counted 16.13 million[2] of 123.53 million[2] U.S. homes using a central heat pump as their main heating equipment, 13% (16.13 ÷ 123.53). A furnace heats 60%[2].

Heat pumps cluster in the Southeast and are rare in the Northeast and California.

StateHomes heated mainly by a central heat pump
South Carolina
41%
Alabama
39%
North Carolina
38%
Tennessee
35%
Florida
31%
Mississippi
28%
Georgia
27%
Virginia
27%
Arizona
25%
United States
13%
California
3%
New York
3%
Massachusetts
2%
Illinois
2%
Source: U.S. Energy Information Administration, 2020 Residential Energy Consumption Survey, Highlights for space heating in U.S. homes by state (final data, March 2023). Share of occupied primary homes whose main heating equipment is a central heat pump. EIA withholds the figure where the estimate is too uncertain or the sample too small, as in Michigan and Minnesota. View EIA's RECS table.

The three types of heat pump

All three move heat with the same cycle; they differ in where the heat comes from and how it reaches the rooms. This table lines up the ENERGY STAR efficiency floor, REMDB's installed cost and REMDB's expected life for each.

TypeHeat source and deliveryENERGY STAR minimumREMDB installed cost (2023 dollars)REMDB life
Air-source, ducted
Outdoor air, through the home's ducts
15.2 SEER2, 7.8 HSPF2
3 tons at 16 SEER: $8,000 to $20,500, mid $14,250
15.6 years
Ductless mini split
Outdoor air, to wall or ceiling heads
15.2 SEER2, 7.8 HSPF2
12,000 Btu, 20 SEER, one zone: $4,500 to $10,500, mid $7,500
15.6 years
Ground-source (geothermal)
Ground or groundwater, through ducts or water pipes
Closed-loop water-to-air: EER 17.1, COP 3.6
$7,050 to $14,450 per ton, mid $10,750
20 years
Sources: ENERGY STAR Heat Pump Key Product Criteria (split systems) and Geothermal Heat Pumps Key Product Criteria (effective January 1, 2012); National Residential Efficiency Measures Database (REMDB), version 4.0.0, National Laboratory of the Rockies (April 2025), Air Source Heat Pump and Ground Source Heat Pump measures, retrofit installed cost, low to high with the mid estimate, rounded to the nearest $50. REMDB does not assign mini splits a SEER2; 16 SEER is about 15.2 SEER2 (16 × 0.95). View the REMDB measure page.
  • Ducted air-source replaces a furnace and central air in one system. ENERGY STAR points homes that already have ducts to a ducted heat pump[3].
  • Ductless mini split suits homes or rooms without ductwork, the case ENERGY STAR designed its ductless guidance around[3]. The DOE notes that a mini split avoids the energy loss that comes with ductwork[12]. See our mini split guide.
  • Ground-source (geothermal) "uses the thermal energy of the ground or groundwater," in ENERGY STAR's definition[10]. The DOE expects the underground loop to last 25 to 50 years[11] and the heat pump 20 or more[11]. For 3 tons, REMDB's range works out to about $21,150 to $43,400 (7,043.89 × 3 and 14,460.91 × 3, rounded to the nearest $50), and REMDB rates that estimate's statistical support as low[9].

A geothermal unit's EER and COP come from a different test, ISO 13256-1[10], so they don't compare directly with an air-source unit's SEER2 and HSPF2. See air-source vs. ground-source for the full comparison.

