KEEP+

Wire for 220V Circuits: AWG Gauge for 10–200 Amps (2026 NEC Guide)

Complete wire sizing chart for 220/240V circuits from 10 to 200 amps. Covers NEC requirements for AC units, water heaters, dryers, ranges, EV chargers, and sub-panels with voltage drop calculations.

HVAC Base TeamUpdated February 5, 202621 min read

For a 220/240V circuit at 30 amps, you need 10 AWG copper wire; at 50 amps, 6 AWG copper; and at 100 amps, 3 AWG copper — but wire runs over 50 feet require upsizing for voltage drop. These are the minimum NEC-compliant wire sizes, and choosing correctly is the difference between a safe installation and a fire waiting to happen.

Whether you're wiring a central air conditioner, electric water heater, dryer, range, EV charger, or sub-panel, this guide gives you the exact wire gauge for every 220V amperage from 10A to 200A, including voltage drop adjustments for long runs.

Quick Note: "220V" vs. "240V" vs. "230V"

People say "220 volt" out of habit, but residential "high-voltage" circuits in the U.S. are actually 240V nominal (measured at the transformer) and often labeled 208V or 230V on equipment nameplates to account for normal voltage variation.

All three terms refer to the same circuit type: two hot conductors from opposite legs of the split-phase service, creating a 240V potential between them. Throughout this guide, "220V" and "240V" are used interchangeably because the wire sizing requirements are identical.

Master Wire Size Chart: 220/240V Circuits (10–200 Amps)

This chart shows the minimum copper and aluminum wire gauges for 220/240V circuits based on NEC Table 310.16 (60°C and 75°C columns) with maximum recommended wire run length at 3% voltage drop.

AmperageBreaker SizeCopper AWG (60°C, NM-B)Copper AWG (75°C, THWN)Aluminum AWG (75°C)Max Run at 3% Drop (Copper, 60°C)
10A15A DP14 AWG14 AWG12 AWG179 ft (14 AWG)
15A20A DP12 AWG12 AWG10 AWG145 ft (12 AWG)
20A25A–30A DP10 AWG12 AWG10 AWG145 ft (10 AWG)
25A30A DP10 AWG10 AWG8 AWG116 ft (10 AWG)
30A30A DP10 AWG10 AWG8 AWG97 ft (10 AWG)
35A40A DP8 AWG8 AWG6 AWG132 ft (8 AWG)
40A40A DP8 AWG8 AWG6 AWG115 ft (8 AWG)
45A50A DP6 AWG8 AWG6 AWG107 ft (6 AWG)
50A50A DP6 AWG6 AWG4 AWG97 ft (6 AWG)
60A60A DP6 AWG*6 AWG4 AWG81 ft (6 AWG)
70A70A DP4 AWG4 AWG3 AWG106 ft (4 AWG)
80A80A DP3 AWG4 AWG2 AWG92 ft (3 AWG)
90A90A DP3 AWG3 AWG1 AWG82 ft (3 AWG)
100A100A DP1 AWG3 AWG1/0 AWG112 ft (1 AWG)
125A125A DP1/0 AWG1 AWG2/0 AWG95 ft (1/0 AWG)
150A150A DP1/0 AWG1/0 AWG3/0 AWG79 ft (1/0 AWG)
175A175A DP2/0 AWG2/0 AWG4/0 AWG77 ft (2/0 AWG)
200A200A DP3/0 AWG2/0 AWG4/0 AWG79 ft (3/0 AWG)

*NEC 240.4(B) allows the next standard breaker size above the wire's ampacity. 6 AWG copper at 60°C = 55A, so a 60A breaker is permitted.

Warning

DP = Double-Pole breaker. All 220/240V circuits require a double-pole breaker that connects to both bus bars in the panel. A single-pole breaker only provides 120V. If you see a "220V" circuit on a single-pole breaker, something is seriously wrong.

