You're adding a dryer, an EV charger, a range or a hot tub, and you need to know one thing: what size wire does this 240-volt circuit need? The NEC answers it with an ampacity table, and four factors can change that answer.

Wire size isn't just a lookup by amperage. It also depends on whether the load runs continuously (like an EV charger), the wire's temperature rating, copper or aluminum, and the length of the run. Below: the standard NEC reference sizes and the four factors that change them.

The wire-to-amperage pairings follow the National Electrical Code (NEC).

One thing up front: ask your local building department whether your new 240-volt circuit needs a permit and inspection, and have a licensed electrician do or verify the work. Use this page to understand what your circuit needs, then confirm the sizing against your appliance's nameplate and your local code.

The NEC minimum copper wire sizes for common 240V circuits: 30 amps needs 10 AWG[3], 40 amps needs 8 AWG[3], and 50 amps needs 6 AWG[3]. Those are baselines: continuous loads, long runs, aluminum wire and your appliance's nameplate can all change what you need, so read the next sections before you buy wire.

Copper conductors drawn to scale for 240-volt circuits: 12 AWG for 20 amps, 10 AWG for 30, 8 AWG for 40, 6 AWG for 50, 6 or 4 AWG for 60 and 3 AWG for 100 amps, from 2.05 to 5.83 millimeters across.
Minimum copper sizes from the table below, drawn to scale.

The standard reference sizes (NEC minimums)

For a standard 240V circuit with copper wire at typical conditions, these are the NEC minimum wire gauges by breaker size. This is your starting point, not your final answer (the next section explains why).

Breaker / circuitMinimum copper wireExample
20 amp
12 AWG
30 amp
10 AWG
Electric dryer; 240 V heat pump water heater
40 amp
8 AWG
A continuous load up to 32 A (32 × 1.25 = 40)
50 amp
6 AWG
A 40 A EV charger (40 × 1.25 = 50)
60 amp
6 AWG at 75°C, or 4 AWG at 60°C
A 48 A EV charger (48 × 1.25 = 60)
100 amp
3 AWG at 75°C
NEC Table 310.16 copper ampacities, as printed in NFPA's 2026-edition first-draft report and Cerrowire's ampacity chart, with the NEC 240.4(D) limits for 12 and 10 AWG. The 20- to 50-amp rows use the 60°C column that NM-B cable is held to; 6 AWG at 60 amps and 3 AWG at 100 amps are 75°C-column sizes. Examples: dryer from ExpertCE, heat pump water heater from ENERGY STAR's installation guide, EV chargers from the NEC 125% rule.

These follow the NEC ampacity tables (Table 310.16) and the small-conductor rule (NEC 240.4(D)), which is why, for example, 10 AWG copper is capped at 30 amps[8] on a branch circuit even though its raw ampacity is slightly higher[3].

The 20- to 50-amp rows assume NM-B cable[7], which is held to the 60°C column[7]. Individual THHN conductors in conduit with 75°C terminations carry more: 8 AWG copper is rated 50 A at 75°C[3], and the table's 6 AWG at 60 amps and 3 AWG at 100 amps[3] need 75°C-rated wire and terminations (in NM-B, 60 amps takes 4 AWG[3]). Air conditioners and heat pumps follow their nameplate instead: NEC Articles 440 and 430 modify the general rules of Article 240 for this equipment[12].

Diagram of the EV charger trap: a 40-amp continuous load times 125 percent needs a 50-amp breaker and, in NM-B cable, 6 AWG copper, not 8 AWG; plus three more factors: the wire's temperature rating, copper versus aluminum and voltage drop on long runs.
The four factors, with the EV charger example from below.

The four things that change your wire size

The table above is a starting point, and four factors can push you to a larger wire.

Continuous loads need 25% more (the EV charger trap)

The NEC calls a load continuous when its maximum current runs for 3 hours or more[5], and an EV charger always counts as one[6]. Circuits for continuous loads must be sized at 125% of the load[4]. A 40-amp EV charger, for example, draws 40 amps continuously, and 8 AWG is rated 40 A at 60°C and 50 A at 75°C[3].

But the 125% rule means that 40-amp continuous load needs a 50-amp breaker (40 × 1.25 = 50) and, in NM-B cable, 6 AWG copper, not 8 AWG, because 6 AWG is rated 55 A in the 60°C column[3]. Getting this wrong means the wire runs hot for hours at a time.

Wire temperature rating matters (the 60/75/90°C columns)

The same gauge wire has different ampacity depending on its insulation's temperature rating, and NM-B cable (Romex) is held to the lowest, 60°C column[7]. 6 AWG copper is rated 55 A in the 60°C column[3], 65 A at 75°C and 75 A at 90°C[3]. So what a 6 AWG wire can carry depends on the wire type and the terminations, not just the gauge.

