A heat pump has two jobs, and they pull the size in different directions. In summer it's an air conditioner and should be sized to the cooling load. In winter its heating output falls as the outdoor temperature drops, just when the house needs the most heat.
Where winters are mild, cooling decides the size. Where they're cold, heating does, and the question becomes how much backup heat covers the coldest hours.
The calculator below handles both seasons. Its heating side uses the same heat-loss model as our furnace size calculator, and every example on this page comes from the calculator itself.
In this page's calculator, a 2,000 sq ft two-story home with 1980s and 1990s insulation in a mixed climate like Virginia or North Carolina (15°F design low) loses about 28,500 BTU per hour on the coldest night and needs about 2.4 tons of cooling. A standard 2.5-ton heat pump heats that house on its own down to about 26.5°F, the calculator finds, and roughly 3.7 kW of backup heat covers the rest. In a cold climate, a cold-climate model sized toward the heating load needs less backup than a standard one.
Heat Pump Size Calculator
Right capacity for heating AND cooling.
How the calculator sizes a heat pump
Heating load = heat loss rate × square footage × adjustments × (70°F − your design low). The heat loss rate depends on the home's age and insulation:
| Home built | Heat loss rate (BTU/hr per °F per sq ft) |
|---|---|
2020 or later | 0.177 |
2000 to 2019 | 0.189 |
1980 to 1999 | 0.270 |
Before 1980 | 0.604 |
The newest level uses the 2021 IECC's insulation and window limits for climate zone 4[4]. The others are calculator assumptions for typical houses of those eras, the same four bands the furnace calculator uses; homes built before 1980 take the pre-1970 rate. Two stories of the same floor area lose slightly less heat (0.96), three stories 0.94, and more window area adds to the load.
Cooling load starts at 850 square feet per ton, the middle of the 800 to 900 square feet per ton[10] that SPEER cites from ACCA for systems designed with Manuals J, D and S, the same anchor as our AC tonnage calculator. A region factor, home age, stories and windows adjust it, and each occupant beyond two adds 400 BTU per hour, all calculator assumptions.
Size: standard, ENERGY STAR and premium heat pumps are sized to the cooling load, at 95% to 115%, 120% or 130% of it by compressor type (single-stage, two-stage, variable), a calculator assumption. A cold-climate heat pump follows a sizing approach the Department of Energy's Building America Solution Center describes: it is sized to the design heating load, rounded up to the next half ton, and its minimum output is checked against the cooling load[11]. The calculator takes that minimum as 30% of rated capacity[12], the turndown DOE's ductless brief gives for most inverter-driven units and a calculator assumption for any one model.
Design lows by region, as the calculator sets them:
| Region | States with the most counties | Design low |
|---|---|---|
| Hot-Humid | TX, GA, FL | 30°F |
| Hot-Dry | TX, CA, AZ | 30°F |
| Marine | OR, WA, CA | 25°F |
| Mixed-Humid | VA, KY, TN | 15°F |
| Mixed-Dry | TX, NM, CA | 15°F |
| Cold | IA, NE, MI | 0°F |
| Very Cold | MN, ND, CO | −10°F |
Building America's Subarctic region is seven areas in Alaska and uses the Very Cold row. Denali is IECC zone 8 but Very Cold in Building America's data. Zone 3A counties fall in Hot-Humid or Mixed-Humid, and the lookup uses each county's own region.
Heating capacity in cold weather
A heat pump's rated heating capacity is measured at 47°F outdoors[1]. It produces less as it gets colder, and the calculator models that drop:
- Standard heat pumps: about 60% of rated capacity at 17°F and 40% at 5°F, a calculator assumption.
- Cold-climate heat pumps: about 79% at 17°F, a calculator assumption; at 5°F it uses 70%[1], the minimum ENERGY STAR requires for its cold-climate designation, rather than a more optimistic figure.
Balance point and backup heat
The balance point is the outdoor temperature where the heat pump's falling capacity meets the house's rising heat loss. Above it, the heat pump heats the house alone. Below it, something else has to add heat: electric resistance strips in the air handler, or a gas furnace in a dual-fuel system.