Wire Size by Application (220/240V)

Air Conditioning and Heat Pumps

EquipmentTypical Amps (MCA)Wire GaugeBreaker (MOP)Cable
1.5-ton AC10–14A14–12 AWG15–20A DP14/2 or 12/2 NM-B
2-ton AC13–17A12–10 AWG20–25A DP12/2 or 10/2 NM-B
2.5-ton AC15–19A10 AWG25–30A DP10/2 NM-B
3-ton AC17–22A10 AWG30A DP10/2 NM-B
3.5-ton AC20–25A10 AWG30–35A DP10/2 NM-B
4-ton AC22–28A10–8 AWG35–40A DP8/2 or THHN in conduit
5-ton AC28–35A8–6 AWG45–50A DPTHHN in conduit
Heat pump (3-ton)19–24A10 AWG30–35A DP10/2 NM-B
Heat pump (5-ton)30–40A8–6 AWG45–60A DPTHHN in conduit
Important

Always use the equipment nameplate, not this table, for final wire sizing. The MCA (Minimum Circuit Ampacity) determines your minimum wire size, and the MOP (Maximum Overcurrent Protection) determines your maximum breaker size. These values account for motor starting currents that generic charts can't predict.

Water Heating

EquipmentWattageAmps at 240VWire GaugeBreakerCable
Tank water heater (30 gal)3,500–4,000W14.6–16.7A12 AWG20A DP12/2 NM-B
Tank water heater (40–50 gal)4,500W18.75A10 AWG30A DP10/2 NM-B
Tank water heater (65–80 gal)5,500W22.9A10 AWG30A DP10/2 NM-B
Tankless (11kW)11,000W45.8A6 AWG60A DP6/2 NM-B
Tankless (18kW)18,000W75A (2×37.5A)2 × 8 AWG2 × 40A DP2 × 8/2 NM-B
Tankless (27kW)27,000W112.5A (3×37.5A)3 × 8 AWG3 × 40A DP3 × 8/2 NM-B
Heat pump water heater500–600W (plus 4,500W backup)2.1–18.75A10 AWG30A DP10/2 NM-B

Cooking and Laundry

EquipmentTypical AmpsWire GaugeBreakerCableNotes
Electric dryer24–30A10 AWG30A DP10/3 NM-BNeeds neutral (4-wire)
Electric range (small)30–40A8–6 AWG40–50A DP6/3 NM-BNeeds neutral (4-wire)
Electric range (large)40–50A6 AWG50A DP6/3 NM-BNeeds neutral (4-wire)
Double oven40–50A6 AWG50A DP6/3 NM-BNeeds neutral (4-wire)
Cooktop + wall ovenSeparate circuitsVariesVariesVariesEach on its own circuit
Pro Tip

Dryers and ranges need 4-wire connections (two hots + neutral + ground) because they contain both 240V heating elements and 120V controls. This requires /3 cable (10/3 for dryers, 6/3 for ranges). AC units, water heaters, and EV chargers typically need only /2 cable (two hots + ground, no neutral).

EV Charging

Charger RatingCircuit Amps (Continuous)Breaker (125% of load)Wire GaugeCable
Level 2, 16A16A20A DP12 AWG12/2 NM-B
Level 2, 24A24A30A DP10 AWG10/2 NM-B
Level 2, 32A32A40A DP8 AWG8/2 NM-B
Level 2, 40A40A50A DP6 AWG6/2 NM-B
Level 2, 48A48A60A DP6 AWG6/2 THHN
Level 2, 80A80A100A DP3 AWG3 AWG THHN

Sub-Panels and Feeders

Sub-Panel RatingWire Gauge (Copper)Wire Gauge (Aluminum)Breaker at MainNotes
30A10 AWG8 AWG30A DPSmall workshop
40A8 AWG6 AWG40A DPGarage
50A6 AWG4 AWG50A DPGarage/workshop
60A6 AWG4 AWG60A DPStandard garage
100A3 AWG (Cu) or 1 AWG (Al)1/0 AWG100A DPLarge garage/ADU
125A1 AWG2/0 AWG125A DPAccessory dwelling
150A1/0 AWG3/0 AWG150A DPLarge ADU
200A2/0 AWG (Cu) or 4/0 AWG (Al)4/0 AWG200A DPSeparate structure

Voltage Drop Tables for 220/240V Circuits

Voltage drop is the most common reason to upsize wire beyond the NEC minimum. Here's how much voltage you lose at various distances and amperages.

