A heat pump pulls heat out of outdoor air, which sounds impossible in January. Natural Resources Canada notes that air at −18°C (about 0°F)[6] still holds 85% of the heat of air at 21°C (70°F)[6]. What matters is how much of that heat the heat pump delivers on the coldest days, and what covers the gap.

Yes. Heat pumps keep heating well below freezing, but their output and efficiency fall as it gets colder. An ENERGY STAR cold-climate heat pump must still deliver at least 70% of its 47°F capacity at 5°F[1], at a COP of at least 1.75[1], and ENERGY STAR says it "will continue working at temperatures below 5°F"[2], paired with backup heat for the coldest hours[2].

Energy flow at 5°F: a cold-climate heat pump at COP 1.75 turns 1 kWh of electricity plus 0.75 kWh of heat from the outdoor air into 1.75 kWh of heat, against 1 kWh from a resistance heater.
ENERGY STAR's cold-climate minimum, against resistance heat.

Why output falls in the cold

A heat pump moves heat instead of making it, which is why ENERGY STAR says it "can deliver up to three times more heat energy to a home than the electrical energy it consumes"[2]. As the outdoor air gets colder, its ability to absorb heat from that air drops[6], so each unit of electricity moves less heat. Capacity falls, and so does efficiency.

Even at the cold-climate floor, a COP of 1.75[1] means 1.75 units of heat for each unit of electricity. A resistance heater turns each kWh into the same 3,412 Btu[12] of heat, a COP of 1, so the heat pump still delivers 75% more heat from the same power (1.75 − 1 = 0.75).

Standard vs. cold-climate heat pumps

ENERGY STAR measures cold-climate performance against the heat pump's capacity in mild weather: "Percent of Heating Capacity at 5°F ≥ 70% of that at 47°F"[1]. Our heat pump size calculator models how capacity falls:

Outdoor temperatureStandard heat pumpCold-climate heat pump
47°F
100%
100%
17°F
about 60%
about 79%
5°F
about 40%
at least 70%
Standard heat pump: calculator assumptions. Cold-climate heat pump: ENERGY STAR's minimum of 70% at 5°F, with 17°F on the straight line from 100% at 47°F to 70% at 5°F (100 − 30 × 30 ÷ 42 = 79)

The cold-climate efficiency minimums are higher too: at least 8.1 HSPF2 for ducted systems[1] and 8.5 for ductless ones[1], against 7.8 for a standard split system[1]. ENERGY STAR also requires "third-party verified performance for low temperatures, testing ASHPs down to 5°F"[2].

NEEP wrote its cold-climate specification for IECC climate zone 4 and colder[3]. It asks makers to report each model's heating capacity, power and COP at 47°F, 17°F and 5°F[3], plus the "lowest temperature at which the manufacturer offers published performance data"[3]. Those figures are on NEEP's cold-climate heat pump list[14].

Defrost

Frost forms on the outdoor coil when it's near or below freezing outside, more of it in damp air[6]. To clear it, the heat pump switches to cooling mode, sending hot refrigerant to the outdoor coil while the outdoor fan stops[6]. Meanwhile it is cooling the air in the ducts, so the air can feel cool and backup heat may switch on[6].

Some heat pumps start a defrost cycle on a timer, every 30, 60 or 90 minutes[6], depending on the climate and the design. Others defrost on demand, only when frost has built up, which NRCan calls generally more efficient[6].

Keep the outdoor unit out of the snow. New York's Clean Heat program checks that units can't be buried in snow, using risers, stands or wall mounts that lift them 6, 12 or 18 inches[9], depending on the location. It also wants defrost water drained "to a safe location that does not cause water damage or a slip hazard"[9].

Finding your design temperature

Heating equipment is sized to a design temperature, not the record low. EPA tells designers of ENERGY STAR homes to use ACCA Manual J's "99% heating season design temperature"[8] for the weather station closest to the home. Most hours of the winter stay above that temperature, and the few below it are covered by backup heat or a short indoor dip.

The colder your design temperature, the more a model's low-temperature output matters. ENERGY STAR tests cold-climate models "down to 5°F"[2], and NEEP's list reports each model's output at 5°F[3]: that is the number to compare between models. Where the design low sits well below it, expect backup heat on more hours, even with a cold-climate unit.

Balance point and backup heat

The balance point is the outdoor temperature where the heat pump's heating capacity equals the house's heat loss[6]. Below it, in the words of DOE's Building America guide, "the heat pump cannot fully meet the home's heating needs without a backup heat source"[7]. Backup can be electric resistance elements in the ducts or electric baseboards, or a furnace or boiler in a hybrid system[6].