Efficiency ratings: SEER2, HSPF2, EER2 and COP

ENERGY STAR's criteria define each rating:

  • SEER2 is "the total heat removed from the conditioned space during the annual cooling season, expressed in Btu, divided by the total electrical energy consumed by the heat pump during the same season, expressed in watt-hours"[13].
  • HSPF2 is the same idea for heating: Btu of heat delivered per watt-hour of electricity over a heating season, measured for climate region IV[13].
  • EER2 is "the ratio of the average rate of space cooling delivered to the average rate of electrical energy consumed by the heat pump"[13], at a single test condition.
  • COP is "the ratio of the average rate of space heating delivered to the average rate of electrical energy consumed by the heat pump"[13].
RatingFederal minimum, split heat pump made from 2023ENERGY STAR, split system
SEER2
14.3
15.2
HSPF2
7.5
7.8
EER2
None in 430.32(c)(5)
11.0
Sources: 10 CFR 430.32(c)(5), energy conservation standards for split-system heat pumps manufactured on or after January 1, 2023; ENERGY STAR Heat Pump Key Product Criteria, split systems. View ENERGY STAR's criteria.

ENERGY STAR's cold-climate tier asks for at least 8.1 HSPF2 from ducted systems[13] and 8.5 from ductless ones[13], a COP of at least 1.75 at 5°F[13], and at least 70%[13] of its 47°F heating capacity left at 5°F[13].

HSPF2 converts to a season's average COP. EIA counts 3,412 Btu in a kilowatt-hour[15], so a watt-hour is 3.412 Btu, and dividing an HSPF2 by 3.412 gives the COP: 7.5 ÷ 3.412 = 2.20, 7.8 ÷ 3.412 = 2.29, and 10 ÷ 3.412 = 2.93.

The number that decides your bill

Heating cost comes down to what you pay for each unit of heat delivered. EIA's U.S. averages are 18.19 cents a kWh for electricity[16] (January to August 2026) and $15.34 per thousand cubic feet of natural gas[17] (2025), about $1.48 a therm at 1,036 Btu a cubic foot[18] (15.34 ÷ 10.36).

For delivered fuels, EIA's U.S. residential prices, excluding taxes, were $2.826 a gallon for propane[19] and $5.915 for heating oil[20] in the week of November 9, 2026[19]. The table turns those prices into the cost of a million Btu of heat in the house.

Heat sourceEfficiencyCost per million Btu delivered
Electric resistance (furnace or baseboard)
COP 1
$53.31
Heat pump at ENERGY STAR's cold-climate floor at 5°F
COP 1.75
$30.46
Heat pump at the federal minimum, 7.5 HSPF2
Seasonal COP 2.20
$24.25
Heat pump at ENERGY STAR's 7.8 HSPF2
Seasonal COP 2.29
$23.32
Heat pump at 10 HSPF2
Seasonal COP 2.93
$18.19
Heat pump, seasonal COP 3
COP 3
$17.77
Gas furnace, federal minimum
80% AFUE
$18.50
Gas furnace, ENERGY STAR (U.S. South)
95% AFUE
$15.58
Propane furnace
95% AFUE
$32.53
Oil furnace, ENERGY STAR
87% AFUE
$49.09
How this was calculated: 1,000,000 Btu ÷ the fuel's energy content (EIA: 3,412 Btu per kWh, 100,000 per therm, 91,452 per gallon of propane, 138,500 per gallon of heating oil) × its price (EIA: 18.19 cents a kWh, January to August 2026; $1.48 a therm, 2025; propane $2.826 and heating oil $5.915 a gallon, week of November 9, 2026, excluding taxes) ÷ the efficiency shown. AFUE levels: 80% is the federal minimum for non-weatherized gas furnaces (10 CFR 430.32(e)); 95% gas and 87% oil are ENERGY STAR's furnace criteria. Prices come from different periods, so treat the rows as a comparison, not a forecast.

Divide the resistance cost by any fuel's cost and you get the COP a heat pump needs to tie it: 53.31 ÷ 15.58 = 3.42 against a 95% gas furnace, 53.31 ÷ 18.50 = 2.88 against an 80% one, 53.31 ÷ 32.53 = 1.64 against propane and 53.31 ÷ 49.09 = 1.09 against oil.

