Each mini split head serves its own room or zone, with its own controls[5], so each one is sized to that room's load. A head too big for its room can short-cycle, which DOE says can lead to poor humidity control in humid climates[7]. One too small can run flat out on the hottest afternoons without reaching the set temperature.

The calculator below sizes each room from its square footage, what the room is used for, your climate, insulation and sun exposure. Every chart and example on this page comes from the same formula, so the numbers match what the calculator shows you. It's an estimate to check quotes against; ask the installer for an ACCA Manual J load calculation[3] before the final choice.

Size each head to its room: the calculator uses about 20 BTU per square foot for bedrooms and offices, 25 for living rooms and kitchens (plus 4,000 BTU for cooking), 18 for basements and 30 for sunrooms, then adjusts for climate, insulation and sun. A 400 sq ft living room in a moderate climate comes to 10,000 BTU per hour, which rounds up to a 12,000 BTU head.

Mini Split Sizing Calculator

Size multi-zone ductless systems.

1

Whole-home context

Affects every zone's load

Climate zone

Zone 4, Mixed: for example New York City, Seattle.

See the full climate zone map
2

Zones

Add an indoor head for each room you want to condition

1Zone 1, Living, 400 sq ft
sq ft
Load: 10,000 BTU(0.83 tons)
Head size: 12k BTU
Enter your values and click Calculate, press Enter in any field.
Four-step diagram of the mini split calculator: room area times a base rate by room type, times climate, insulation and sun adjustments, kitchens plus 4,000 BTU with a 6,000 BTU minimum, rounded up to the next 3,000 BTU step; a hot, sunny 400 sq ft living room needs a 15,000 BTU head.
The calculator's method, with example 2 from below.

How the calculator sizes each room

Each room's load is its square footage times a base rate for the room type, multiplied by three adjustments:

InputValues
Room type (BTU per sq ft)
Bedroom 20 · Office 20 · Basement 18 · Living room 25 · Kitchen 25 · Sunroom 30
Climate
Hot (South, Southwest) 1.2 · Moderate (Mid-Atlantic, mixed) 1.0 · Cold (northern states) 0.9
Insulation
Poor 1.2 · Average 1.0 · Good 0.9
Sun on that room
Shaded 0.9 · Moderate 1.0 · Full sun 1.15
Calculator assumption. The room-type base rates and the climate, insulation and sun multipliers this page's calculator uses.

Three more rules finish the number:

  • Kitchens add 4,000 BTU[1] after the multipliers, for the heat from cooking. That's the adjustment ENERGY STAR gives for room air conditioners used in kitchens.
  • No room goes below 6,000 BTU: as a calculator assumption, 6,000 BTU is the smallest head.
  • Each room rounds up to the next 3,000 BTU step: 6,000, 9,000, 12,000 and so on (a calculator assumption).

As a cross-check, ENERGY STAR's room air conditioner chart runs from 5,000 BTU for 100 to 150 sq ft[1]; 18,000 BTU covers 700 to 1,000 sq ft[1], and the chart continues to 34,000 BTU for 2,000 to 2,500 sq ft[1]. It notes that an oversized unit cools the room before it removes the humidity[1]. The calculator's base rates for bedrooms and living rooms sit near the chart's 12,000 BTU row for 450 to 550 sq ft[1], which works out to 22 to 27 BTU per square foot (12,000 ÷ 550 = 21.8 and 12,000 ÷ 450 = 26.7).

Two ENERGY STAR adjustments it handles differently: it adds 15% for full sun (a calculator assumption) where ENERGY STAR adds 10%[1], and it doesn't include ENERGY STAR's extra 600 BTU[1] for each regular occupant beyond two. Add that yourself for a room that's often crowded.

Mini split size chart by room

Computed at the calculator's middle settings: moderate climate, average insulation, moderate sun. Each cell is the head size in BTU per hour.

Room sizeBedroom / officeLiving roomKitchenBasementSunroom
150 sq ft
6,000
6,000
9,000
6,000
6,000
200 sq ft
6,000
6,000
9,000
6,000
6,000
250 sq ft
6,000
9,000
12,000
6,000
9,000
300 sq ft
6,000
9,000
12,000
6,000
9,000
350 sq ft
9,000
9,000
15,000
9,000
12,000
400 sq ft
9,000
12,000
15,000
9,000
12,000
500 sq ft
12,000
15,000
18,000
9,000
15,000
600 sq ft
12,000
15,000
21,000
12,000
18,000
750 sq ft
15,000
21,000
24,000
15,000
24,000
1,000 sq ft
21,000
27,000
30,000
18,000
30,000
How this was calculated: square footage times the room-type base rate, with kitchens plus 4,000 BTU, a 6,000 BTU minimum, and rounding up to the next 3,000 BTU step, at the calculator's middle settings.