ENERGY STAR describes the hybrid option as dual fuel: heating "with a heat pump or with a more traditional gas or oil furnace"[2]. For example, the heat pump size calculator gives these results for a 2,000 sq ft two-story home built between 1980 and 1999 with a cold-climate heat pump:

  • Cold region, design low 0°F (a calculator assumption): a 3.5-ton unit, a balance point of about 9.5°F and about 2.7 kW of backup at the design low.
  • Very cold region, design low −10°F (a calculator assumption): a 3.5-ton unit, a balance point of about 9°F and about 5.4 kW of backup.

In both cases the heat pump carries the house alone down into the single digits, so backup runs only on the coldest days. DOE's guide calls electric resistance backup "an inefficient and typically expensive form of heat, which should be minimized in all cases of heat pump installations"[7]. With electric backup, NRCan recommends setting the backup's thermostat 2°C to 3°C below (about 4°F to 5°F)[6] the heat pump's, so the heat pump does as much of the work as it can.

What it costs to run in the cold

ENERGY STAR defines COP as "the ratio of the average rate of space heating delivered to the average rate of electrical energy consumed by the heat pump"[1]. HSPF2 is the seasonal version, heat in Btu "divided by the total electrical energy consumed by the heat pump system during the same season, expressed in watt-hours"[1]. One kWh is 3,412 Btu[12], so ENERGY STAR's 7.8 HSPF2 minimum for split systems[1] works out to a seasonal COP of 2.29 (7.8 ÷ 3.412 = 2.29).

HSPF2 is measured over the heating season of DOE's region IV[1], so in a colder climate the seasonal average comes out lower. Delivering one million Btu of heat takes 293 kWh of electricity (1,000,000 ÷ 3,412 = 293), divided by the COP. At EIA's U.S. residential average for January to August 2026, 18.19 cents per kWh[11], that comes to:

Heat sourceEfficiencyCost per million Btu
Electric resistance (strip backup)
COP 1.0
about $53.31
Heat pump at ENERGY STAR's 5°F floor
COP 1.75
about $30.46
Heat pump, seasonal at 7.8 HSPF2
COP 2.29
about $23.28
Heat pump, mild weather
COP 3.0
about $17.77
Gas furnace
95% AFUE
about $15.58
How this was calculated: 293 kWh per million Btu (1,000,000 ÷ 3,412) at 18.19 cents per kWh (EIA, January to August 2026), divided by the COP. COP 1.75 is ENERGY STAR's cold-climate minimum at 5°F, COP 2.29 is 7.8 HSPF2 ÷ 3.412, and COP 3.0 is the top of ENERGY STAR's "up to three times". The gas row is 10 therms at $1.48 (EIA's 2025 U.S. residential average) divided by 0.95

The gas row is 10 therms per million Btu, since a therm is 100,000 Btu[12]. EIA's 2025 U.S. residential gas price was $15.34 per thousand cubic feet[4], about $1.48 a therm at 1,036 Btu a cubic foot[5] (15.34 ÷ 10.36 = 1.48). Divided by 95% AFUE, ENERGY STAR's minimum for gas furnaces in the U.S. South[13], that is about $15.58 (14.80 ÷ 0.95 = 15.58).

DOE sums it up: heat pumps "can reduce your electricity use for heating by approximately 50%"[10] compared with electric furnaces or baseboard heaters. That is also why the backup choice matters: strips run at COP 1.0, the top row, while a dual-fuel system burns gas in the coldest hours at under a third of the strip cost here ($15.58 ÷ $53.31 = 0.29).

The backup in the examples above turns into an hourly cost the same way. At 18.19 cents per kWh, 2.7 kW of strips cost about $0.49 an hour (2.7 × 0.1819 = 0.49) and 5.4 kW about $0.98 an hour (5.4 × 0.1819 = 0.98). Those rates apply only in the hours the heat pump can't carry the house alone.

Sizing for cold climates

Heat pumps used to be sized to the cooling load. DOE's Building America guide explains: "Traditionally, best practice has been to right-size the heat pump for cooling. Often this meant that the heating capacity was undersized, but the system would make up for any lack of heating capacity with auxiliary heat"[7].

For a cold-climate heat pump, the guide's approaches size to the heating load instead: all of it at the design temperature, or most of it, such as 80% of the design heating load[7]. NRCan adds that an undersized heat pump leans on supplementary heat more often, while an oversized one cycles on and off in milder weather[6]. ENERGY STAR says your contractor should verify the size "using a tool called 'Manual J'"[2].

Bringing your attic and walls up to the recommended insulation levels for your climate zone lowers the heating load first, which shrinks both the size you need and the backup hours. The heat pump size calculator sizes for both seasons and estimates the balance point and backup for your home.

Frequently asked questions

At what temperature do heat pumps stop working?