Voltage Drop in Volts (Copper Wire, 240V Circuit)

Wire Gauge25 ft50 ft75 ft100 ft150 ft200 ft
14 AWG at 15A2.4V4.7V7.1V9.4V14.1V18.8V
12 AWG at 20A2.0V4.0V5.9V7.9V11.9V15.8V
10 AWG at 30A1.9V3.7V5.6V7.4V11.2V14.9V
8 AWG at 40A1.6V3.1V4.7V6.2V9.3V12.5V
6 AWG at 50A1.2V2.5V3.7V4.9V7.4V9.8V
4 AWG at 70A1.1V2.2V3.2V4.3V6.5V8.6V
2 AWG at 100A1.0V1.9V2.9V3.9V5.8V7.8V

Percentage Voltage Drop (3% Limit = 7.2V on 240V)

Wire Gauge25 ft50 ft75 ft100 ft150 ft200 ft
14 AWG at 15A1.0%2.0%3.0%❌ 3.9%❌ 5.9%❌ 7.8%
12 AWG at 20A0.8%1.7%2.5%❌ 3.3%❌ 5.0%❌ 6.6%
10 AWG at 30A0.8%1.6%2.3%❌ 3.1%❌ 4.7%❌ 6.2%
8 AWG at 40A0.7%1.3%2.0%2.6%❌ 3.9%❌ 5.2%
6 AWG at 50A0.5%1.0%1.5%2.0%3.1%❌ 4.1%
4 AWG at 70A0.4%0.9%1.3%1.8%2.7%❌ 3.6%
2 AWG at 100A0.4%0.8%1.2%1.6%2.4%❌ 3.2%

❌ = Exceeds 3% voltage drop — upsize wire for this distance.

Warning

3% on the branch circuit, 5% total. The NEC recommends no more than 3% voltage drop on any branch circuit and no more than 5% total from the service entrance to the farthest outlet. If your feeder already drops 2%, your branch circuit should stay under 3% — giving you only 3% remaining on the branch.

When to Upsize Wire (Beyond NEC Minimum)

Scenario 1: Long Run to AC Condenser

Setup: 3-ton AC condenser (MCA 19A, MOP 30A) located 120 feet from the panel.

NEC minimum: 10 AWG copper, 30A breaker.

Voltage drop check: (2 × 120 × 19 × 1.24) / 1000 = 5.65V → 2.4% on 240V.

Decision: 10 AWG works at 2.4% — under the 3% limit. But if you're also feeding through a long feeder, upsize to 8 AWG for margin. Cost difference: about $0.55/ft × 120 ft = $66 more for 8/2 vs. 10/2.

Scenario 2: EV Charger in Detached Garage

Setup: 48A EV charger (continuous load) in a garage 80 feet from the main panel.

NEC minimum: 6 AWG copper, 60A breaker.

Voltage drop check: (2 × 80 × 48 × 0.491) / 1000 = 3.77V → 1.6% on 240V.

Decision: 6 AWG is fine at 1.6%. However, if you might upgrade to a higher-amperage charger in the future, running 4 AWG now ($1.30/ft × 80 ft = $104 more) saves you from re-pulling wire later.

Scenario 3: Electric Range Far from Panel

Setup: Electric range (40A continuous) in a kitchen 60 feet from the panel.