A seasonal COP of 3.42 equals about 11.7 HSPF2 (3.42 × 3.412), well above ENERGY STAR's 7.8. So at these average prices a heat pump clearly undercuts propane, oil and resistance heat, while against a 95% gas furnace it needs cheap electricity, pricey gas or a very efficient unit.

HSPF2 is rated for one climate region[13], so a real season runs better in a mild climate and worse in a cold one. Local prices swing even more: EIA's January to August 2026 averages[16] run from 12.46 cents a kWh in North Dakota[16] to 46.41 in Hawaii[16]. Run your own numbers with the heat pump running cost calculator and your state's rate in the kWh cost calculator.

What heat pumps cost

For a 3-ton[8] ducted heat pump at 15 SEER[8], about 14.3 SEER2 (15 × 0.95), REMDB's installed cost is $7,450 to $19,250[8], $13,350 at the mid estimate[8], in 2023 dollars[8] as a replacement. At 16 SEER[8], about 15.2 SEER2 (16 × 0.95), it's $8,000 to $20,500[8], and a new electrical circuit adds about $1,400[8].

REMDB's air-source heat pump costs come from Lawrence Berkeley National Laboratory regressions dated August 2024[8]. It also lists what moves a quote: local wages and drive time, codes, the condition of the electrical service and ducts, extra wiring, condensate drainage, the equipment type and the contractor's experience[8].

Installation quality matters too: ENERGY STAR warns that improper installation can reduce system efficiency by up to 30 percent[21]. Our heat pump cost-to-install guide breaks the pricing down by size and type.

Cold climates: do heat pumps work?

Yes, with the right model. ENERGY STAR tests air-source heat pumps down to 5°F[1] for certification and says a cold-climate model "will continue working at temperatures below 5°F"[1].

Natural Resources Canada puts most newer models' minimum operating temperature between −15°C and −25°C[4], about 5°F to −13°F (−15 × 1.8 + 32 and −25 × 1.8 + 32). The DOE says air-source heat pumps "can be used in all climates" and that cold-climate models "are designed specifically for cold climates"[6].

Output still falls as it gets colder. Below the balance point, in the DOE's words, "the heat pump cannot fully meet the home's heating needs without a backup heat source"[22]. Compare models on capacity and COP at your design temperature, not only at the standard rating point: NEEP's cold-climate list reports both at 47°F, 17°F and 5°F[23], plus the lowest outdoor temperature the maker publishes data for[23].

The DOE's sizing guide lays out the choices for the coldest hours:

  • Size for the full load. "Size to meet the design heating load at the location's design heating temperature"[22], so backup heat rarely runs.
  • Size for most of the load. The guide uses 80% of the design heating load as one example[22], with backup covering the rest.
  • Dual fuel. ENERGY STAR describes pairing the heat pump with "a more traditional gas or oil furnace"[1] that takes over in deep cold.
  • Electric resistance strips. Simple to add, but the DOE calls resistance backup "an inefficient and typically expensive form of heat, which should be minimized in all cases"[22].

The DOE says not to set a heat pump back manually if doing so brings on backup electric-resistance heat[6]. Frost on the outdoor coil is melted by defrost: the unit switches to cooling mode with its outdoor fan off, and supplementary heat may run meanwhile[4].

Size the system with the heat pump size calculator, and see heat pumps in cold weather for the full treatment. ENERGY STAR says your contractor should verify the size with an ACCA Manual J calculation[1].

2026 tax credits and rebates

The federal 25C credit ended for heat pumps placed in service after December 31, 2025[25]. Before it ended, it covered 30% of the cost[24], up to $2,000 a year[24] for a heat pump meeting the CEE's highest efficiency tier. The geothermal credit, 25D, ended too: it doesn't cover expenditures after December 31, 2025[25], and the IRS counts the expenditure when installation is complete[25].

