You need to know what size wire a circuit calls for, whether you're planning a project, checking an existing installation, or trying to understand what the electrician quoted. Undersized wire on a circuit that draws more than it's rated for overheats, and that's a fire risk. For how circuits, breakers and wire fit together in a house, see the home electrical wiring guide.

Below: the NEC Table 310.16 ampacities for copper and aluminum in all three temperature columns, wire dimensions, resistance for voltage-drop math, and the code rules that decide which number applies. Use it to understand wire sizing and talk to your electrician; a new or modified circuit should be sized and installed to your local code by a licensed electrician.

On standard branch circuits, 14 AWG copper is capped at 15 amps, 12 AWG at 20 and 10 AWG at 30.[5] These caps come from NEC 240.4(D) and are fixed regardless of insulation type. Larger wire follows NEC Table 310.16, but the number that applies depends on the wire's temperature rating and your terminations, explained below.

Copper conductors drawn to scale from 14 AWG at 1.628 mm to 1/0 at 8.252 mm, showing that a smaller AWG number is a thicker wire and that every 6 steps doubles the diameter and every 3 steps doubles the cross-section.
Physical sizes from the dimensions table below.

The NEC Table 310.16 ampacity chart (copper)

These are the allowable ampacities from NEC Table 310.16 for copper conductors[3], based on no more than three current-carrying conductors in a raceway or cable at an ambient temperature of 30°C (86°F)[6]. The three columns correspond to the wire's insulation temperature rating.

AWG60°C (TW, UF, NM-B)75°C (THW, THWN, XHHW)90°C (THHN, THWN-2, XHHW-2)
14
15
20
25
12
20
25
30
10
30
35
40
8
40
50
55
6
55
65
75
4
70
85
95
3
85
100
115
2
95
115
130
1
110
130
145
1/0
125
150
170
2/0
145
175
195
3/0
165
200
225
4/0
195
230
260
Allowable ampacities, NEC (NFPA 70) Table 310.16: not more than three current-carrying conductors, 30°C (86°F) ambient. Checked against NFPA's 2026-edition First Draft report and Cerrowire's ampacity chart (2017 NEC basis).

Three rules govern which column and breaker you actually use:

  • The termination rule (NEC 110.14(C)): the ampacity column can't exceed the lowest temperature rating of any termination, conductor or device in the circuit[6]. If the breaker and equipment terminals are rated 75°C, even 90°C wire is limited to its 75°C ampacity there, so you can't use the 90°C number just because the wire allows it.
  • The NM-B (Romex) rule (NEC 334.80): standard NM-B cable, even though its conductors are 90°C-rated, must be sized using the 60°C column[2]. So 12 AWG NM-B is 20 amps, not the 25 of the 75°C column[3].
  • The small-conductor cap (NEC 240.4(D)): regardless of ampacity, 14 AWG copper is capped at a 15A breaker, 12 AWG at 20A, and 10 AWG at 30A[5].

Aluminum conductor ampacities (NEC Table 310.16)

Aluminum carries less current than copper for the same gauge, so it needs to be sized larger. At 2 AWG and 75°C, for example, the tables here put aluminum at 90 amps against copper's 115[3], about 78% (90 ÷ 115).

AWG60°C75°C90°C
12
15
20
25
10
25
30
35
8
35
40
45
6
40
50
55
4
55
65
75
3
65
75
85
2
75
90
100
1
85
100
115
1/0
100
120
135
2/0
115
135
150
3/0
130
155
175
4/0
150
180
205
Allowable ampacities, NEC (NFPA 70) Table 310.16: not more than three current-carrying conductors, 30°C (86°F) ambient. Checked against NFPA's 2026-edition First Draft report and Cerrowire's ampacity chart (2017 NEC basis).

In the 60°C column, 4 AWG aluminum carries the 55 A of 6 AWG copper[3], and 6 AWG aluminum the 40 A of 8 AWG copper[3], so aluminum runs about two sizes larger. Ask an electrician to confirm that every terminal suits aluminum conductors.

Physical dimensions

For conduit-fill calculations and wire identification, here are the standard AWG dimensions.

AWGDiameter (in)Diameter (mm)Cross-Section (mm²)Area (kcmil)
14
0.0641
1.628
2.08
4.11
12
0.0808
2.053
3.31
6.53
10
0.1019
2.588
5.26
10.38
8
0.1285
3.264
8.37
16.51
6
0.1620
4.115
13.30
26.24
4
0.2043
5.189
21.15
41.74
2
0.2576
6.544
33.62
66.36
1/0
0.3249
8.252
53.49
105.6
2/0
0.3648
9.266
67.43
133.1
4/0
0.4600
11.68
107.2
211.6
Calculated from the AWG definition: diameter = 0.005 in × 92^((36 - n)/39), with n = 0 for 1/0, -1 for 2/0, -3 for 4/0; mm and areas from the diameter.

Wire resistance (for voltage-drop math)

Resistance determines voltage drop over distance, which matters on long runs to HVAC equipment, detached garages, and outbuildings. The values are Michigan State University's Table 212.1 figures in ohms per 1,000 feet[4].

