DOE warns against casual sizing estimates based on a home's floor area and says over-sizing is very common[10]: in a large survey its fact sheet cites, nearly 40 percent[10] of contractors said they oversized equipment on purpose.

This calculator sizes a furnace from heat loss instead: how much heat your house loses per degree of temperature difference, times the difference between indoors and your coldest typical night. Every chart and example on this page comes from the same model, so the page and the calculator agree.

The calculator estimates that a 2,000 sq ft home with typical 1980s and 1990s insulation, in a climate with a 10°F design low (its assumption for a zone 4 climate), loses about 36,000 BTU per hour on the coldest night, so a 40,000 BTU furnace at 95% efficiency covers it. Use the result to check a quote, and ask the contractor for a Manual J load calculation before you buy.

Furnace Sizing Calculator

Manual J–style heat-load estimate.

1

Your home

Size, layout, and how it's built

sq ft

More stories = smaller envelope per floor = slightly less heat loss.

5% (very few)15% (typical)50% (glass walls)
2

Your climate

Local winter severity

Climate zone

Zone 4, Mixed: for example New York City, Seattle.

See the full climate zone map
Heating degree days: 4,500
Design temp: 10°F
Heating season: 5–6 months

Design temperature and heating season are calculator assumptions for zone 4 (Mixed); heating degree days use the shared per-zone assumption.

3

Your furnace preference

Efficiency tier and where the ducts run

Enter your values and click Calculate, press Enter in any field.

Input BTU vs. output BTU

The calculator treats furnace sizes as input ratings: how much fuel energy the furnace burns per hour. What heats the house is the output: AFUE is the ratio of the useful heat delivered to the fuel energy put in over a year[11], so output is input times AFUE.

An 80,000 BTU furnace at 80% AFUE delivers 64,000 BTU per hour (80,000 × 0.80); the same input at 95% AFUE delivers 76,000 (80,000 × 0.95). The calculator works out the output your house needs, then the input that delivers it at the efficiency you choose.

Four-step diagram of the furnace calculator: heat loss rate by insulation era, times square footage and adjustments, times 70°F minus the design low, divided by AFUE and rounded up; a 1,500 sq ft 1990s ranch needs a 40,000 BTU furnace.
The calculator's method, with example 1 from below.

How the calculator works

Design heat loss = heat loss rate × square footage × adjustments × (70°F − your design low).

The heat loss rate depends on how well the house is insulated and sealed. The calculator's four levels come from an assumed reference house, 2,000 sq ft and one story with 8-foot ceilings and windows equal to 15% of the floor area (calculator assumptions):

Insulation levelWhat it representsHeat loss rate (BTU/hr per °F per sq ft)
Excellent
Current code: the 2021 IECC's climate zone 4 insulation and window limits, tight construction, mechanical ventilation
0.177
Good
2000s construction: better walls and attic, double-pane low-E windows
0.189
Average
1980s and 1990s: R-13 walls, R-30 attic, double-pane windows
0.270
Poor
Before 1970: little or no wall insulation, thin attic insulation, single-pane windows, drafty
0.604
Calculator assumption. The per-square-foot heat-loss rates this page's calculator uses by insulation era; the page labels the older rows its assumptions for typical houses of those eras, and the Excellent row the 2021 IECC zone 4 U-factors.

The "Excellent" row uses the 2021 IECC's maximum U-factors for climate zone 4: windows 0.30[1], ceilings 0.024, walls 0.045, floors 0.047.[1] The older rows are calculator assumptions for typical houses of those eras. The model's other calculator assumptions are tested air leakage of 3, 5, 8 and 15 air changes per hour at 50 pascals for the four levels, actual leakage on a cold night at 1/15 of that, and a floor over an unheated basement or crawlspace that sees 50% of the indoor-outdoor difference.