What still runs is state-administered money from the Inflation Reduction Act:

  • HEEHR (High-Efficiency Electric Home Rebates): up to $8,000 for a heat pump[26], covering 100% of the cost[26] below 80% of area median income[26] and 50% from 80% to 150%[26], with a $14,000 cap per household[26]. DOE Program Notice 26-2, effective May 29, 2026[27], limits these HVAC rebates to upgrades from existing electric equipment; a home may keep its fossil-fuel system beside the new heat pump[27].
  • HOMES (whole-home rebates): for modeled savings of 20%[28] to under 35%[28], the lesser of $2,000 or 50% of the cost[28]; at 35% or more, $4,000 or 50%[28]. Low- and moderate-income homes get $4,000 or $8,000, up to 80% of the cost[28].
  • Not both: a HEEHR rebate can't be combined with HOMES for the same project[26].

The DOE says these rebates are available in select states and points homeowners to their State or Territory Energy Office[29]. State and utility programs are listed in the DSIRE database[30]. Our heat pump tax credit and rebate guide has the details.

Maintenance

  • Filters. The DOE says to clean or change heat pump filters monthly or as needed[6], and ENERGY STAR's checklist says to check them once a month[31]. On the cooling side, clean filters can lower energy use by 5 to 15 percent[12].
  • Seasonal tune-ups. ENERGY STAR suggests a cooling check in spring and a heating check in fall[31]. The technician tightens electrical connections, lubricates moving parts, checks the condensate drain and refrigerant level, and cleans the coils[31].
  • Outdoor unit. Keep it clear of leaves and debris[12]. New York's Clean Heat program checks that outdoor units won't get buried in snow, set on risers, stands or wall mounts of 6, 12 or 18 inches[32] depending on location, with defrost water drained to a safe spot[32].
  • Refrigerant. Work that adds or removes refrigerant or connects refrigerant lines requires EPA Section 608 certification[33]. See our maintenance checklist for the full routine.

Common myths about heat pumps

"Heat pumps don't work below freezing." ENERGY STAR tests them down to 5°F[1], and its cold-climate models keep working below that[1].

"A heat pump always saves money." Not against a 95% gas furnace at average U.S. prices: it needs a seasonal COP of about 3.42 (53.31 ÷ 15.58) to tie one. Against propane, oil and resistance heat it wins at far lower efficiencies.

"Heat pumps blow cold air." The air is cooler than a furnace's, not cold. Natural Resources Canada puts heat pump supply air at 25°C to 45°C (77°F to 113°F)[4] against 55°C to 60°C (131°F to 140°F)[4] from a furnace.

Downsides of heat pumps

  • Higher upfront cost. REMDB's mid estimate is $13,350 for a 3-ton ducted heat pump[8] but $4,050 for a gas furnace swap[34] (95% AFUE, 80,000 Btu/h[34]), though the heat pump also replaces the air conditioner.
  • Less heat when it's coldest. Even ENERGY STAR's cold-climate models only have to keep 70% of their capacity at 5°F[13], so cold climates need a cold-climate model, backup heat or both.
  • Running cost depends on local prices. At U.S. averages, a 95% gas furnace delivers heat for $15.58 per million Btu against $23.32 for a heat pump at ENERGY STAR's 7.8 HSPF2, as the table above shows (53.31 × 3.412 ÷ 7.8).
  • Defrost cycles. In cold, damp weather the unit pauses heating to melt frost off the outdoor coil[4].
  • Electrical capacity. A new circuit adds about $1,400 in REMDB[8], and backup resistance strips can push a panel toward an upgrade.

Frequently asked questions

Is a heat pump worth it? It depends on what you're replacing and your local prices. At U.S. averages it beats electric resistance, propane and oil comfortably, and it replaces your air conditioner too.

Against natural gas it's close: a heat pump needs a seasonal COP of about 3.42 (53.31 ÷ 15.58) to match a 95% furnace. Check your own rates in our running cost calculator.

Do heat pumps work in cold weather? Yes. ENERGY STAR tests them down to 5°F[1], and its cold-climate models keep working below that[1].

