Air changes per hour is how many times a room's full volume of air is moved, replaced or filtered in an hour. It's a way of comparing airflow across rooms of different sizes, whether the air comes from outdoors, an exhaust fan or an air purifier.

ACH = airflow in cubic feet per minute × 60 ÷ room volume in cubic feet. A 12 × 15 foot room with an 8-foot ceiling holds 12 × 15 × 8 = 1,440 cubic feet, so 120 CFM moves its air 120 × 60 ÷ 1,440 = 5 times an hour. Ventilation ACH (fresh outdoor air) and an air purifier's ACH (filtered room air) measure different things: AHAM sizes purifiers for 4.8 filtered air changes an hour[2].

Air Changes Per Hour (ACH) Calculator

Ventilation rate from airflow and room size.

1

Room dimensions

Length × width × ceiling = volume

ft
ft
ft
Floor area: 120 sq ft
Volume: 960 cu ft
2

Space type

Determines the target ACH

3

Current airflow

Measured or designed CFM into the room

CFM

For comparison, the 2021 IRC’s minimums for a fan run intermittently are 50 CFM for a bathroom and 100 for a kitchen (Table M1505.4.4); check the rating plate for your equipment’s figure.

Enter your values and click Calculate, press Enter in any field.
A 12 by 15 foot room with an 8-foot ceiling holds 1,440 cubic feet; a 120 CFM fan moves 7,200 cubic feet an hour, which is 5 air changes, one room's worth of air every 12 minutes.
The page's example room, worked through the ACH formula.

The formula

  • ACH = CFM × 60 ÷ volume.
  • CFM needed = volume × target ACH ÷ 60.

Volume is length × width × ceiling height: a 12 × 15 ft room with an 8-foot ceiling holds 12 × 15 × 8 = 1,440 cubic feet. The 60 converts cubic feet per minute to cubic feet per hour.

From a target back to CFM

The calculator also runs the formula in reverse: for any room but a kitchen or bathroom, it shows the airflow its rule-of-thumb target needs, and it checks kitchens and bathrooms against the IRC's exhaust rates instead. Its targets for the other rooms are calculator assumptions for comparing rooms, not code requirements.

Take a 200 sq ft room with a 9-foot ceiling, so a volume of 200 × 9 = 1,800 cubic feet. To move its air 6 times an hour, you need 1,800 × 6 ÷ 60 = 180 CFM. Halving the target to 3 ACH halves the airflow to 1,800 × 3 ÷ 60 = 90 CFM.

Ventilation vs. filtration

Ventilation brings in outdoor air and exhausts indoor air. ACCA gives ASHRAE 62.2-2016's whole-house formula as Qtot = 0.03 Afloor + 7.5 × (Nbr + 1)[1], with occupants generally counted as bedrooms plus one[1]. For a 2,000 sq ft, three-bedroom home that's 0.03 × 2,000 + 7.5 × 4 = 90 cfm, and in a 16,000-cubic-foot house (8-foot ceilings) 90 × 60 ÷ 16,000 = 0.34 ACH.

The 2021 IRC sets a lower whole-house rate in its Table M1505.4.3(1): 60 cfm for the same house[4], or 60 × 60 ÷ 16,000 = 0.23 ACH. See whole-house ventilation.

Filtration recirculates room air through a filter. AHAM Verifide says its suggested room sizes for air cleaners are based on 4.8 air changes per hour[2], and ENERGY STAR notes the effective room size is 1.55 times the smoke CADR, "the same formula used by AHAM"[3]. That's the two-thirds rule: CADR = room area ÷ 1.55 = 0.65 × the area.

The EPA adds that the AHAM room size is meant to give an 80 percent reduction[5] in particle levels once the room reaches equilibrium. See the air purifier sizing guide.

For kitchens and bathrooms the calculator checks your fan against the 2021 IRC's minimum local exhaust rates: 100 CFM[4] for a kitchen fan run intermittently or 25 run continuously[4], and 50 or 20 for a bathroom[4].

Turning a purifier's CADR into ACH

A purifier's clean air delivery rate (CADR) is an airflow in CFM, so it drops straight into the formula: filtered ACH = CADR × 60 ÷ room volume. The table works that out for three CADR values at an 8-foot ceiling.