Heads come in fixed sizes, and your installer's product line decides which; if the calculator lands on a size that line doesn't offer, compare the two neighboring sizes.

How many square feet does each head size cover?

The largest room each head covers at the same middle settings, plus a hot, sunny living room for contrast:

Head sizeBedroom / officeLiving roomLiving room, hot climate + full sun
6,000 BTU
300 sq ft
240 sq ft
173 sq ft
9,000 BTU
450 sq ft
360 sq ft
260 sq ft
12,000 BTU
600 sq ft
480 sq ft
347 sq ft
15,000 BTU
750 sq ft
600 sq ft
434 sq ft
18,000 BTU
900 sq ft
720 sq ft
521 sq ft
24,000 BTU
1,200 sq ft
960 sq ft
695 sq ft
How this was calculated: head capacity divided by the room-type base rate (20 for bedrooms and offices, 25 for living rooms), with the hot-climate column also dividing by the 1.2 climate and 1.15 full-sun factors, at the calculator's middle settings.

Three worked examples

Each example is computed with this page's calculator, following the steps in How the calculator sizes each room.

1. A 200 sq ft bedroom, shaded, moderate climate, average insulation: 200 × 20 × 0.9 (shade) = 3,600 BTU/hr, which the 6,000 BTU minimum lifts to a 6,000 BTU head. The head is bigger than the load, but DOE's code brief says inverter-driven compressors adjust capacity, most down to about 30% of rated capacity[5]: 1,800 BTU for a 6,000 BTU head (6,000 × 0.30), below this room's 3,600.

2. A 400 sq ft living room, hot climate, average insulation, full sun: 400 × 25 × 1.2 (hot) × 1.15 (full sun) = 13,800 BTU/hr → a 15,000 BTU head. The same room in a moderate climate with moderate sun needs 12,000.

3. A 250 sq ft kitchen, moderate climate, average insulation, moderate sun: 250 × 25 = 6,250, plus 4,000 for cooking = 10,250 BTU/hr → a 12,000 BTU head.

Bar chart of the largest room each mini split head covers: from 300 sq ft at 6,000 BTU to 1,200 sq ft at 24,000 BTU for a bedroom or office, and from 173 to 695 sq ft for a living room in a hot climate with full sun.
Climate and sun change a head's reach by almost half.

What size mini split for a garage?

The calculator has no garage setting. For an uninsulated garage, the closest match is Living room (25 BTU per sq ft, a calculator assumption) with Poor insulation, and Full sun if the big door faces the sun:

  • One-car garage, 260 sq ft, moderate climate: 8,970 BTU/hr → a 9,000 BTU head.
  • Two-car garage, 480 sq ft, hot climate: 19,872 BTU/hr → 21,000 in the calculator's 3,000 BTU steps; if the line you're buying goes from 18,000 to 24,000, compare both.
  • The same two-car garage with the door and walls insulated (rerun at Average): 16,560 BTU/hr → an 18,000 BTU head.

Insulating the door and walls dropped the two-car example by a full size.

The calculator doesn't model a door left open while you work, which lets outdoor air straight in.

Is it OK to oversize a mini split?

Within limits:

  • The calculator already rounds up to the next head size. Don't add another size on top of its answer.
  • Inverter heads throttle down. DOE's Building America guide says modulating or staged capacity mitigates oversizing issues[6].
  • The limit is the head's minimum output. DOE's guide says to choose a unit whose minimum cooling capacity is at or below the design cooling load[6], and DOE's right-sizing fact sheet says short-cycling can lead to poor humidity control in humid climates[7]. Ask the installer for the head's minimum capacity and compare it with the room's load.
  • In cold climates, size for heating first (see the next section). DOE's guide describes sizing a cold-climate heat pump to the design heating load while keeping its minimum cooling capacity at or below the cooling load[6].

Cold climates: check the heating capacity

The calculator sizes for cooling. A mini split heat pump also heats, and its heating output falls as the outdoor temperature drops: ENERGY STAR's cold-climate criteria require at least 70% of the 47°F capacity at 5°F[8].

Under NEEP's cold-climate specification, makers report each listed system's heating capacity at 47°F, 17°F and 5°F[4]. Compare the coldest of those figures with what the room needs on your coldest days before settling on a size, and see our heat pump size calculator for the heating side.

Multi-zone systems

A multi-zone system runs several indoor heads from one outdoor unit. This five-room layout uses the calculator's middle settings:

RoomRoom loadHead
Bedroom, 140 sq ft
2,800 BTU/hr
6,000
Bedroom, 160 sq ft
3,200 BTU/hr
6,000
Bedroom, 220 sq ft
4,400 BTU/hr
6,000
Living room, 420 sq ft
10,500 BTU/hr
12,000
Kitchen, 180 sq ft
8,500 BTU/hr
9,000
Total
29,400 BTU/hr
39,000
How this was calculated: each room's load is its square footage times the room-type base rate (plus 4,000 BTU for the kitchen), and the head is that load lifted to the 6,000 BTU minimum and rounded up to the next 3,000 BTU step, at the calculator's middle settings.