Natural Resources Canada puts newer models' minimum operating temperature at −15°C to −25°C[4]. Below the balance point, backup heat or a dual-fuel furnace covers the gap.

How much does a heat pump cost to run? At EIA's U.S. average of 18.19 cents a kWh[16], a million Btu of heat costs $23.32 at ENERGY STAR's 7.8 HSPF2 (53.31 × 3.412 ÷ 7.8) and $17.77 at a seasonal COP of 3 (53.31 ÷ 3). Use the running cost calculator with your rate and climate.

How long do heat pumps last? REMDB gives an air-source heat pump about 15.6 years[8] and a ground-source system 20[9]. The DOE expects a geothermal ground loop to last 25 to 50 years[11], and ENERGY STAR suggests considering replacement once a heat pump is more than 10 years old[35]. The HVAC serial number decoder reads a unit's age from its serial for the formats we could source.

What size heat pump do I need? That depends on your home's heat loss, climate and design temperature. ENERGY STAR says your contractor should verify the size with ACCA Manual J[1], and the DOE says ACCA Manual S "provides a sound method for sizing heat pumps"[22]; for a first estimate, use our heat pump size calculator.

What HSPF2 should I look for? The federal minimum for a split heat pump is 7.5 HSPF2[14] and ENERGY STAR's is 7.8[13]. In a cold climate, ENERGY STAR's cold-climate tier asks for 8.1 ducted or 8.5 ductless[13].