The calculator draws the house's heat loss as a straight line from zero at 65°F, where it assumes no heat is needed, to the full load at your design low. It finds the balance point where that line meets the heat pump's capacity curve and sizes backup heat to the gap at your design low, plus a 10% margin for cold snaps (calculator assumptions). Its balance point is an estimate; the real one depends on the house and the specific model.
Three examples from the calculator
Each example is computed with this page's calculator for a 2,000 sq ft two-story home built between 1980 and 1999, with average windows and four occupants.
The annual cost is the calculator's own estimate at $0.18 per kWh, about the EIA's 2026 national average[9]: cooling and heating energy each equal the load times the climate's equivalent full-load hours, divided by the unit's SEER2 or HSPF2. Those equivalent full-load hours are a calculator assumption that varies by region, so treat the cost as directional.
Example 1: mixed-humid climate (15°F design low, a calculator assumption), ENERGY STAR heat pump:
- Heating load: 0.270 × 2,000 × 0.96 × 55°F = 28,512 BTU/hr
- Cooling load: 2,000 ÷ 850 × 12,000 + 800 for two occupants beyond two = 29,035 BTU/hr, or 2.42 tons
- Size: the calculator lands on 2.5 tons, set by cooling (103% of the cooling load)
- Balance point: the calculator finds about 26.5°F, with about 3.7 kW of backup at the design low
- Annual heating and cooling cost: the calculator estimates $1,660 at $0.18/kWh
Example 2: cold climate (0°F design low, a calculator assumption), cold-climate heat pump:
- Heating load: 0.270 × 2,000 × 0.96 × 70°F = 36,288 BTU/hr
- Cooling load: the calculator finds 25,002 BTU/hr, or 2.08 tons
- Size: the calculator lands on 3.5 tons, the heating load (3.02 tons) rounded up; its assumed minimum output, 1.05 tons (3.5 × 0.30), is below the 2.08-ton cooling load
- Balance point: the calculator finds about 9.5°F, with about 2.7 kW of backup at the design low
- Annual cost: the calculator estimates $2,156
Example 3: very cold climate (−10°F design low, a calculator assumption), cold-climate heat pump:
- Heating load: 0.270 × 2,000 × 0.96 × 80°F = 41,472 BTU/hr
- Cooling load: the calculator finds 22,313 BTU/hr, or 1.86 tons
- Size: the calculator lands on 3.5 tons, the heating load (3.46 tons) rounded up; its assumed minimum output, 1.05 tons, is below the 1.86-ton cooling load
- Balance point: the calculator finds about 9°F, with about 5.4 kW of backup at the design low
- Annual cost: the calculator estimates $3,086
In the cold examples the heating load sets the size, as the Department of Energy's Building America Solution Center describes: size a cold-climate heat pump to the design heating load, and choose one whose minimum cooling capacity is at or below the design cooling load[11]. DOE calls electric resistance backup an inefficient and typically expensive form of heat that should be minimized in all cases[11]. NEEP's cold-climate specification has makers report each listed model's capacity at 5°F[7], so a contractor can check a specific unit against the heating load.
Efficiency tiers in the calculator
| Tier | Ratings | What it means |
|---|---|---|
Code minimum | 14.3 SEER2, 7.5 HSPF2[8] | Federal requirement for split heat pumps since 2023[8] |
ENERGY STAR | 15.2 SEER2, 7.8 HSPF2, 11.0 EER2[1] | ENERGY STAR minimum for split systems |
Premium inverter | 18 SEER2, 9.5 HSPF2 | Variable-speed compressor |
Cold climate | 16 SEER2, 10.0 HSPF2 | Tested for low-temperature performance |
ENERGY STAR's cold-climate designation requires a COP of at least 1.75 at 5°F[1], at least 70% of rated heating capacity at 5°F[1], and at least 8.1 HSPF2[1] for ducted split systems (8.5 for ductless)[1]. NEEP's cold-climate specification asks manufacturers to report heating capacity and COP at 47°F, 17°F and 5°F[7], so its product list is a useful place to compare specific units.