AWGCopper (Ω/1000 ft)Aluminum (Ω/1000 ft)
14
3.14
5.17
12
1.98
3.25
10
1.24
2.04
8
0.778
1.28
6
0.491
0.808
4
0.308
0.508
2
0.194
0.319
1/0
0.122
0.201
2/0
0.0967
0.159
4/0
0.0608
0.100
DC resistance at 75°C, stranded conductors: Michigan State University, Electrical Tech Note 212, Conductor Properties, Table 212.1. View Tech Note 212.

The voltage-drop formula: VD = (2 × L × I × R) / 1000, where L is the one-way run length in feet, I is the current in amps, and R is the resistance above. The NEC's informational notes recommend keeping voltage drop under 3% on a branch circuit (under 5% total including the feeder)[10]. On a long run that can mean going up a wire size even when the ampacity table says the smaller wire is fine: at 120 volts, 20 amps on 12 AWG copper reaches the 3% drop, 3.6 volts, at about 45 feet (3.6 × 1,000 ÷ (2 × 20 × 1.98) = 45.5).

Bar chart of ampacity adjustment for conductors sharing a raceway: 100% for 1 to 3 current-carrying conductors, 80% for 4 to 6, 70% for 7 to 9 and 50% for 10 to 20, plus a note that heat above 30°C also reduces ampacity.
Both adjustments can push you to a larger wire.

The two adjustments that change the numbers

The ampacity values above assume standard conditions. Two factors require you to reduce them:

Conduit fill (NEC 310.15(C)(1)), when more than three current-carrying conductors share a raceway[3]:

ConductorsAdjustment
1–3
100% (no derating)
4–6
80%
7–9
70%
10–20
50%
NEC Table 310.15(C)(1) adjustment factors (4 to 6 conductors 80%, 7 to 9 70%, 10 to 20 50%), checked against NFPA's 2026-edition First Draft report.

Ambient temperature (NEC Table 310.15(B)(1)(1)), when it's hotter than 30°C (86°F):[3] ampacity drops as the surrounding air gets hotter. At 46 to 50°C (114 to 122°F)[3], the table multiplies ampacity by 0.82 for a 90°C conductor[3], 0.75 for a 75°C conductor[3] and 0.58 for a 60°C conductor[3].

A 12 AWG copper conductor's 30 A in the 90°C column becomes 24.6 A in that heat (30 × 0.82)[3]; NM-B's final ampacity still can't exceed its 60°C value, 20 A[2]. Wiring through a space that hot may need a larger size, so have an electrician verify it.

Wire sizing by application (reference)

These pairings come from the rules above and from published guidance for each appliance. Always confirm against your equipment's nameplate and your local code.

ApplicationCircuitTypical wireTypical breaker
15 A branch circuit
120V, 15A
14 AWG
15A
20 A branch circuit
120V, 20A
12 AWG
20A
Electric dryer
240V, 30A
10 AWG
30A
Heat pump water heater
240V
10 AWG
30A
Central AC or heat pump
240V
at least the nameplate MCA
at most the nameplate maximum
EV charger (continuous load)
240V
125% of the load, see note
125% of the load, see note
Sub-panel feeder
240V
sized to the calculated load
sized to the calculated load
15 A and 20 A rows: NEC 240.4(D), as quoted by Encore Wire. Dryer: ExpertCE's Table 310.16 guide (10 AWG copper is typical for a 30 A dryer). Heat pump water heater: ENERGY STAR's installation guide (a 240 V unit typically uses a 30 A breaker and 10-gauge wire). Air conditioners: the nameplate, per IAEI. EV charger: the 125% rule below.

Air conditioners and heat pumps are sized from their nameplate: the minimum circuit ampacity (MCA) sets the smallest wire, and the maximum fuse or breaker size caps the breaker[11]. NEC Articles 440 and 430 modify the general rules of Article 240 for this equipment[12], so an AC breaker can be larger than a general-purpose circuit would use for the same wire.

EV chargers and other continuous loads need extra room: a continuous load is one whose maximum current runs for 3 hours or more[8], and its circuit must be sized at 125% of that load[7]. An EV charger counts as continuous[9], so a 48-amp charger needs a 60-amp breaker (48 × 1.25 = 60) and wire rated accordingly, not the wire that 48 amps alone would suggest. Have an electrician size EV and other high-draw circuits.

For 240-volt circuits specifically, our 220/240V wire sizing guide walks through the four factors (continuous load, temperature rating, copper vs aluminum, and run length) that change the size.

How the AWG system works

The AWG is defined by two diameters: No. 0000 is 0.4600 inch and No. 36 is 0.0050 inch, with 38 sizes between them[13]. So each AWG step changes the diameter by a factor of about 1.123, the 39th root of 92 (0.4600 ÷ 0.0050 = 92). The practical consequences:

  • Every 6 AWG steps about doubles the wire's diameter (1.123⁶ = 2.005)[13].
  • Every 3 AWG steps doubles the cross-sectional area[13].

Below 1 AWG the sizes continue as 1/0, 2/0, 3/0 and 4/0. Larger conductors are stranded and specified by their cross section in circular mils[13], written in kcmil (thousands of circular mils), like 250 or 350 kcmil[2].

