You need to know what size wire a circuit calls for, whether you're planning a project, checking an existing installation, or trying to understand what the electrician quoted. Undersized wire on a circuit that draws more than it's rated for overheats, and that's a fire risk. For how circuits, breakers and wire fit together in a house, see the home electrical wiring guide.
Below: the NEC Table 310.16 ampacities for copper and aluminum in all three temperature columns, wire dimensions, resistance for voltage-drop math, and the code rules that decide which number applies. Use it to understand wire sizing and talk to your electrician; a new or modified circuit should be sized and installed to your local code by a licensed electrician.
On standard branch circuits, 14 AWG copper is capped at 15 amps, 12 AWG at 20 and 10 AWG at 30.[5] These caps come from NEC 240.4(D) and are fixed regardless of insulation type. Larger wire follows NEC Table 310.16, but the number that applies depends on the wire's temperature rating and your terminations, explained below.
The NEC Table 310.16 ampacity chart (copper)
These are the allowable ampacities from NEC Table 310.16 for copper conductors[3], based on no more than three current-carrying conductors in a raceway or cable at an ambient temperature of 30°C (86°F)[6]. The three columns correspond to the wire's insulation temperature rating.
| AWG | 60°C (TW, UF, NM-B) | 75°C (THW, THWN, XHHW) | 90°C (THHN, THWN-2, XHHW-2) |
|---|---|---|---|
14 | 15 | 20 | 25 |
12 | 20 | 25 | 30 |
10 | 30 | 35 | 40 |
8 | 40 | 50 | 55 |
6 | 55 | 65 | 75 |
4 | 70 | 85 | 95 |
3 | 85 | 100 | 115 |
2 | 95 | 115 | 130 |
1 | 110 | 130 | 145 |
1/0 | 125 | 150 | 170 |
2/0 | 145 | 175 | 195 |
3/0 | 165 | 200 | 225 |
4/0 | 195 | 230 | 260 |
Three rules govern which column and breaker you actually use:
- The termination rule (NEC 110.14(C)): the ampacity column can't exceed the lowest temperature rating of any termination, conductor or device in the circuit[6]. If the breaker and equipment terminals are rated 75°C, even 90°C wire is limited to its 75°C ampacity there, so you can't use the 90°C number just because the wire allows it.
- The NM-B (Romex) rule (NEC 334.80): standard NM-B cable, even though its conductors are 90°C-rated, must be sized using the 60°C column[2]. So 12 AWG NM-B is 20 amps, not the 25 of the 75°C column[3].
- The small-conductor cap (NEC 240.4(D)): regardless of ampacity, 14 AWG copper is capped at a 15A breaker, 12 AWG at 20A, and 10 AWG at 30A[5].
Aluminum conductor ampacities (NEC Table 310.16)
Aluminum carries less current than copper for the same gauge, so it needs to be sized larger. At 2 AWG and 75°C, for example, the tables here put aluminum at 90 amps against copper's 115[3], about 78% (90 ÷ 115).
| AWG | 60°C | 75°C | 90°C |
|---|---|---|---|
12 | 15 | 20 | 25 |
10 | 25 | 30 | 35 |
8 | 35 | 40 | 45 |
6 | 40 | 50 | 55 |
4 | 55 | 65 | 75 |
3 | 65 | 75 | 85 |
2 | 75 | 90 | 100 |
1 | 85 | 100 | 115 |
1/0 | 100 | 120 | 135 |
2/0 | 115 | 135 | 150 |
3/0 | 130 | 155 | 175 |
4/0 | 150 | 180 | 205 |
In the 60°C column, 4 AWG aluminum carries the 55 A of 6 AWG copper[3], and 6 AWG aluminum the 40 A of 8 AWG copper[3], so aluminum runs about two sizes larger. Ask an electrician to confirm that every terminal suits aluminum conductors.
Physical dimensions
For conduit-fill calculations and wire identification, here are the standard AWG dimensions.
| AWG | Diameter (in) | Diameter (mm) | Cross-Section (mm²) | Area (kcmil) |
|---|---|---|---|---|
14 | 0.0641 | 1.628 | 2.08 | 4.11 |
12 | 0.0808 | 2.053 | 3.31 | 6.53 |
10 | 0.1019 | 2.588 | 5.26 | 10.38 |
8 | 0.1285 | 3.264 | 8.37 | 16.51 |
6 | 0.1620 | 4.115 | 13.30 | 26.24 |
4 | 0.2043 | 5.189 | 21.15 | 41.74 |
2 | 0.2576 | 6.544 | 33.62 | 66.36 |
1/0 | 0.3249 | 8.252 | 53.49 | 105.6 |
2/0 | 0.3648 | 9.266 | 67.43 | 133.1 |
4/0 | 0.4600 | 11.68 | 107.2 | 211.6 |
Wire resistance (for voltage-drop math)
Resistance determines voltage drop over distance, which matters on long runs to HVAC equipment, detached garages, and outbuildings. The values are Michigan State University's Table 212.1 figures in ohms per 1,000 feet[4].