NEC minimum: 6 AWG copper (for 50A breaker), 6/3 NM-B (needs neutral).

Voltage drop check: (2 × 60 × 40 × 0.491) / 1000 = 2.36V → 1.0% on 240V.

Decision: 6/3 NM-B is perfect. No need to upsize at this distance.

Scenario 4: 200A Sub-Panel to Detached Workshop

Setup: 200A sub-panel feeding a woodworking shop 150 feet from the main panel.

NEC minimum: 2/0 AWG copper or 4/0 AWG aluminum.

Voltage drop check (aluminum): (2 × 150 × 200 × 0.100) / 1000 = 6.0V → 2.5% on 240V.

Decision: 4/0 aluminum at 2.5% — acceptable but tight. For a 150-foot run at 200A, 250 kcmil aluminum ($3.50–$5.00/ft) provides more comfortable margin at 1.8% drop.

2-Wire vs. 3-Wire vs. 4-Wire: Which Do You Need?

This is one of the most confusing aspects of 220/240V wiring. Here's the definitive breakdown.

ConfigurationWiresCableUse CaseExamples
2-wire + ground2 hots + ground/2 (e.g., 10/2)240V-only loads, no 120V componentsAC, water heater, well pump
3-wire + ground2 hots + neutral + ground/3 (e.g., 10/3)240V loads with 120V componentsDryer, range, oven
2-wire (no ground, legacy)2 hots onlyOld /2 no groundPre-1960s installationsReplace immediately
3-wire (no ground, legacy)2 hots + neutralOld /3 no groundPre-1996 dryer/range outletsUpgrade to 4-wire

The key question: Does the appliance need 120V power in addition to 240V?

  • No (AC, water heater, baseboard heater, well pump) → Use /2 cable
  • Yes (dryer, range, oven with clock/light, spa with 120V pump) → Use /3 cable
Real-World Example

Real-world example: Your electric dryer has a 240V heating element AND a 120V motor plus a drum light. The heating element uses both hot wires (240V). The motor and light each use one hot wire and the neutral (120V). Without a neutral, the motor and light can't work. That's why dryers need 10/3 cable (3 insulated conductors + ground = 4 wires total).

Copper vs. Aluminum for 220V Circuits

For branch circuits under 6 AWG, copper is standard. For larger feeders and service entrance conductors, aluminum offers significant cost savings.

FactorCopperAluminum
30A circuit wire cost (per ft)$0.65–$1.00 (10/2 NM-B)Not practical at this size
50A circuit wire cost (per ft)$2.50–$3.80 (6/2 NM-B)$1.00–$1.60 (4 AWG SE)
100A feeder cost (per ft)$4.00–$6.00 (3 AWG)$1.50–$2.50 (1/0 AWG)
200A service cost (per ft)$8.00–$12.00 (2/0 AWG)$2.50–$4.00 (4/0 AWG)
ConnectionsStandard terminalsAnti-oxidant compound + AL-rated terminals
Expansion/contractionMinimalSignificant — needs proper torque
Code restrictionsNoneNot for <6 AWG branch circuits (practical limitation)

Bottom line: Use copper for 220V branch circuits (AC, water heater, dryer, range). Consider aluminum for 100A+ feeders and service entrance where cost savings are substantial — $300–$800+ on a 200A, 100-foot run.

Real-World Wiring Examples

Example 1: Wiring a 4-Ton Central AC

Equipment: Lennox XC21-048-230 (4-ton, 21 SEER2). Nameplate: MCA 24.8A, MOP 40A, 208/230V.

Step 1 — Wire size: MCA 24.8A → need wire rated ≥24.8A. 10 AWG at 60°C = 30A ✓. However, MOP is 40A, so the breaker is 40A. For a 40A breaker, NEC requires 8 AWG minimum (40A at 60°C).

