A heat pump moves heat instead of making it, so it can deliver more heat than the electricity it uses. The coefficient of performance (COP) measures that ratio, and it's the number that decides what a heat pump costs to run.

COP is the heat a heat pump delivers divided by the electricity it uses, a pure number with no units[1]. Natural Resources Canada puts typical air-source COPs at 2.0 to 5.4 at 8°C (46°F)[2] and 1.1 to 3.7 at −8°C (18°F)[2], and ENERGY STAR's cold-climate tier needs at least 1.75 at 5°F[1]. Dividing an HSPF2 rating by 3.412 gives a seasonal COP, so ENERGY STAR's 7.8 HSPF2 minimum[1] is 7.8 ÷ 3.412 = 2.29.

A heat pump using 1 kW of electricity and 2 kW from the outdoor air to deliver 3 kW of heat, a COP of 3, beside typical air-source COPs at 46°F and 18°F, ENERGY STAR's 1.75 at 5°F and resistance heat's 1.
Natural Resources Canada's example and ranges, with ENERGY STAR's cold-climate floor.

The formula

ENERGY STAR's heat pump criteria define COP as "the ratio of the average rate of space heating delivered to the average rate of electrical energy consumed by the heat pump"[1], and add that "COP is a dimensionless quantity"[1]. Natural Resources Canada's example: a heat pump that uses 1 kW of electricity to move 3 kW of heat has a COP of 3[2].

That's the sense of ENERGY STAR's line that a heat pump "can deliver up to three times more heat energy to a home than the electrical energy it consumes"[3]. Electric resistance heat turns each kilowatt-hour into exactly a kilowatt-hour of heat, a COP of 1 by the same formula.

For cooling, the same idea is written in Btu per watt-hour. EER2 is "the ratio of the average rate of space cooling delivered to the average rate of electrical energy consumed by the heat pump," expressed in Btu/Wh[1], and SEER2 is a season's heat removed in Btu over its electricity in watt-hours[1]. One kilowatt-hour is 3,412 Btu[4], so a watt-hour is 3,412 ÷ 1,000 = 3.412 Btu, and any of these ratings ÷ 3.412 = a COP.

How temperature changes COP

Natural Resources Canada explains that COPs drop as the outdoor air gets colder, because the heat pump has to work across a bigger temperature difference between indoors and outdoors[2]. Its typical ranges for air-source units:

Outdoor temperatureTypical air-source COP
8°C (46°F)
2.0 to 5.4
−8°C (18°F)
1.1 to 3.7
Source: Natural Resources Canada, Heating and cooling with a heat pump (page modified December 24, 2025). Fahrenheit values converted from the Celsius figures. View the source.

Physics also sets a ceiling, the Carnot limit: the delivered temperature divided by the temperature gap to the source, both in kelvin. Natural Resources Canada says air-to-air heat pumps normally heat air to between 25°C and 45°C[2], so the table below assumes 95°F (35°C) supply air.

Outdoor temperatureMaximum possible COP, delivering 95°F air
47°F
11.56
35°F
9.24
17°F
7.11
5°F
6.16
−5°F
5.55
How this was calculated: Carnot limit = delivered absolute temperature ÷ (delivered temperature − outdoor temperature), with 95°F = 308.15 K; for example 308.15 ÷ (308.15 − 281.48) = 11.56 at 47°F (281.48 K). The 95°F supply temperature is an assumption inside Natural Resources Canada's 25°C to 45°C range.

Real heat pumps sit well under the ceiling. At −8°C the limit is 308.15 ÷ (308.15 − 265.15) = 7.17, so the top of Natural Resources Canada's range, 3.7, is about half of it (3.7 ÷ 7.17 = 52%). ENERGY STAR certifies air-source models with testing down to 5°F[3]; see heat pumps in cold weather.

Instantaneous COP vs seasonal COP (SCOP)

A COP describes one operating point: ENERGY STAR's definition requires its rates to come "from a single test" or a single set of operating conditions[1]. That's the kind of figure quoted at 47°F or 5°F[1].

A seasonal metric averages a whole season. Natural Resources Canada describes seasonal metrics as giving a better estimate of performance over a heating or cooling season, because they include real-life temperature swings[2].

  • SCOP (Europe): the EU's air conditioner rules define the seasonal coefficient of performance as "the overall coefficient of performance of the unit, representative for the whole designated heating season," calculated as the reference annual heating demand divided by the annual electricity used for heating[5]. The regulation sets three heating seasons for it: average, colder and warmer[5].
  • HSPF2 (United States): "the total space heating required in region IV during the space heating season, expressed in Btu, divided by the total electrical energy consumed by the heat pump system during the same season, expressed in watt-hours"[1]. Divided by 3.412, it's a seasonal COP for that rating climate.