| AWG | Copper (Ω/1000 ft) | Aluminum (Ω/1000 ft) |
|---|---|---|
14 | 3.14 | 5.17 |
12 | 1.98 | 3.25 |
10 | 1.24 | 2.04 |
8 | 0.778 | 1.28 |
6 | 0.491 | 0.808 |
4 | 0.308 | 0.508 |
2 | 0.194 | 0.319 |
1/0 | 0.122 | 0.201 |
2/0 | 0.0967 | 0.159 |
4/0 | 0.0608 | 0.100 |
The voltage-drop formula: VD = (2 × L × I × R) / 1000, where L is the one-way run length in feet, I is the current in amps, and R is the resistance above. The NEC's informational notes recommend keeping voltage drop under 3% on a branch circuit (under 5% total including the feeder)[10]. On a long run that can mean going up a wire size even when the ampacity table says the smaller wire is fine: at 120 volts, 20 amps on 12 AWG copper reaches the 3% drop, 3.6 volts, at about 45 feet (3.6 × 1,000 ÷ (2 × 20 × 1.98) = 45.5).
The two adjustments that change the numbers
The ampacity values above assume standard conditions. Two factors require you to reduce them:
Conduit fill (NEC 310.15(C)(1)), when more than three current-carrying conductors share a raceway[3]:
| Conductors | Adjustment |
|---|---|
1–3 | 100% (no derating) |
4–6 | 80% |
7–9 | 70% |
10–20 | 50% |
Ambient temperature (NEC Table 310.15(B)(1)(1)), when it's hotter than 30°C (86°F):[3] ampacity drops as the surrounding air gets hotter. At 46 to 50°C (114 to 122°F)[3], the table multiplies ampacity by 0.82 for a 90°C conductor[3], 0.75 for a 75°C conductor[3] and 0.58 for a 60°C conductor[3].
A 12 AWG copper conductor's 30 A in the 90°C column becomes 24.6 A in that heat (30 × 0.82)[3]; NM-B's final ampacity still can't exceed its 60°C value, 20 A[2]. Wiring through a space that hot may need a larger size, so have an electrician verify it.
Wire sizing by application (reference)
These pairings come from the rules above and from published guidance for each appliance. Always confirm against your equipment's nameplate and your local code.
| Application | Circuit | Typical wire | Typical breaker |
|---|---|---|---|
15 A branch circuit | 120V, 15A | 14 AWG | 15A |
20 A branch circuit | 120V, 20A | 12 AWG | 20A |
Electric dryer | 240V, 30A | 10 AWG | 30A |
Heat pump water heater | 240V | 10 AWG | 30A |
Central AC or heat pump | 240V | at least the nameplate MCA | at most the nameplate maximum |
EV charger (continuous load) | 240V | 125% of the load, see note | 125% of the load, see note |
Sub-panel feeder | 240V | sized to the calculated load | sized to the calculated load |
Air conditioners and heat pumps are sized from their nameplate: the minimum circuit ampacity (MCA) sets the smallest wire, and the maximum fuse or breaker size caps the breaker[11]. NEC Articles 440 and 430 modify the general rules of Article 240 for this equipment[12], so an AC breaker can be larger than a general-purpose circuit would use for the same wire.
EV chargers and other continuous loads need extra room: a continuous load is one whose maximum current runs for 3 hours or more[8], and its circuit must be sized at 125% of that load[7]. An EV charger counts as continuous[9], so a 48-amp charger needs a 60-amp breaker (48 × 1.25 = 60) and wire rated accordingly, not the wire that 48 amps alone would suggest. Have an electrician size EV and other high-draw circuits.
For 240-volt circuits specifically, our 220/240V wire sizing guide walks through the four factors (continuous load, temperature rating, copper vs aluminum, and run length) that change the size.
How the AWG system works
The AWG is defined by two diameters: No. 0000 is 0.4600 inch and No. 36 is 0.0050 inch, with 38 sizes between them[13]. So each AWG step changes the diameter by a factor of about 1.123, the 39th root of 92 (0.4600 ÷ 0.0050 = 92). The practical consequences:
- Every 6 AWG steps about doubles the wire's diameter (1.123⁶ = 2.005)[13].
- Every 3 AWG steps doubles the cross-sectional area[13].
Below 1 AWG the sizes continue as 1/0, 2/0, 3/0 and 4/0. Larger conductors are stranded and specified by their cross section in circular mils[13], written in kcmil (thousands of circular mils), like 250 or 350 kcmil[2].
Frequently asked questions
What amperage can each wire gauge handle? Copper wire is capped at 15A for 14 AWG, 20A for 12 AWG and 30A for 10 AWG (NEC 240.4(D))[5]; then NEC Table 310.16 gives 8 AWG 40–55A[3] and 6 AWG 55–75A[3], depending on the insulation temperature column. The figure for your circuit depends on the wire type and your terminations, and NM-B (Romex) uses the more conservative 60°C column[2].
