A generator's rating is in watts, but outlets, cords and transfer switches are rated in amps. Converting between them tells you what you can plug in and how to connect the generator safely.

Amps = watts ÷ volts. A 2,200-watt generator supplies 2,200 ÷ 120 = 18.3 amps at 120 volts, and a 7,500-watt generator 7,500 ÷ 240 = 31.3 amps at 240 volts. Use the running (continuous) watts, not the higher starting watts, for what it can carry steadily.

Generator Amps Calculator

Convert watts to amps and back for a generator, at the voltage of the outlet you use. It doesn’t size wire.

1

Calculator mode

Pick what you're solving for

2

Inputs

Voltage, current/watts, phase, PF

W
Enter your values and click Calculate, press Enter in any field.

Generator sizing and electrical safety notes

  • Two numbers, two questions. The 125% breaker figure sizes a house circuit for a continuous load; a generator’s running watts are what it can supply steadily.
  • A motor draws more power while starting than at steady full load (DOE), so size the generator for the running load plus the largest motor’s start.
  • Each outlet’s amp rating is printed beside it on the generator; check it before plugging in a large load.
  • Never backfeed a house through a wall outlet; connect through a transfer switch installed by a qualified electrician.
  • This calculator converts between watts, amps and volt-amps. It doesn’t size wire.
The same 7,500 running watts as 62.5 amps at 120 volts and 31.3 amps per leg at 240 volts, beside bars of what 20 and 30 amp outlets at 120 volts and 30 and 50 amp outlets at 240 volts can carry.
Amps = watts ÷ volts; an outlet carries its amps × volts.

Watts to amps

Running wattsAt 120 VAt 240 V
1,000 W
8.3 A
4.2 A
1,800 W
15.0 A
7.5 A
2,200 W
18.3 A
9.2 A
3,000 W
25.0 A
12.5 A
3,500 W
29.2 A
14.6 A
5,000 W
41.7 A
20.8 A
7,500 W
62.5 A
31.3 A
8,000 W
66.7 A
33.3 A
9,000 W
75.0 A
37.5 A
10,000 W
83.3 A
41.7 A
12,000 W
100.0 A
50.0 A
15,000 W
125.0 A
62.5 A
22,000 W
183.3 A
91.7 A
How this was calculated: amps = watts ÷ volts, each cell the watt rating ÷ 120 or ÷ 240 volts. For example, 10,000 ÷ 120 = 83.3 and 10,000 ÷ 240 = 41.7.

Every amp figure is the watt rating divided by the voltage, so 10,000 watts is 10,000 ÷ 120 = 83.3 amps at 120 volts and 10,000 ÷ 240 = 41.7 amps at 240 volts. For the same wattage the higher-voltage current is half the lower-voltage current, because 240 ÷ 120 = 2.

On a generator with both voltages, the higher-voltage figure is what each of the two legs carries when the load is balanced between them. Check your generator's outlet panel: a unit with only 120-volt outlets has no 240-volt receptacles, so the right-hand column doesn't apply to it.

Example generator sizes in amps

Example sizeOutlets on the exampleAmps
2,000 W
120 V only
16.7 A at 120 V
3,500 W
120 V
29.2 A at 120 V
7,500 W
120 V and 240 V
62.5 A at 120 V, 31.3 A at 240 V
22,000 W
120 V and 240 V
91.7 A at 240 V
How this was calculated: amps = the example's watt output ÷ volts: 2,000 ÷ 120, 3,500 ÷ 120, 7,500 ÷ 120 and ÷ 240, and 22,000 ÷ 240. The sizes and outlet voltages are examples; read yours off the generator's outlet panel.

Each figure is again the watts divided by the volts: a 2,000-watt unit gives 2,000 ÷ 120 = 16.7 amps, and a 22,000-watt unit gives 22,000 ÷ 240 = 91.7 amps per leg. A unit that has only 120-volt outlets puts its whole output on one leg, so its current is 240 ÷ 120 = 2 times what the same wattage would draw at 240 volts.

Watts, VA and power factor

The amp figures above use amps = watts ÷ volts, which is the same as amps = watts ÷ (volts × power factor) when the power factor is 1, as for a purely resistive load such as a heater. Current follows apparent power in volt-amps, where VA = watts ÷ power factor.