Sources & References

  1. ENERGY STAR: Air-Source Heat Pumps (up to three times more heat energy than the electricity consumed; certification testing down to 5°F; cold-climate models keep working below 5°F; dual fuel with a gas or oil furnace; size with Manual J)
  2. U.S. EIA: 2020 Residential Energy Consumption Survey, Highlights for space heating in U.S. homes by state (final data, March 2023; 16.13 million of 123.53 million homes, 13%, heat mainly with a central heat pump)
  3. ENERGY STAR: Ductless Heating & Cooling (works in reverse for air conditioning; for homes or sections without ductwork, ducted heat pumps for homes with ducts)
  4. Natural Resources Canada: Heating and cooling with a heat pump (heat in cold air; minimum operating temperatures; defrost; supply air temperatures)
  5. ENERGY STAR: Furnaces Key Product Criteria (AFUE definition; gas 95% South and 97% North, oil 87%)
  6. U.S. DOE: Energy Saver Guide 2022 (PDF) (heat pumps cut heating electricity about 50% vs electric furnaces and baseboard; all climates; cold-climate models; setback and filter tips)
  7. U.S. DOE Building America Solution Center: Ductless Mini-Split Heat Pumps code compliance brief (inverter compressors, most down to about 30% of rated capacity)
  8. National Laboratory of the Rockies (formerly NREL): National Residential Efficiency Measures Database (REMDB), version 4.0.0 (April 2025), Air Source Heat Pump (retrofit installed cost, 2023 dollars; new circuit; 15.6-year life; cost drivers; data sources)
  9. National Laboratory of the Rockies (formerly NREL): REMDB, version 4.0.0 (April 2025), Ground Source Heat Pump (retrofit, 2023 dollars per ton: $7,043.89 low, $10,752.40 mid, $14,460.91 high; 20-year life; low statistical significance)
  10. ENERGY STAR: Geothermal Heat Pumps Key Product Criteria (effective January 1, 2012; closed-loop water-to-air EER 17.1 and COP 3.6; ISO 13256-1 test)
  11. U.S. DOE: Guide to Geothermal Heat Pumps (PDF) (ground loop 25 to 50 years, heat pump 20 years or more)
  12. U.S. DOE: Energy Saver 101, Home Cooling (PDF) (clean filters lower energy use 5 to 15 percent; keep the outdoor unit clean; mini splits avoid duct losses)
  13. ENERGY STAR: Heat Pump Key Product Criteria (SEER2, HSPF2, EER2 and COP definitions; split 15.2 SEER2, 7.8 HSPF2, 11.0 EER2; cold climate 8.1 ducted and 8.5 ductless HSPF2, COP 1.75 and 70% capacity at 5°F)
  14. 10 CFR 430.32, Energy and water conservation standards (split heat pumps made from January 1, 2023: 14.3 SEER2 and 7.5 HSPF2; furnaces in 430.32(e))
  15. U.S. EIA: British thermal units (3,412 Btu per kWh; 100,000 per therm; propane 91,452 and heating oil 138,500 per gallon)
  16. U.S. EIA: Electric Power Monthly, Table 5.6.B, average price of electricity to residential customers by state, year to date (January to August 2026: U.S. 18.19 cents; North Dakota 12.46, Hawaii 46.41)
  17. U.S. EIA: U.S. Price of Natural Gas Delivered to Residential Consumers, annual (2025: $15.34 per thousand cubic feet; released October 30, 2026)
  18. U.S. EIA: Heat Content of Natural Gas Delivered to Consumers (U.S., 2025: 1,036 Btu per cubic foot)
  19. U.S. EIA: Weekly Heating Oil and Propane Prices, residential propane (U.S., week of November 9, 2026: $2.826 a gallon, excluding taxes)
  20. U.S. EIA: Weekly Heating Oil and Propane Prices, residential heating oil (U.S., week of November 9, 2026: $5.915 a gallon, excluding taxes)
  21. ENERGY STAR: Heat & Cool Efficiently (improper installation can reduce system efficiency by up to 30 percent)
  22. U.S. DOE Building America Solution Center: Cold Climate Heat Pump Sizing and Selection (balance point; sizing approaches; resistance backup; ACCA Manual S)
  23. NEEP: Cold Climate Air Source Heat Pump Specification, version 4.0 (capacity and COP at 47°F, 17°F and 5°F; lowest cataloged outdoor temperature)
  24. IRS: Energy Efficient Home Improvement Credit (25C) (30% of qualified expenses; $2,000 a year for heat pumps meeting the CEE highest efficiency tier)
  25. IRS: FAQs on the 25C and 25D changes under Public Law 119-21 (FS-2025-05) (no 25C credit for property placed in service after December 31, 2025; no 25D credit for expenditures after December 31, 2025)
  26. 42 U.S.C. 18795a, High-Efficiency Electric Home Rebate Program ($8,000 heat pump cap; 100% of cost below 80% of area median income, 50% from 80% to 150%; $14,000 per household; not combined with HOMES for the same project)
  27. U.S. DOE: Home Energy Rebates Program Notice 26-2 (HEEHR, effective May 29, 2026; HVAC rebates only from existing electric equipment)
  28. 42 U.S.C. 18795, HOMES rebates (20% to under 35% savings: lesser of $2,000 or 50% of cost; 35% or more: $4,000 or 50%; low- and moderate-income: $4,000 and $8,000, up to 80%)
  29. U.S. DOE: Home Energy Rebates (available in select states; State or Territory Energy Office)
  30. DSIRE: Database of State Incentives for Renewables & Efficiency
  31. ENERGY STAR: Maintenance Checklist (filters monthly; cooling check in spring, heating check in fall; technician tasks)
  32. NYS Clean Heat: ASHP Field Assessment Hot List (PDF) (outdoor units not buried in snow; 6, 12 or 18 inch risers by location; defrost water drainage)
  33. U.S. EPA: Refrigerant management program, questions and answers for Section 608 certified technicians (certification for adding or removing refrigerant and connecting refrigerant lines)
  34. National Laboratory of the Rockies (formerly NREL): REMDB, version 4.0.0 (April 2025), Furnaces (retrofit equipment swap, 2023 dollars: 80,000 Btu/h, 95% AFUE gas furnace mid $4,050)
  35. ENERGY STAR: When is it time to replace? (consider replacing a heat pump more than 10 years old)

Related Articles