Tightly built homes save energy, but they also hold in moisture and pollutants from cooking, cleaning and people. The DOE says energy-efficient homes, new and existing, require mechanical ventilation to maintain indoor air quality,[2] and a whole-house system brings in outdoor air at a controlled rate instead of relying on leaks.

ASHRAE Standard 62.2 sets a home's ventilation at 0.03 cfm per square foot plus 7.5 cfm per occupant, with occupants generally counted as bedrooms plus one,[1] so a 2,000 sq ft, three-bedroom home needs 0.03 × 2,000 + 7.5 × (3 + 1) = 90 cfm. A balanced system with a heat or energy recovery ventilator (HRV or ERV) can supply that air while recovering, the DOE says, about 70% to 80% of the energy in the air it exhausts.[2]

Three houses showing exhaust, supply and balanced whole-house ventilation with lines for outdoor air in and indoor air out, above the ASHRAE 62.2 formula worked for a 2,000 sq ft three-bedroom home
Exhaust, supply or balanced, and how much air: 90 cfm for a 2,000 sq ft, three-bedroom home.

Why ventilate

The EPA lists three ways to improve indoor air: controlling pollutant sources, which is usually the most effective, improving ventilation, and air cleaners.[3] It also notes that most home heating and cooling systems, forced-air ones included, don't mechanically bring fresh air into the house.[3] For the pollutants ventilation dilutes, see VOCs in your home.

How much ventilation a home needs

ACCA's summary of ASHRAE 62.2-2016 gives the formula: total ventilation in cubic feet per minute = 0.03 × floor area + 7.5 × (bedrooms + 1), with at least one bedroom counted.[1] ACCA's own sample, a 1,525 sq ft two-bedroom house, needs 0.03 × 1,525 + 7.5 × (2 + 1) = 68.25 cfm.[1]

The table applies the same formula across common home sizes and bedroom counts:

Floor areaBedrooms0.03 × area7.5 × (bedrooms + 1)Required cfm
1,000 sq ft
2
30
22.5
52.5
1,500 sq ft
2
45
22.5
67.5
1,500 sq ft
3
45
30
75
2,000 sq ft
3
60
30
90
2,000 sq ft
4
60
37.5
97.5
2,500 sq ft
4
75
37.5
112.5
3,000 sq ft
4
90
37.5
127.5
3,000 sq ft
5
90
45
135
How this was calculated: the ASHRAE 62.2-2016 formula as ACCA states it, 0.03 cfm times the floor area plus 7.5 cfm times bedrooms plus one; the two component columns sum to the required cfm Read ACCA's summary of ASHRAE 62.2.

In an example 2,000 sq ft house with 8-foot ceilings, 2,000 × 8 = 16,000 cubic feet, and 90 cfm is 90 × 60 ÷ 16,000 = 0.34 air changes per hour; see air changes per hour. The 2021 International Residential Code's own table asks for less, 60 cfm for the same house,[4] and ACCA notes that where the local code official requires a different rate, that rate must be used.[1]

Three kinds of systems

The DOE describes the basic whole-house systems this way:[2]

  • Exhaust: fans pull air out and depressurize the house, while outdoor air leaks in through the shell and any passive vents. Typically it is a single fan at one central exhaust point, and a better design ducts the fan to several rooms, such as bathrooms. It is relatively inexpensive and simple, and most appropriate for cold climates.
  • Supply: a fan pressurizes the house with outdoor air while indoor air leaks out. It gives better control than exhaust, keeps outdoor pollutants and combustion backdrafting down, and lets the incoming air be filtered or dehumidified. The DOE points it to hot or mixed climates.
  • Balanced: properly designed and installed, it neither pressurizes nor depressurizes the house, bringing in and exhausting about equal amounts of air. It usually has two fans and two duct systems, supplying bedrooms and living rooms and exhausting from the kitchen, bathrooms and perhaps the laundry room. It suits all climates but usually costs more to install and run than supply or exhaust.