Two points from the table:

  • The heads add up to more than the rooms need: 39,000 BTU of heads for a 29,400 BTU load (39,000 ÷ 29,400 = 1.33). The three bedrooms need 2,800 to 4,400 BTU each but get the calculator's 6,000 BTU minimum. A concealed ducted mini split with short duct runs[5] is another way to cover several small rooms.
  • The outdoor unit has to carry the combined load. Your installer matches the heads to an outdoor unit using the manufacturer's data.

A single-zone system is simpler: one indoor head on one outdoor unit. For how many heads a home needs and when to choose ductless over ducted, see how many mini splits do I need. For installed prices, see our mini split installation cost guide.

Frequently asked questions

What size mini split do I need for a 500 sq ft room?

From this page's calculator at its middle settings: 12,000 BTU for a bedroom or office, 15,000 BTU for a living room, and 18,000 BTU for a kitchen. A hot climate, poor insulation or full sun can push each answer up a size.

How many square feet does a 12,000 BTU mini split cool?

In this page's calculator, up to about 600 sq ft for a bedroom or office (12,000 ÷ 20) and 480 sq ft for a living room (12,000 ÷ 25) in a moderate climate with average insulation. In a hot climate with full sun, a living room tops out around 350 sq ft (12,000 ÷ 25 ÷ 1.2 ÷ 1.15 ≈ 348).

Can one mini split cool a whole house?

Only if the house is open plan. Each head serves the room or zone it's in, with its own controls[5], and walls and closed doors keep its air from the rest of the house. Separate rooms need their own heads or a ducted unit.

Should I size a mini split for heating or cooling?

In warm climates, cooling, which is what this calculator estimates. In cold climates, DOE's Building America guide describes sizing to the design heating load[6], so check the unit's heating capacity at low outdoor temperatures before you buy.

Is a bigger mini split better?

No. The calculator already builds in headroom by rounding up. Beyond that, DOE's right-sizing fact sheet says short-cycling can lead to poor humidity control in humid climates[7], and a larger system costs more: REMDB's middle installed cost for a single-zone 18,000 BTU, 20 SEER system is $9,850[9] against $6,300[9] at 9,000 BTU, both in 2023 dollars[9].

Sources & References

  1. ENERGY STAR: Room Air Conditioners, Buying Guidance (sizing chart: 5,000 BTU for 100 up to 150 sq ft, 18,000 for 700 up to 1,000, 34,000 for 2,000 up to 2,500; reduce 10% for a heavily shaded room, add 10% for a very sunny one, add 600 BTU per person beyond two, add 4,000 BTU in a kitchen)
  2. NEEP: Cold Climate Air Source Heat Pump Product List
  3. ACCA: Manual J, Residential Load Calculation
  4. NEEP: Cold Climate Air Source Heat Pump Specification, version 4.0 (heating capacity, power and COP reported at 47°F, 17°F and 5°F and the lowest cataloged outdoor dry bulb)
  5. U.S. DOE Building America Solution Center: Ductless Mini-Split Heat Pumps, Code Compliance Brief (inverter-driven compressors adjust capacity, most down to about 30% of rated capacity)
  6. U.S. DOE Building America Solution Center: Cold Climate Heat Pump Sizing and Selection (last updated May 14, 2024; size to all or most of the design heating load, minimum cooling capacity at or below the design cooling load; modulating or staged capacity mitigates oversizing)
  7. U.S. DOE: Right-Size Heating and Cooling Equipment, Technology Fact Sheet (DOE/GO-102002-1490, January 2002; short-cycling can lead to poor humidity control in humid climates)
  8. ENERGY STAR: Heat Pump Equipment Key Product Criteria (cold climate: COP at least 1.75 and at least 70% of the 47°F capacity at 5°F)
  9. National Laboratory of the Rockies (formerly NREL): National Residential Efficiency Measures Database (REMDB), version 4.0.0 (April 2025), Air Source Heat Pump, non-ducted single-zone, retrofit, 2023 dollars (9,000 BTU 20 SEER middle $6,300; 18,000 BTU 20 SEER middle $9,850)
  10. U.S. DOE Energy Saver: Ductless Minisplit Heat Pumps (archived copy of August 24, 2025; DOE has since retired the page): duct losses can account for more than 30% of space-conditioning energy, especially in an unconditioned attic; each zone has its own thermostat
  11. ENERGY STAR: Ductless Heating & Cooling (quiet, efficient air conditioning)
  12. ENERGY STAR: Air-Source Heat Pumps (certification testing down to 5°F; cold climate heat pumps keep working below 5°F)

Related Articles