Adjustments then scale the result:

AdjustmentOptions and multipliers
Ceiling height
8 ft 1.00 · 9 ft 1.06 · 10 ft 1.13 · 12 ft or more 1.25
Stories
Two stories 0.96 · three stories 0.94 (a taller house of the same floor area loses slightly less)
Windows
Plus 1.5% for each percentage point of window area above 15% of the floor
Ducts
Inside the heated space 1.00 · insulated attic 1.10 · crawlspace 1.18 · uninsulated attic 1.28
Basement
Heated 1.10 · slab 1.05 · unheated 1.00
Calculator assumption. The ceiling, story, window, duct and basement multipliers this page's calculator applies to the heat-loss rate.

The calculator has no sun input; it sizes for the design low. It divides the output by your furnace's AFUE and picks the smallest size in its list (a calculator assumption) that covers it: 40,000, 60,000, 80,000, 100,000, 120,000 or 140,000 BTU input. When even a 40,000 BTU furnace delivers more than 1.4 times the load (the calculator's flag, an assumption), it says so.

Furnace size chart for a 2,000 sq ft home

Furnace input, computed with this page's calculator at 95% AFUE, one story, 8-foot ceilings, ducts in an insulated attic and an unheated basement:

Insulation40°F30°F20°F10°F0°F−10°F−30°F
Excellent
40,000*
40,000*
40,000*
40,000*
40,000
40,000
60,000
Good
40,000*
40,000*
40,000*
40,000*
40,000
40,000
60,000
Average
40,000*
40,000*
40,000
40,000
60,000
60,000
80,000
Poor
60,000
60,000
80,000
100,000
100,000
120,000
140,000
How this was calculated: heat-loss rate times 2,000 square feet times a 1.10 duct factor times (70 minus the assumed design low), divided by 0.95 AFUE and rounded up to the next common input size.

Column headings are the calculator's assumed design low for each zone, not a fixed value for any one place. * Even the smallest furnace in the calculator's list delivers more than 1.4 times the load; ask the contractor about two-stage and modulating models.

By home size

Computed with this page's calculator at average insulation, a 10°F design low and 95% AFUE:

Home sizeHeat neededFurnace input
1,000 sq ft
17,820 BTU/hr
40,000*
1,500 sq ft
26,730 BTU/hr
40,000*
2,000 sq ft
35,640 BTU/hr
40,000
2,500 sq ft
44,550 BTU/hr
60,000
3,000 sq ft
53,460 BTU/hr
60,000
3,500 sq ft
62,370 BTU/hr
80,000
How this was calculated: 0.270 heat-loss rate times square footage times a 1.10 duct factor times a 60 degree difference (70 minus an assumed 10 degree design low), with input rounded up at 95 percent AFUE.
Bar chart of modeled heat loss per square foot at a 10°F design low: about 12 BTU per hour for current-code and 2000s homes, about 18 for 1980s and 1990s homes and about 40 for a drafty pre-1970 house.
Modeled heat loss per square foot by insulation era, from about 12 to about 40 BTU per hour.

Heat loss per square foot by insulation level

DOE warns against sizing from floor area alone[10], because the heat a house loses per square foot depends on how it's built. At a 10°F design low with ducts in an insulated attic, the calculator models heat loss at:

  • About 12 BTU/hr per sq ft for current-code and 2000s homes (0.177 × 1.10 × 60 ≈ 11.7; 0.189 × 1.10 × 60 ≈ 12.5).
  • About 18 BTU/hr per sq ft for 1980s and 1990s homes (0.270 × 1.10 × 60 ≈ 17.8).
  • About 40 BTU/hr per sq ft for a drafty pre-1970 house (0.604 × 1.10 × 60 ≈ 39.9).

DOE's right-sizing fact sheet lists what oversizing costs: higher first cost, lower efficiency, higher energy costs and possibly less comfort; more starts and stops, which accelerate wear and can lead to premature failure; and more blower fan power, often with more duct leakage from higher duct pressures[10].