Each has a moisture risk in the wrong climate. The DOE warns that an exhaust system in a warm, humid summer can draw moist air into wall cavities, where it may condense, and that a supply system in a cold winter can push humid indoor air into the attic or exterior walls, causing mold, mildew and decay.[2]

An exhaust system can also draw in pollutants along with the fresh air, the DOE says: radon and molds from a crawlspace, dust from an attic, fumes from an attached garage, and flue gases from a fireplace or fossil-fuel water heater and furnace.[2] That is a particular concern when bath fans, range fans and clothes dryers run at the same time.[2]

HRV vs. ERV

Both are energy recovery ventilators with a heat exchanger, fans and controls; most are central systems with their own ducts or shared ductwork, and some small models mount in a wall or window.[2] In winter they warm the incoming air with heat from the outgoing air, and in summer the indoor air cools the warmer incoming air.[2]

The difference is moisture: an HRV transfers only heat, while an ERV transfers some water vapor along with the heat.[2] The DOE says most energy recovery systems recover about 70% to 80%[2] of the energy in the exiting air and are most cost-effective where winters or summers are extreme and fuel costs are high.[2]

HRVERV
Core transfers
Heat only
Heat plus some water vapor
Winter
Warms the incoming air
Warms it and keeps indoor humidity more constant, with a warmer core that is less prone to freezing
Summer with air conditioning
Precools the incoming air
Generally better humidity control than an HRV
Energy recovered
About 70% to 80% of the energy in the exiting air
About 70% to 80% of the energy in the exiting air
Most cost-effective
Extreme winters or summers and high fuel costs
Extreme winters or summers and high fuel costs
Source: U.S. DOE Energy Saver, Whole-House Ventilation (archived copy of October 1, 2025; DOE has since retired the page) Read the DOE's archived ventilation page.

Choosing a system for your climate

Match the system to the climate and the moisture problem. The DOE's guidance points exhaust systems to cold climates, supply systems to hot or mixed climates, and balanced systems to any climate.[2] With air conditioning, it says an ERV generally offers better humidity control than an HRV.[2]

In mild climates, the DOE warns, the electricity for the fans may exceed the energy an energy recovery ventilator saves.[2] For very humid but not very hot weather, the DOE reports some controversy about ventilating at all: some experts suggest turning the system off, and it can instead run only when the air conditioner runs, or use pre-cooling coils.[2] No ventilator removes the moisture the house itself generates, so the humidity target still matters; see ideal indoor humidity level.

Installation and upkeep

The DOE's layout advice: a supply and a return duct for each bedroom and each common living area, runs as short and straight as possible, ducts sized correctly, ducts in unheated spaces insulated, and every joint sealed with duct mastic, never ordinary duct tape.[2] Energy recovery systems in cold climates need devices that prevent freezing and frost in the heat exchanger, which can damage it and cut ventilation.[2]

They also need more maintenance than other systems: regular cleaning keeps the ventilation rate and heat recovery from deteriorating and keeps mold and bacteria off the heat exchanger.[2] The DOE adds that only some HVAC contractors have the expertise to install them and that simplicity is key to a cost-effective installation.[2]

A balanced system is only balanced if its supply and exhaust airflows match.[2] Ask the installer to measure both after installation and show you that they are close to each other and to the design rate from the table above.

Frequently asked questions

How much fresh air does my house need?

Under ASHRAE 62.2, 0.03 cfm per square foot plus 7.5 cfm per occupant, counted as bedrooms plus one.[1] For a 2,000 sq ft, three-bedroom home that is 0.03 × 2,000 + 7.5 × 4 = 90 cfm; the 2021 IRC's table gives 60 cfm for the same house.[4]

Should I get an HRV or an ERV?

An ERV transfers some moisture as well as heat, so it keeps winter humidity more constant and, with air conditioning, generally controls summer humidity better.[2] An HRV transfers only heat. Either is most cost-effective where winters or summers are extreme and fuel is expensive.[2]

Do I need mechanical ventilation?

The DOE says energy-efficient homes, new and existing, require it to maintain indoor air quality.[2] The EPA notes that most home heating and cooling systems don't bring in fresh air mechanically.[3]

Is a bathroom fan enough?

A fan exhausting from bathrooms is the start of an exhaust system, and the DOE calls ducting one fan to several rooms a better design than a single exhaust point.[2] It doesn't recover heat, and the DOE warns that exhaust systems can draw pollutants in from a crawlspace, attic or garage.[2]

Can an HRV or ERV cool or dehumidify my house?

Not on its own. In summer the indoor air precools the incoming air, and an ERV can move some incoming moisture back out,[2] but neither replaces an air conditioner or dehumidifier for the moisture a house generates.

How do I know if my ventilation system is balanced?

A balanced system brings in and exhausts about equal amounts of air, so it neither pressurizes nor depressurizes the house.[2] Ask for the measured supply and exhaust airflows after installation; they should be close to each other and to the ASHRAE 62.2 design rate.