Wait — this is a common confusion point. NEC 440.22 allows the breaker to be sized by MOP, and NEC 440.32 says the wire is sized by MCA. You can use 10 AWG wire (rated 30A, which exceeds MCA of 24.8A) with a 40A breaker — this is legal for motor circuits under NEC Article 440.

Step 2 — Run length: 50 feet. Voltage drop: (2 × 50 × 24.8 × 1.24) / 1000 = 3.1V → 1.3% ✓

Step 3 — Cable: 10/2 NM-B from panel to pull-out disconnect, 10 AWG THHN in flex conduit from disconnect to unit.

Step 4 — Breaker: 40A double-pole.

Example 2: Wiring a Tesla Wall Connector

Equipment: Tesla Wall Connector Gen 3 set to 48A output. Continuous load.

Step 1 — Breaker: 48A × 1.25 = 60A (continuous load, 80% rule) → 60A double-pole breaker.

Step 2 — Wire: 60A breaker → NEC allows 6 AWG copper (55A at 60°C, next standard breaker size per 240.4(B)).

Step 3 — Run length: 35 feet to garage wall. Voltage drop: (2 × 35 × 48 × 0.491) / 1000 = 1.65V → 0.7% ✓

Step 4 — Cable: 6/2 NM-B, straight run through interior wall to garage. No neutral needed.

Example 3: Wiring an Electric Tankless Water Heater

Equipment: Stiebel Eltron Tempra 24 Plus (24kW, 240V). Requires 2 × 50A circuits.

Step 1 — Per circuit: 24kW ÷ 2 = 12kW per circuit → 12,000W ÷ 240V = 50A per circuit. Continuous load: 50A × 1.25 = 62.5A → but wait, the manufacturer specs 2 × 50A breakers.

Step 2 — Wire per circuit: 50A breaker → 6 AWG copper. Run length: 15 feet → voltage drop negligible.

Step 3 — Cable: Two runs of 6/2 NM-B. Each breaker takes 2 panel spaces → 4 spaces total.

Step 4 — Panel check: Two 50A circuits draw 100A at full load. If you have a 200A panel, that's 50% of your service just for hot water. This is why tankless electric heaters often trigger a panel upgrade.

Example 4: Feeding a 100A Sub-Panel in Detached Garage

Equipment: 100A sub-panel, 100 feet underground from main panel.

Step 1 — Feeder wire: 100A → 3 AWG copper or 1/0 AWG aluminum.

Step 2 — Voltage drop (aluminum): (2 × 100 × 100 × 0.201) / 1000 = 4.02V → 1.7% ✓

Step 3 — Wire type: Underground → THWN-2 conductors in Schedule 40 PVC conduit (1.25" minimum for 4 conductors of 1/0 AWG aluminum).

Step 4 — Ground rod: Detached building requires its own grounding electrode system — two 8-foot ground rods minimum, bonded together.

Step 5 — Cost comparison:

  • 3 AWG copper (4 conductors × 100 ft × $1.40/ft) = $560
  • 1/0 AWG aluminum (4 conductors × 100 ft × $0.60/ft) = $240
  • Savings: $320 by using aluminum

Key Takeaways

Key Takeaway
  • 30A / 240V → 10 AWG copper — covers most central AC units and electric water heaters
  • 50A / 240V → 6 AWG copper — covers electric ranges, large AC units, and EV chargers
  • 100A / 240V → 3 AWG copper or 1/0 AWG aluminum — standard for sub-panels
  • 200A / 240V → 2/0 AWG copper or 4/0 AWG aluminum — service entrance size
  • Always check voltage drop on runs over 50 feet — upsize wire if drop exceeds 3%
  • Use /2 cable for 240V-only loads (AC, water heater) and /3 cable for loads needing neutral (dryer, range)
  • HVAC equipment: Use nameplate MCA for wire sizing and MOP for breaker sizing — don't guess
  • Aluminum saves 40–60% on large feeders (100A+) — use it for service entrance and sub-panel runs

Frequently Asked Questions

Related Articles