Homes run on single-phase power[3]; three-phase supplies larger loads, such as the 40-hp motor[6] in the Department of Energy's motor-load example. Its formulas carry an extra factor, the square root of three, because the three phases peak at different moments and share the load.

For three-phase power, amps = kW × 1,000 ÷ (volts × 1.732 × power factor). At 480 volts and a power factor of 0.85, 10 kW draws about 14.2 amps, and 50 amps delivers about 35.3 kW.

Three-Phase Power Calculator

P = √3 × V × I × PF, full electrical analysis for industrial systems.

1

Configuration

Wye vs delta + input convention

2

Measurements

Voltage, current, power factor

V
A
3

Your electricity rate

For the energy-cost estimates below

$/kWh

The calculator starts at $0.18 per kWh, EIA’s U.S. residential average for January to August 2026; enter your own rate.

Enter your values and click Calculate, press Enter in any field.
Three sine waves for phases A, B and C offset by 120 degrees, beside the three-phase power formulas: kVA equals volts times amps times the square root of 3 divided by 1,000, and kW also multiplies by the power factor.
Three phases 120 degrees apart deliver steady total power.

The formulas

With line-to-line voltage V, line current I and power factor PF:

  • Apparent power (kVA) = V × I × √3 ÷ 1,000
  • Real power (kW) = V × I × √3 × PF ÷ 1,000
  • Amps from kW = kW × 1,000 ÷ (V × √3 × PF)
  • Amps from kVA = kVA × 1,000 ÷ (V × √3)

√3 is about 1.732 (1.732 × 1.732 = 3.0). The calculator also accepts phase values instead of line values, and shows reactive power, horsepower and energy over time.

Quick reference: kW to amps

Load208 V240 V480 V600 V
5 kW
16.3 A
14.2 A
7.1 A
5.7 A
10 kW
32.7 A
28.3 A
14.2 A
11.3 A
25 kW
81.6 A
70.8 A
35.4 A
28.3 A
50 kW
163.3 A
141.5 A
70.8 A
56.6 A
100 kW
326.6 A
283.0 A
141.5 A
113.2 A
How this was calculated: amps equal kW times 1,000 divided by (volts times the square root of 3 times a 0.85 power factor), the three-phase formula stated above

These use an assumed power factor of 0.85 for motor loads. For purely resistive loads such as heaters (power factor 1.0), the current is 15% lower: 10 kW at 480 volts draws 12.0 amps (10,000 ÷ (480 × 1.732 × 1.0)).

Power triangle with real power in kW, a reactive part and apparent power in kVA, plus an example: 10 kW at 480 volts is 11.8 kVA and 14.2 amps at a power factor of 0.85, or 10 kVA and 12.0 amps at 1.0.
A lower power factor means more current for the same real power.

Power factor

Power factor is the share of the current that does useful work: kW ÷ kVA. Resistive loads such as heaters run near 1.0; inductive loads such as motors and transformers run lower[5], because part of their current flows back and forth without doing work. A lower power factor means more current for the same real power, which sets the size of wires and breakers.

Wye and delta

  • Wye (Y): each phase connects between a line and a shared neutral. Line voltage = √3 × phase voltage, and line current = phase current. A 208Y/120 system gives 120 volts from each line to neutral.
  • Delta (Δ): each phase connects between two lines. Line voltage = phase voltage, and line current = √3 × phase current.

The calculator converts between line and phase values for either connection.

Single-phase vs. three-phase

Homes run on single-phase power: the residential code limits the home services it covers to single-phase systems of 120/240 volts[3], up to 400 amps[3]. For the same power, three-phase uses less current per conductor: 10 kW at 240 volts and a power factor of 1.0 draws 41.7 amps single-phase (10,000 ÷ 240) but 24.1 amps three-phase (10,000 ÷ (240 × 1.732)). Less current means smaller conductors for the same load.

For single-phase loads, the power consumption calculator turns volts and amps into watts and kWh.

Motors and horsepower

One horsepower is 745.7 watts[1]. A motor's electrical input is its shaft output divided by its efficiency: a 10 hp motor at full output and 90% efficiency draws about 8,286 watts (10 × 745.7 ÷ 0.90). For sizing conductors and protection on a general motor circuit, the National Electrical Code has electricians use the full-load currents in its motor tables (Table 430.250 for three-phase motors), not the motor's nameplate current[4].

Frequently asked questions

How many amps is 10 kW three-phase?

About 14.2 amps at 480 volts (10,000 ÷ (480 × 1.732 × 0.85)), 28.3 at 240 and 32.7 at 208, at a power factor of 0.85. At a power factor of 1.0 the current is 15% lower.

How do I convert amps to kW for three-phase?

kW = volts × amps × 1.732 × power factor ÷ 1,000. 50 amps at 480 volts and 0.85 is about 35.3 kW.

Why is the square root of 3 in three-phase formulas?

The three phases are 120 degrees apart, so the voltage between two lines is √3 times the voltage of one phase.

What's the difference between kW and kVA?

kVA is apparent power, volts times amps. kW is the real power that does work: kVA times the power factor.

Sources & References

  1. NIST Special Publication 811, Appendix B.9: horsepower (550 ft·lbf/s) = 745.6999 W
  2. EIA Electric Power Monthly, residential average retail price (about $0.18/kWh, January to August 2026); the calculator's default rate
  3. ICC: 2021 International Residential Code, Chapter 34, Section E3401.2 (services limited to 120/240-volt, 0- to 400-ampere, single-phase systems)
  4. EC&M: Eddie Guidry, Motor Nameplate Current vs. NEC Full Load Current Values (May 23, 2017): NEC 430.6(A)(1) table currents instead of nameplate current
  5. U.S. DOE Motor Challenge fact sheet: Reducing Power Factor Cost (power factor is the ratio of real to apparent power; low power factor comes from inductive loads such as transformers, electric motors and HID lighting; utilities usually charge a penalty below 0.95; originally published by the Bonneville Power Administration)
  6. U.S. DOE fact sheet: Determining Electric Motor Load and Efficiency (three-phase power = V × I × PF × √3 ÷ 1,000; the 40-hp, 1800 rpm motor example)
  7. U.S. DOE Advanced Manufacturing Office: Turn Motors Off When Not in Use, Motor Systems Tip Sheet 10 (a NEMA Design B motor may draw four to eight times full-load current while starting, usually for under 2 seconds)
  8. NFPA: 2026-edition National Electrical Code First Draft report, Code-Making Panel 6 (Table 310.16 ampacities)
  9. Encore Wire: Wire Ampacity Size Table (NEC 240.4(D): overcurrent protection no more than 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10 AWG copper)
  10. Mike Holt Enterprises: Electrical Exam Preparation (2020 NEC), Unit 8.6 (the Code's informational notes recommend voltage drop of no more than 3% for a branch circuit or feeder and 5% combined)

Related Articles