When to get a Manual J
This calculator uses typical houses. A Manual J load calculation measures your walls, windows and air leakage room by room, and ACCA's Manual S matches the equipment to that load.
ENERGY STAR advises having the contractor verify the size with a Manual J[2]. For a heat pump in a cold climate, also ask for the model's capacity at your design low, not just its rated tonnage.
Frequently asked questions
What size heat pump do I need for a 2,000 square foot house?
In a mixed climate, about 2.5 tons in this page's calculator, sized for cooling. In a cold climate a 1980s or 1990s house of that size loses about 36,000 to 41,000 BTU/hr at 0°F to −10°F; sized to that heating load, as DOE's Building America guidance describes[11], a cold-climate model comes to 3.5 tons here, with about 2.7 to 5.4 kW of backup at the design low.
Should a heat pump be sized for heating or cooling?
For cooling where winters are mild, since the heating load there is small. For heating where winters are cold, within a limit: DOE's guidance is to choose a unit whose minimum cooling capacity is at or below the design cooling load[11].
How much backup heat does a heat pump need?
Enough to cover the gap between the heat pump's output and the house's heat loss at your design low. In the worked examples above, that's about 3.7 kW in a mixed climate and 2.7 to 5.4 kW in cold climates with a cold-climate heat pump.
Do heat pumps work in cold weather?
Yes, with the right model. ENERGY STAR's cold-climate criteria require performance measured at 5°F[1], and NEEP's cold-climate specification also asks manufacturers to report performance at the lowest outdoor temperature they catalog[7]. ENERGY STAR says a cold climate heat pump keeps working below 5°F[2], and that pairing it with backup heat heats the home most efficiently when temperatures drop even lower[2].
What is a heat pump balance point?
The outdoor temperature where the heat pump's output equals the house's heat loss. Below it, backup heat makes up the difference.
Sources & References
- ENERGY STAR: Heat Pump Key Product Criteria (incl. cold climate)
- ENERGY STAR: Air-Source Heat Pumps (Manual J sizing; a cold climate heat pump keeps working below 5°F; pairing with backup heat heats the home most efficiently when temperatures are even lower)
- NEEP: Cold Climate Air Source Heat Pump List
- ICC: 2021 International Energy Conservation Code
- ACCA: Manual J, Residential Load Calculation
- ACCA: Manual S, Residential Equipment Selection
- NEEP: Cold Climate Air Source Heat Pump Specification, version 4.0 (heating capacity, power and COP reported at 47°F, 17°F and 5°F and the lowest cataloged outdoor dry bulb)
- 10 CFR 430.32(c)(5): split-system heat pumps made on or after January 1, 2023 must reach 14.3 SEER2 and 7.5 HSPF2
- U.S. EIA: Electric Power Monthly, Table 5.6.B (U.S. residential average 18.19 cents per kWh, January to August 2026)
- SPEER: Factsheet: HVAC Sizing (ACCA: systems designed with Manuals J, D and S should usually have at least 800-900 square feet per ton)
- U.S. DOE Building America Solution Center: Cold Climate Heat Pump Sizing and Selection (last updated May 14, 2024; size to all or most of the design heating load, minimum cooling capacity at or below the design cooling load; electric resistance backup is inefficient and typically expensive)
- U.S. DOE Building America Solution Center: Ductless Mini-Split Heat Pumps code compliance brief (inverter-driven compressors adjust capacity, most down to about 30% of rated capacity)
Related Articles
Heat Pumps: A Homeowner's Guide to Cost, Efficiency and Cold Weather
Guide • 24 min read
Furnace Size Calculator: What Size Furnace Do I Need?
Calculator • 13 min read
AC Tonnage Calculator Per Square Foot (+Sizing Chart)
Calculator • 17 min read
Mini Split Sizing Calculator: What BTU Mini Split Do I Need?
Calculator • 14 min read
Heat Pump Installation Cost by System Type
Cost guide • 13 min read