Three worked examples

Example 1: a 1,500 sq ft 1990s ranch where winter lows reach 0°F, average insulation, ducts in an insulated attic:

  • 0.270 × 1,500 × 1.10 (ducts) × 70°F = 31,185 BTU/hr
  • At 95% AFUE: 32,826 BTU input → a 40,000 BTU furnace
  • Estimated gas use: the calculator estimates about 732 therms a year with the gas formula below, or $1,083 at EIA's average U.S. residential gas price for 2025, $15.34 per thousand cubic feet[8], about $1.48 a therm at 1,036 Btu a cubic foot[9] (732 × 1.48), using 6,500 heating degree days (its assumption for a zone 5 climate)

Example 2: a new 2,400 sq ft two-story home, 9-foot ceilings, windows at 18% of the floor, ducts inside the heated space, 10°F design low (the calculator's zone 4 assumption):

  • 0.177 × 2,400 × 1.06 (ceilings) × 0.96 (two stories) × 1.045 (windows) × 60°F = 27,104 BTU/hr
  • At 95% AFUE: 28,531 BTU input → a 40,000 BTU furnace, which delivers more than 1.4 times the load, so the calculator flags it; ask the contractor about two-stage and modulating models

Example 3: an 1,800 sq ft 1950s bungalow where lows reach −10°F, little insulation, ducts in an uninsulated attic:

  • 0.604 × 1,800 × 1.28 (ducts) × 80°F = 111,329 BTU/hr
  • At 95% AFUE: 117,188 BTU input → a 120,000 BTU furnace

Air seal and insulate the same bungalow to the "average" level and insulate its ducts, and the calculator finds the load falls to 42,768 BTU/hr (0.270 × 1,800 × 1.10 × 80): a 60,000 BTU furnace. Estimated gas use drops from about 2,813 to 1,080 therms a year, using 8,000 heating degree days (the calculator's assumption for a zone 6 climate). Weatherizing before replacing the furnace can shrink the furnace you need by half (120,000 to 60,000 BTU).

Efficiency changes the size you need

Because the calculator sizes by output, a less efficient furnace needs a bigger input rating for the same house. The 2,000 sq ft average-insulation home at a 10°F design low, computed with this page's calculator:

AFUEFurnace inputGas per yearCost at $1.48/therm (EIA 2025 average)
80%
60,000
802 therms
$1,187
90%
40,000
713 therms
$1,055
95%
40,000
675 therms
$999
98%
40,000
655 therms
$969
How this was calculated: annual gas = heat-loss rate times square footage times adjustments times 4,500 assumed heating degree days times 24 divided by (AFUE times 100,000); cost at $1.48 per therm, EIA's 2025 U.S. residential average.

Annual gas = heat loss rate × square footage × adjustments × heating degree days × 24 ÷ (AFUE × 100,000). This example uses 4,500 heating degree days, the calculator's assumption for a mixed zone 4 climate, and a 1.10 duct factor, which is why its therm figures differ from the AFUE and heating-cost pages.

Under the Department of Energy’s rule, non-weatherized and mobile-home gas furnaces manufactured on or after December 18, 2028 must reach 95% AFUE[4], so condensing furnaces become the standard. In June 2026[3] the Supreme Court vacated the appeals-court decision that upheld the rule; the rule stays in place while the DC Circuit reconsiders the case. In February 2026[4] the American Gas Association, the American Public Gas Association and the National Propane Gas Association asked DOE to move that date to at least January 1, 2030[4]; DOE published the petition for comment on April 27, 2026[4], and the rule still stands.

See our furnace guide for the rest of the rule.

When to get a Manual J

The calculator uses one reference house shape. Small homes lose a little more heat per square foot, large homes a little less, and your actual walls, windows and air leakage may not match any of the four levels.

A Manual J load calculation measures them room by room, and ACCA's Manual S then matches equipment to that load. For a furnace replacement, ask the contractor for both, and compare their load with this estimate.

Frequently asked questions

What size furnace do I need for a 2,000 square foot house?