Frequently asked questions

What amperage can each wire gauge handle? Copper wire is capped at 15A for 14 AWG, 20A for 12 AWG and 30A for 10 AWG (NEC 240.4(D))[5]; then NEC Table 310.16 gives 8 AWG 40–55A[3] and 6 AWG 55–75A[3], depending on the insulation temperature column. The figure for your circuit depends on the wire type and your terminations, and NM-B (Romex) uses the more conservative 60°C column[2].

Why does the same wire show different amperages? Because the ampacity depends on the insulation's temperature rating (the 60/75/90°C columns). You can't always use the highest number: NEC 110.14(C) limits you to the lowest temperature rating of any termination or device in the circuit[6], and NM-B cable must use the 60°C column per NEC 334.80[2].

What wire do I need for a long run? Start with the ampacity table, then check voltage drop with VD = (2 × L × I × R) / 1000, using the resistance table above. The NEC's informational notes recommend no more than 3% drop on a branch circuit[10], so go up a wire size past that. A long run to a detached garage or outbuilding can need a larger wire for voltage drop even when the ampacity would be fine.

Can I use aluminum wire? It carries less current than copper of the same gauge, so it runs about two sizes larger: 4 AWG aluminum carries the 55 A of 6 AWG copper in the 60°C column[3]. Ask an electrician whether aluminum suits your circuit and its terminals.

Do I need an electrician, or can I do this myself? The ampacity table helps you understand and plan, but wire sizing depends on conditions (temperature, run length, load type, terminations) that a general chart can't fully capture for your install. Have a licensed electrician do or verify the work, and ask your local building department which permits and inspections apply.

About these figures

The ampacity values (copper and aluminum, 60°C/75°C/90°C columns) are from NEC Table 310.16 (National Electrical Code, NFPA 70), and the sizing rules are the corresponding NEC articles: the small-conductor caps (240.4(D)), the termination temperature rule (110.14(C)), the NM-B 60°C requirement (334.80), conduit-fill and ambient-temperature derating (310.15(C)(1) and 310.15(B)(1)(1)), and voltage-drop recommendations (210.19). Wire dimensions follow the AWG definition in NIST's Copper Wire Tables (Handbook 100), and resistance is Michigan State University's Table 212.1.

The application pairings are typical references; size each circuit to the equipment's nameplate and your local code. NFPA 70 is the authoritative U.S. electrical standard, adopted (sometimes with amendments) by your local jurisdiction.

Sources & References

  1. National Electrical Code (NFPA 70): Table 310.16 and related articles (240.4(D), 110.14(C), 334.80, 310.15)
  2. Cerrowire: Ampacity Charts (NEC Table 310.16, 2017 NEC basis)
  3. NFPA: 2026-edition National Electrical Code First Draft report (Table 310.16 ampacities, FR-8036)
  4. Michigan State University: Electrical Tech Note 212, Conductor Properties, Table 212.1 (DC resistance at 75C, stranded)
  5. Encore Wire: Wire Ampacity Size Table (NEC 240.4(D): overcurrent protection no more than 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10 AWG copper)
  6. ExpertCE: How to Use NEC Table 310.16 (NEC 110.14(C): the temperature rating used can't exceed the lowest rating of any termination, conductor or device; table based on 30°C (86°F) and no more than three current-carrying conductors; 10 AWG copper typical for a 30 A dryer)
  7. NFPA: 2026-edition National Electrical Code First Draft report, Code-Making Panel 2 (210.19(A)(1) and 210.20(A): conductors and breakers sized at the noncontinuous load plus 125 percent of the continuous load)
  8. IAEI Magazine, Focus on the Code, November/December 2012 (NEC Article 100: a continuous load is one where the maximum current is expected to continue for 3 hours or more)
  9. U.S. DOE Alternative Fuels Data Center: Plug-In Electric Vehicle Handbook for Electrical Contractors (EV supply equipment is a continuous load under the NEC)
  10. Mike Holt Enterprises: Electrical Exam Preparation (2020 NEC), Unit 8.6 (the Code's informational notes recommend voltage drop of no more than 3% for a branch circuit or feeder and 5% combined)
  11. IAEI Magazine, L. Keith Lofland, Air-Conditioning Equipment Installations (July/August 2017): the nameplate's minimum supply circuit ampacity sets the minimum branch-circuit conductor size; its maximum fuse or circuit breaker size is the largest permitted
  12. North Carolina Office of State Fire Marshal: Air-Conditioning and Refrigerating Equipment Branch Circuit Ampacity and Protection (June 28, 2017): Articles 440 and 430 modify the general rules of Article 240; the nameplate maximum can't be exceeded
  13. NIST (National Bureau of Standards) Handbook 100, Copper Wire Tables (1966): No. 0000 is 0.4600 inch and No. 36 is 0.0050 inch with 38 sizes between; every three gage numbers the cross section doubles or halves; stranded conductors are specified in circular mils
  14. ENERGY STAR: Heat Pump Water Heater Installation Guide (a 240 V unit typically uses a 30-amp breaker and 10-gauge wire)

Related Articles