It depends on the model. NRCan says most air-source heat pumps have a minimum operating temperature, which for newer models runs from −15°C to −25°C (5°F to −13°F)[6], and a supplemental system must take over below it[6]. For cold-climate models, ENERGY STAR says the unit "will continue working at temperatures below 5°F"[2], and NEEP's list shows each model's lowest cataloged outdoor temperature[3].

Is a heat pump worth it in a cold climate?

It can be, with a cold-climate model sized to the heating load. DOE's Energy Saver guide says air-source heat pumps "can be used in all climates" and that "Cold-climate air-source heat pumps are designed specifically for cold climates"[10]. Whether it costs less to run than gas depends on local prices; see gas vs. electric heating cost.

Do heat pumps need backup heat?

In cold climates, usually some, for the coldest hours. ENERGY STAR says pairing a heat pump with backup "will heat your home the most efficiently when temperatures are even lower"[2]. In the examples above, a cold-climate heat pump sized to the heating load needs about 2.7 to 5.4 kW of backup at the design low (calculator assumptions).

Do I need a cold-climate model in zone 4, 5 or 6?

NEEP wrote its cold-climate specification for IECC climate zone 4 and colder[3], and DOE's guide says the shortfall of a heat pump sized for cooling is "more exaggerated" in climate zones 5 to 8[7]. A cold-climate model holds at least 70% of its 47°F capacity at 5°F[1], against about 40% for a standard unit in the calculator's model (a calculator assumption). The colder your design temperature, the more that difference pays off.

Should I turn my heat pump down at night in winter?

Not if the setback brings on backup heat. DOE says: "Do not set back the heat pump's thermostat manually if it causes backup electric-resistance heating to come on. This type of heating is more expensive"[10].

NRCan suggests setbacks of no more than 2°C, about 4°F[6], or a smart thermostat that starts warming the house early[6].

Will my bills spike on the coldest days?

They rise, because efficiency falls and backup heat may run. Strip backup runs at a COP of 1.0, so in the examples above 2.7 kW of it costs about $0.49 an hour and 5.4 kW about $0.98 an hour at 18.19 cents per kWh (2.7 × 0.1819 = 0.49; 5.4 × 0.1819 = 0.98). The spike is limited to the hours below your balance point, and a dual-fuel system blunts it by burning gas instead.

Why does my heat pump blow cooler air in winter?

A heat pump delivers air at a lower temperature than a furnace. NRCan gives typical heat pump air temperatures of 25°C to 45°C (77°F to 113°F)[6], against 55°C to 60°C (131°F to 140°F)[6] for a furnace. During a defrost cycle the heat pump is cooling the air in the ducts[6], so the air can feel cool until it ends.

Sources & References

  1. ENERGY STAR: Air Source Heat Pump Key Product Criteria (split and single-package minimums, cold climate HSPF2, COP at 5°F, capacity at 5°F, definitions of HSPF2 and COP)
  2. ENERGY STAR: Air-Source Heat Pumps (cold weather, testing down to 5°F, backup and dual fuel, Manual J sizing, up to three times more heat)
  3. NEEP: Cold Climate Air Source Heat Pump Specification, Version 4.0 (IECC climate zone 4 and higher; heating capacity, power and COP reported at 47°F, 17°F and 5°F and the lowest cataloged outdoor dry bulb)
  4. U.S. EIA: U.S. Price of Natural Gas Delivered to Residential Consumers, annual (2025: $15.34 per thousand cubic feet; released October 30, 2026)
  5. U.S. EIA: Heat Content of Natural Gas Delivered to Consumers (U.S., 2025: 1,036 Btu per cubic foot)
  6. Natural Resources Canada: Heating and cooling with a heat pump (heat in cold air, thermal balance point, minimum operating temperature, defrost cycle, supplementary heat, sizing, set-points and setbacks, supply air temperatures; modified December 24, 2025)
  7. U.S. DOE Building America Solution Center (PNNL): Cold Climate Heat Pump Sizing and Selection (balance point, electric resistance backup, sizing approaches; updated May 14, 2024)
  8. ENERGY STAR: Design Temperature Limits for Residential New Construction (ACCA Manual J 99% heating season design temperature)
  9. NYS Clean Heat: ASHP Field Assessment Hot List (May 2025; snow protection, risers and stands, defrost drainage)
  10. U.S. DOE: Energy Saver Guide 2022 (heat pumps in all climates, cold-climate heat pumps, about 50% less heating electricity than electric furnaces and baseboards, heat pump setback tip)
  11. U.S. EIA: Electric Power Monthly, Table 5.6.B, average price of electricity to residential customers, year to date (January to August 2026: 18.19 cents per kWh)
  12. U.S. EIA: British thermal units (1 kWh = 3,412 Btu; 1 therm = 100,000 Btu)
  13. ENERGY STAR: Furnaces Key Product Criteria (gas furnaces 95% AFUE in the U.S. South, 97% in the North)