The two seasonal numbers come from different climates and test methods, so an EU SCOP and an HSPF2-based COP don't compare one to one. Compare heat pumps on the same metric.

COP and other ratings

RatingWhat it measuresAs a COP (rating ÷ 3.412)
HSPF2
Seasonal heating, Btu per watt-hour
Federal minimum 7.5 = 2.20; ENERGY STAR 7.8 = 2.29
SEER2
Seasonal cooling, Btu per watt-hour
Federal minimum 14.3 = 4.19; ENERGY STAR 15.2 = 4.45
EER2
Cooling at one rating condition, Btu per watt-hour
ENERGY STAR 11.0 = 3.22
How this was calculated: each COP is the rating ÷ 3.412 Btu per watt-hour (EIA: 1 kWh = 3,412 Btu); for example 7.8 ÷ 3.412 = 2.29. Ratings: ENERGY STAR Heat Pump Key Product Criteria (split systems: 7.8 HSPF2, 15.2 SEER2, 11.0 EER2) and 10 CFR 430.32(c)(5), split heat pumps made from January 1, 2023 (14.3 SEER2, 7.5 HSPF2). View the ENERGY STAR criteria.

The federal minimums for split heat pumps made from January 1, 2023 are 14.3 SEER2 and 7.5 HSPF2[6], and ENERGY STAR's split-system floors are 15.2 SEER2, 7.8 HSPF2 and 11.0 EER2[1].

Reading COP off a spec sheet

U.S. ratings for central heat pumps are SEER2, EER2 and HSPF2[1], which you convert by dividing by 3.412. Take a listing showing 15.2 SEER2, 11.0 EER2 and 7.8 HSPF2: 15.2 ÷ 3.412 = 4.45 for seasonal cooling, 11.0 ÷ 3.412 = 3.22 at the EER2 rating point, and 7.8 ÷ 3.412 = 2.29 for seasonal heating.

A COP printed on its own needs its test temperature beside it. ENERGY STAR's cold-climate tier requires a COP of at least 1.75 at 5°F[1], measured in the federal test's H4₂ condition, plus at least 70% of the 47°F heating capacity at 5°F[1]. NEEP's cold-climate specification has makers report capacity, power and COP at 47°F, 17°F and 5°F[7], which gives the clearest picture of how a model holds up as it gets colder.

Ground-source heat pumps and COP

A ground-source (geothermal) heat pump draws heat from the ground instead of outdoor air. The DOE says the ground stays between about 50°F[8] and 59°F year-round at about 30 feet down[8], so the temperature gap is smaller exactly when an air-source unit struggles most.

The ceiling shows the size of the advantage: delivering 95°F air from 50°F ground gives 308.15 ÷ (308.15 − 283.15) = 12.33, against 6.16 from 5°F outdoor air. ENERGY STAR's geothermal criteria ask for a COP of at least 3.6 from closed-loop water-to-air units and 4.1 from open-loop ones[9], rated under a different test than air-source HSPF2[9], and the DOE's geothermal guide puts their efficiency at 300% to 600% on the coldest winter nights[10], a COP of 3 to 6 (300% ÷ 100 = 3).

Our air-source vs. ground-source comparison runs the same house on ENERGY STAR's 3.6 against 2.40 for an 8.2 HSPF2 air-source model (8.2 ÷ 3.412 = 2.40).

What COP means for your bill

A million Btu of heat is 1,000,000 ÷ 3,412 = 293.08 kWh[4], so the cost per million Btu of heat is 293.08 kWh × your electricity rate ÷ COP. At 18.19 cents per kWh, the U.S. residential average for January to August 2026[11]:

COPCost per million Btu of heat
1.0 (resistance)
$53.31
1.75
$30.46
2.29 (7.8 HSPF2)
$23.32
3.0
$17.77
4.0
$13.33
How this was calculated: cost per million Btu = 293.08 kWh × $0.1819 ÷ COP (EIA: 3,412 Btu per kWh; Electric Power Monthly Table 5.6.B, U.S. residential, January to August 2026); for example 293.08 × 0.1819 ÷ 3.0 = $17.77. The 7.8 HSPF2 row divides by the unrounded 7.8 ÷ 3.412 = 2.286.