Motors and some electronics draw current that is partly out of step with the voltage, so their power factor is below 1 and they draw more current than their watt rating alone suggests: amps = watts ÷ (volts × power factor). If a load lists volt-amps or amps on its plate, use that figure rather than converting from watts.

What an outlet can carry

The most power an outlet can deliver is its amp rating times its voltage, so read the rating printed beside each outlet on the generator. A few examples:

Example outlet ratingMost power through it
20 A at 120 V
2,400 W
30 A at 120 V
3,600 W
30 A at 240 V
7,200 W
50 A at 240 V
12,000 W
How this was calculated: most power = amps × volts, for example 20 × 120 = 2,400 W and 50 × 240 = 12,000 W.

The generator's own breaker and running watts also limit what any one outlet can deliver, whichever is lower.

Running vs. starting watts

DOE notes that a starting motor "draws more power than when it is operating steadily at full load."[2] A generator's starting (surge) rating covers those moments, and its running rating is what it can supply continuously. Size for the running load plus the largest motor's start; see what size generator you need.

Convert both ratings the same way. A generator listed at 3,500 running watts and 4,500 starting watts (an example) supplies 3,500 ÷ 120 = 29.2 amps continuously and briefly up to 4,500 ÷ 120 = 37.5 amps during a motor start. Size the cord and outlet to the continuous 29.2 amps, and use the starting figure only to check that the generator can start your largest motor.

Matching output to the connection

A 7,500-watt generator produces 7,500 ÷ 240 = 31.3 amps at 240 volts, more than a 30-amp, 240-volt connection carries (30 × 240 = 7,200 W). Through that connection its usable output is 7,200 watts, so delivering its full running output takes a higher-rated path. A 3,500-watt, 120-volt generator at 3,500 ÷ 120 = 29.2 amps fits a 30-amp, 120-volt connection, which carries up to 30 × 120 = 3,600 watts.

Have the electrician who installs the transfer switch match the inlet and cord to your generator's outlet and amps.

Connecting to a house

Never plug a generator into a household outlet to backfeed the house. CPSC warns that backfeeding through a wall outlet "presents an electrocution risk to utility workers and neighbors served by the same utility transformer" and bypasses some of the home's circuit protection.[3] OSHA says a generator should connect to a building's wiring only through a transfer switch installed by a qualified electrician.[4]

Wisconsin's consumer protection agency recommends a double-pole, double-throw transfer switch and telling your electric company about the installation.[5]

Carbon monoxide

Generator exhaust contains carbon monoxide. The CPSC says to run portable generators outdoors only, at least 20 feet from the house[1], with the exhaust pointed away from the home, and to keep CO alarms on every level and outside sleeping areas.[1]

Frequently asked questions

How many amps does a 7,500-watt generator produce?

From its running watts, 7,500 ÷ 240 = 31.3 amps at 240 volts, or 7,500 ÷ 120 = 62.5 amps at 120 volts.

How many amps is a 2,200-watt generator?

2,200 ÷ 120 = 18.3 amps at 120 volts.

How many amps is a 10,000-watt generator?

10,000 ÷ 120 = 83.3 amps at 120 volts, or 10,000 ÷ 240 = 41.7 amps at 240 volts. On a generator with both voltages, the 41.7 amps is what each leg carries with the load balanced.

How many amps is a 5,000-watt generator?

5,000 ÷ 120 = 41.7 amps at 120 volts, or 5,000 ÷ 240 = 20.8 amps at 240 volts.

How many amps is a 3,500-watt generator?

3,500 ÷ 120 = 29.2 amps at 120 volts, or 3,500 ÷ 240 = 14.6 amps at 240 volts.

What size cord do I need for my generator?

CPSC advises heavy-duty outdoor extension cords rated for more than the wattage you connect.[3] Keep it as short as practical, since long, thin cords drop voltage; see our wire gauge chart.

Can I plug a generator into my dryer outlet?

No. Feeding power back through a dryer or any other household outlet is backfeeding, which CPSC warns can electrocute utility workers and neighbors.[3] Connect through a transfer switch installed by a qualified electrician.[4]

Related Articles