Why does the same wire show different amperages? Because the ampacity depends on the insulation's temperature rating (the 60/75/90°C columns). You can't always use the highest number: NEC 110.14(C) limits you to the lowest temperature rating of any termination or device in the circuit[6], and NM-B cable must use the 60°C column per NEC 334.80[2].
What wire do I need for a long run? Start with the ampacity table, then check voltage drop with VD = (2 × L × I × R) / 1000, using the resistance table above. The NEC's informational notes recommend no more than 3% drop on a branch circuit[10], so go up a wire size past that. A long run to a detached garage or outbuilding can need a larger wire for voltage drop even when the ampacity would be fine.
Can I use aluminum wire? It carries less current than copper of the same gauge, so it runs about two sizes larger: 4 AWG aluminum carries the 55 A of 6 AWG copper in the 60°C column[3]. Ask an electrician whether aluminum suits your circuit and its terminals.
Do I need an electrician, or can I do this myself? The ampacity table helps you understand and plan, but wire sizing depends on conditions (temperature, run length, load type, terminations) that a general chart can't fully capture for your install. Have a licensed electrician do or verify the work, and ask your local building department which permits and inspections apply.
About these figures
The ampacity values (copper and aluminum, 60°C/75°C/90°C columns) are from NEC Table 310.16 (National Electrical Code, NFPA 70), and the sizing rules are the corresponding NEC articles: the small-conductor caps (240.4(D)), the termination temperature rule (110.14(C)), the NM-B 60°C requirement (334.80), conduit-fill and ambient-temperature derating (310.15(C)(1) and 310.15(B)(1)(1)), and voltage-drop recommendations (210.19). Wire dimensions follow the AWG definition in NIST's Copper Wire Tables (Handbook 100), and resistance is Michigan State University's Table 212.1.
The application pairings are typical references; size each circuit to the equipment's nameplate and your local code. NFPA 70 is the authoritative U.S. electrical standard, adopted (sometimes with amendments) by your local jurisdiction.
Sources & References
- National Electrical Code (NFPA 70): Table 310.16 and related articles (240.4(D), 110.14(C), 334.80, 310.15)
- Cerrowire: Ampacity Charts (NEC Table 310.16, 2017 NEC basis)
- NFPA: 2026-edition National Electrical Code First Draft report (Table 310.16 ampacities, FR-8036)
- Michigan State University: Electrical Tech Note 212, Conductor Properties, Table 212.1 (DC resistance at 75C, stranded)
- Encore Wire: Wire Ampacity Size Table (NEC 240.4(D): overcurrent protection no more than 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10 AWG copper)
- ExpertCE: How to Use NEC Table 310.16 (NEC 110.14(C): the temperature rating used can't exceed the lowest rating of any termination, conductor or device; table based on 30°C (86°F) and no more than three current-carrying conductors; 10 AWG copper typical for a 30 A dryer)
- NFPA: 2026-edition National Electrical Code First Draft report, Code-Making Panel 2 (210.19(A)(1) and 210.20(A): conductors and breakers sized at the noncontinuous load plus 125 percent of the continuous load)
- IAEI Magazine, Focus on the Code, November/December 2012 (NEC Article 100: a continuous load is one where the maximum current is expected to continue for 3 hours or more)
- U.S. DOE Alternative Fuels Data Center: Plug-In Electric Vehicle Handbook for Electrical Contractors (EV supply equipment is a continuous load under the NEC)
- Mike Holt Enterprises: Electrical Exam Preparation (2020 NEC), Unit 8.6 (the Code's informational notes recommend voltage drop of no more than 3% for a branch circuit or feeder and 5% combined)
- IAEI Magazine, L. Keith Lofland, Air-Conditioning Equipment Installations (July/August 2017): the nameplate's minimum supply circuit ampacity sets the minimum branch-circuit conductor size; its maximum fuse or circuit breaker size is the largest permitted
- North Carolina Office of State Fire Marshal: Air-Conditioning and Refrigerating Equipment Branch Circuit Ampacity and Protection (June 28, 2017): Articles 440 and 430 modify the general rules of Article 240; the nameplate maximum can't be exceeded
- NIST (National Bureau of Standards) Handbook 100, Copper Wire Tables (1966): No. 0000 is 0.4600 inch and No. 36 is 0.0050 inch with 38 sizes between; every three gage numbers the cross section doubles or halves; stranded conductors are specified in circular mils
- ENERGY STAR: Heat Pump Water Heater Installation Guide (a 240 V unit typically uses a 30-amp breaker and 10-gauge wire)
Related Articles
Home Electrical Wiring Guide: Wire Sizes, Breakers & Safety
Guide • 12 min read
Wire Size for 220V/240V Circuits (30, 40 & 50 Amp): NEC Reference & the 4 Factors That Change It
Guide • 12 min read
Water Heater Wire & Breaker Size Chart: AWG Gauge & Amps
Reference • 12 min read
How Many Amps Does a House Use? (Service Size and Load)
Explainer • 10 min read