A 95% gas furnace at EIA's average U.S. residential gas price for 2025, $15.34 per thousand cubic feet[12], about $1.48 a therm at 1,036 Btu a cubic foot[13], delivers heat for about $15.58 per million Btu (14.80 ÷ 0.95). At average prices a heat pump needs a seasonal COP of about 3.4 to beat it (53.31 ÷ 15.58 = 3.42); see gas vs. electric heating cost.

Frequently asked questions

What is a good COP for a heat pump?

Natural Resources Canada puts typical air-source COPs at 2.0 to 5.4 at 8°C (46°F)[2], so a figure toward the top of that range is a strong mild-weather number. ENERGY STAR's cold-climate minimum is 1.75 at 5°F[1].

Over a season, ENERGY STAR's 7.8 HSPF2 floor[1] works out to 7.8 ÷ 3.412 = 2.29.

How do I convert HSPF2 to COP?

Divide by 3.412, the Btu in a watt-hour[4]. ENERGY STAR's cold-climate floor for ducted units, 8.1 HSPF2[1], is 8.1 ÷ 3.412 = 2.37.

What does a COP of 3 mean?

Three units of heat for each unit of electricity: 1 kWh in, 3 kWh of heat out, or 3 × 3,412 = 10,236 Btu[4]. The DOE writes the same idea as an efficiency of 300%[10].

Can COP be less than 1?

Not while a heat pump is drawing heat from outdoors: the heat it delivers is that heat plus the electricity it uses, so the ratio can't fall below one. Natural Resources Canada's lowest typical figure at −8°C is 1.1[2].

During defrost the unit runs in cooling mode and backup heat may come on[2], which pulls the average for that stretch down.

Why is my heat pump's COP lower in winter?

It has to move heat across a larger temperature difference between outdoors and indoors, which takes more electricity for each unit of heat[2].

What is the difference between COP and SCOP?

COP describes one operating condition, such as 47°F or 5°F[1]. SCOP is the EU's seasonal figure: heat delivered over a whole designated heating season divided by the electricity used[5]. HSPF2 ÷ 3.412 is the U.S. seasonal counterpart, measured for a different climate.

What is the COP of a geothermal heat pump?

ENERGY STAR's minimums are 3.6 for closed-loop water-to-air units[9] and 4.1 for open-loop ones[9]. The Carnot ceiling drawing from 50°F ground and delivering 95°F air is 308.15 ÷ (308.15 − 283.15) = 12.33, far above what real units reach.

Sources & References

  1. ENERGY STAR: Heat Pump Equipment Key Product Criteria (COP, HSPF2, SEER2 and EER2 definitions; split 7.8 HSPF2, 15.2 SEER2, 11.0 EER2; cold climate COP at 5°F at least 1.75 in the H4₂ test, 70% of 47°F capacity, 8.1 HSPF2 ducted)
  2. Natural Resources Canada: Heating and cooling with a heat pump (COP example; typical COP 2.0 to 5.4 at 8°C and 1.1 to 3.7 at −8°C; seasonal metrics; supply air 25 to 45°C; defrost)
  3. ENERGY STAR: Air-Source Heat Pumps (up to three times more heat than electricity; certification testing down to 5°F)
  4. U.S. EIA: British thermal units (1 kWh = 3,412 Btu)
  5. Commission Regulation (EU) No 206/2012, Annex I, definitions (seasonal coefficient of performance; average, colder and warmer heating seasons), via legislation.gov.uk
  6. 10 CFR 430.32(c)(5): split heat pumps made from January 1, 2023, 14.3 SEER2 and 7.5 HSPF2 (Cornell LII)
  7. NEEP: Cold Climate Air-Source Heat Pump Specification, Version 4.0 (capacity, power and COP reported at 47°F, 17°F and 5°F)
  8. U.S. DOE Office of Geothermal: Geothermal Heat Pumps (ground at about 30 feet stays about 50°F to 59°F)
  9. ENERGY STAR: Geothermal Heat Pumps Key Product Criteria (closed-loop water-to-air COP 3.6, open-loop 4.1; ISO 13256 tests)
  10. U.S. DOE: Guide to Geothermal Heat Pumps, DOE/EE-0385 (February 2011) (300% to 600% efficiency on the coldest winter nights)
  11. U.S. EIA: Electric Power Monthly, Table 5.6.B, average residential price, year to date (January to August 2026: U.S. 18.19 cents per kWh)
  12. U.S. EIA: U.S. Price of Natural Gas Delivered to Residential Consumers, annual (2025: $15.34 per thousand cubic feet; released October 30, 2026)
  13. U.S. EIA: Heat Content of Natural Gas Delivered to Consumers (U.S., 2025: 1,036 Btu per cubic foot)

Related Articles