Room (8-ft ceiling)CADR 100CADR 200CADR 300
150 sq ft (1,200 cf)
5.0 ACH
10.0 ACH
15.0 ACH
300 sq ft (2,400 cf)
2.5 ACH
5.0 ACH
7.5 ACH
500 sq ft (4,000 cf)
1.5 ACH
3.0 ACH
4.5 ACH
How this was calculated: filtered ACH = CADR in CFM × 60 ÷ room volume in cubic feet, at an 8-foot ceiling; for example 200 × 60 ÷ 2,400 = 5.0 ACH.

AHAM's 4.8 ACH works out to 4.8 × 8 ÷ 60 = 0.64 cfm of CADR per square foot at an 8-foot ceiling: about 192 for a 300 sq ft room. The EPA notes the CADR on the box is typically measured at the highest fan speed[5], so lower settings deliver less.

How fast a given ACH clears the air

The CDC's infection-control guidelines give the clearance time in a well-mixed room with no new source: minutes = ln(C1 ÷ C2) ÷ ACH × 60[6]. In those conditions the share still airborne after t hours is e to the power of minus ACH × t, so one air change clears 1 − e⁻¹ = 63% of what was there, not all of it.

Air changes per hour15 min30 min60 min
2 ACH
39%
63%
86%
5 ACH
71%
92%
99%
8 ACH
86%
98%
~100%
How this was calculated: percent removed = 1 − e^(−ACH × hours), the well-mixed decay behind the CDC's Table B.1; for example at 5 ACH for 30 minutes, 1 − e^(−2.5) = 92%. View CDC Appendix B.

The CDC's times assume perfect mixing in an empty room, and it says clearance takes longer where mixing is poor[6]. The EPA adds that clean air not aimed at the breathing zone can short-circuit back to the cleaner[5], so treat these times as the shortest you'd see. At AHAM's 4.8 ACH, 99% removal takes ln(100) ÷ 4.8 × 60 = 58 minutes.

ACH50: measuring air leakage

A blower door depressurizes a house and measures the airflow needed to hold it there; the energy code reports leakage at 50 pascals[7]. That airflow × 60 ÷ the house volume is ACH50, a measure of how leaky the building is.

The 2021 IECC caps any new home at 5.0 air changes per hour[7] or 0.28 cfm per square foot[7] of enclosure area, and homes on the prescriptive path at 5.0 ACH in climate zones 0 to 2 and 3.0 ACH in zones 3 to 8[7].

Frequently asked questions

How do I calculate air changes per hour?

Multiply the airflow in CFM by 60 and divide by the room's volume in cubic feet: 120 × 60 ÷ 1,440 = 5 ACH.

How many air changes per hour does a house need?

Ventilation standards set it in cfm, not ACH. ASHRAE 62.2-2016's formula[1] gives 0.03 × 2,000 + 7.5 × 4 = 90 cfm for a 2,000 sq ft, three-bedroom home, or 90 × 60 ÷ 16,000 = 0.34 ACH at 8-foot ceilings. The 2021 IRC's table gives 60 cfm[4], or 60 × 60 ÷ 16,000 = 0.23 ACH.

How many air changes per hour should an air purifier provide?

AHAM sizes air cleaners for 4.8 air changes per hour[2]. The EPA says higher fan speeds and longer run times filter more air[8], so a larger CADR gives you room to do better.

What is ACH50?

The air changes per hour measured with a blower door at 50 pascals[7], used to rate how airtight a house is. New homes under the 2021 IECC's prescriptive path must test at 3.0 ACH50 or less in climate zones 3 to 8[7].

How many air changes per hour clear smoke or a cooking smell?

At 5 air changes an hour a well-mixed room is about 92% clear of particles in 30 minutes, and at 8 ACH about 98% (1 − e^(−4) = 98%). A purifier's CADR covers particles only[8]; for gases and odors the EPA points to a thick activated carbon filter[8], and to kitchen and bathroom fans that vent outdoors[9].

What ACH does a bedroom need?

Ventilation codes set airflow for the whole house in cfm, not per room in ACH, so there's no single required bedroom number. For an air purifier, AHAM's basis is 4.8 filtered air changes an hour[2].

The EPA notes a noise rating around 50 dB is roughly a modern refrigerator[8], and a unit with more CADR than the room needs can hit the target on a quieter setting.

Related Articles