With average 1980s or 1990s insulation, the calculator lands on about 40,000 BTU input at 95% AFUE where design lows are 10°F or warmer, and 60,000 where they reach 0°F. A drafty, poorly insulated older house can need 100,000 or more.

What size furnace for a 1,500 square foot house?

The calculator finds a 40,000 BTU furnace covers an average-insulation 1,500 sq ft house even at a 0°F design low (example 1 above). In a mild climate even that is more than the house needs; ask the contractor about two-stage and modulating models.

Is a bigger furnace better?

No. DOE says oversized equipment costs more up front, runs less efficiently, may compromise comfort, and starts and stops more often, which accelerates wear[10]. The goal is the smallest furnace that covers the coldest-night heat loss.

Should I replace my furnace with the same size?

Not automatically. DOE says over-sizing is very common[10], and added insulation or new windows lower the load an old furnace was sized for. Run the calculator and ask for a Manual J.

How many BTU per square foot do I need for heating?

It depends on insulation and climate. At a 10°F design low, the calculator models about 12 BTU/hr per sq ft for a current-code home, about 18 for a 1980s or 1990s home, and about 40 for a drafty pre-1970 house.

Sources & References

  1. ICC: 2021 International Energy Conservation Code, Table R402.1.2 (climate zone 4 maximum U-factors: fenestration 0.30, ceiling 0.024, frame wall 0.045, floor 0.047)
  2. U.S. DOE: Final energy efficiency standards for residential furnaces (non-weatherized and mobile-home gas furnaces must reach 95 percent AFUE from late 2028)
  3. HARDI: Supreme Court vacates 95% furnace decision; rule remains in place (June 8, 2026)
  4. Federal Register: DOE Notification of Petition for Rulemaking, doc. 2026-08145, 91 FR 22477 (published Apr. 27, 2026; DOE received the AGA, APGA and NPGA petition Feb. 19, 2026, to move the 2028 furnace rule date to at least Jan. 1, 2030)
  5. ACCA: Manual J, Residential Load Calculation
  6. ACCA: Manual S, Residential Equipment Selection
  7. PNNL-33270: Guide to Determining Climate Zones by County (2021 IECC), for the U.S. DOE
  8. U.S. EIA: U.S. Price of Natural Gas Delivered to Residential Consumers, annual (2025: $15.34 per thousand cubic feet; released October 30, 2026)
  9. U.S. EIA: Heat Content of Natural Gas Delivered to Consumers (U.S., 2025: 1,036 Btu per cubic foot)
  10. U.S. DOE: Right-Size Heating and Cooling Equipment, Technology Fact Sheet (DOE/GO-102002-1490, January 2002): beware of casual sizing estimates based on floor area; over-sizing is very common; nearly 40 percent of surveyed contractors oversized on purpose; what oversizing costs; insist on documented ACCA Manual J calculations
  11. 10 CFR 430.23(n) (Cornell LII): AFUE is the ratio of the annual fuel output of useful energy delivered to the heated space to the annual fuel energy input
  12. U.S. DOE Energy Saver: Furnaces and Boilers (archived copy of October 1, 2025; DOE has since retired the page): with 90% AFUE, 10% of the fuel's energy escapes up the chimney and elsewhere
  13. EPA: Greenhouse Gas Equivalencies Calculator, calculations and references (natural gas 0.0053 metric tons CO2 per therm, about 11.7 lb)
  14. Federal Register: DOE, Energy Conservation Standards for Consumer Furnaces, final rule, 88 FR 87502 (December 18, 2023): installation adders for condensing furnaces, including PVC flue and combustion-air venting, an orphaned water heater and condensate removal
  15. National Laboratory of the Rockies (formerly NREL): National Residential Efficiency Measures Database (REMDB), version 4.0.0 (April 2025), Furnaces (gas-furnace equipment swap, retrofit, 2023 dollars: 80% AFUE below 95% AFUE at each size)

Related Articles