Copper vs. aluminum are not interchangeable

In Table 310.16, aluminum carries less current than copper of the same gauge, so it has to be sized up: a circuit that needs 6 AWG copper needs 4 AWG aluminum[3] for the same job. Using an aluminum conductor at a copper gauge undersizes it, so with aluminum wire every size in the table above goes up.

Long runs need thicker wire (voltage drop)

At full load, a 240 V circuit reaches a 3% voltage drop at about 97 feet on 10 AWG copper at 30 A, about 116 feet on 8 AWG at 40 A, and about 147 feet on 6 AWG at 50 A (run length = 3% of 240 volts ÷ (2 conductors × amps × the wire's resistance per foot), with copper resistance from Michigan State University's conductor table[9]). The NEC's informational notes, which are advice rather than requirements, suggest no more than 3% on a branch circuit and 5% combined[2] with the feeder, and a long run can require going up a wire size (or more) to stay within that, even though the ampacity table says the smaller wire is "fine." For example, a 48 A charger needs a 60-amp circuit (48 × 1.25 = 60), which 6 AWG copper meets only with 75°C-rated wire and terminations[3]; at 150 feet that 6 AWG drops about 2.9% at full load, just inside 3%, and 4 AWG drops about 1.8%.

Your appliance nameplate: MCA and maximum breaker

For hardwired 240V equipment, especially AC units and EV chargers, the appliance's data plate sets the circuit. Look for two ratings:

  • Minimum Circuit Ampacity (MCA): sets the minimum branch-circuit conductor size[11].
  • Maximum fuse or breaker size (often shown as MOP): the largest overcurrent device permitted[11].

Size your wire and breaker to these nameplate numbers, not to a generic chart. For air conditioning equipment, NEC Articles 440 and 430 modify the general rules, and the nameplate maximum can't be exceeded[12], so the nameplate wins.

"Can I do this myself?"

Permit rules are local, so start with your building department: ask whether your circuit needs a permit and an inspection, and who may do the work. The mistakes this page covers (wrong gauge, a missed 125% continuous-load step[4], the wrong temperature column) are the ones an inspection checks for.

Our recommendation: use this page to understand your circuit, then have a licensed electrician do or verify the work and handle any permit. If you do it yourself, get it inspected wherever your jurisdiction allows that.

Frequently asked questions

What size wire do I need for a 240V dryer? A 30-amp dryer circuit[10] typically uses 10 AWG copper on a 30-amp breaker[8]. Check your dryer's nameplate and installation instructions for its circuit.

What size wire for a 50-amp 240V circuit? In NM-B cable, the NEC minimum is 6 AWG copper for a 50-amp circuit[3], rated 55 A in the 60°C column[3]. But if it's a continuous load like an EV charger, remember the 125% rule[4], and on long runs, voltage drop may require upsizing.

Aluminum would need to be larger (about 4 AWG[3]). Always confirm against the appliance nameplate and your local code.

What wire do I need for a 40-amp EV charger? This is the classic trap. A 40-amp EV charger is a continuous load[6], so the NEC 125% rule[4] means it needs a 50-amp breaker (40 × 1.25) and, in NM-B cable, 6 AWG copper, not the 8 AWG that 40 amps alone would suggest. On long runs it may need to go larger still for voltage drop.

Is 240V wiring something I can do myself? It depends on your local rules, so ask your building department whether the circuit needs a permit and inspection, and who may do the work. Our recommendation is a licensed electrician; if you do it yourself, get it inspected.

Does copper or aluminum wire change the size I need? Yes. In Table 310.16, aluminum carries less current than copper of the same gauge, so every size goes up[3].

A circuit needing 6 AWG copper needs 4 AWG aluminum[3]. Don't substitute one for the other by matching gauge numbers.

About these figures

The wire-to-amperage pairings and the rules that govern them are from the National Electrical Code (NEC / NFPA 70): the conductor ampacity table (Table 310.16)[3], the small-conductor rule (240.4(D))[8], the continuous-load 125% requirement[4] and the voltage-drop recommendations in its informational notes[2]. The nameplate rules for air conditioning equipment are from IAEI[11] and the North Carolina Office of State Fire Marshal[12].

Because wire sizing depends on conductor material, insulation temperature rating, ambient conditions, load type and run length, the sizes here are minimum references for typical conditions, not universal answers. Size every circuit to the appliance's nameplate and confirm it with a licensed electrician and your local code.

Sources & References

  1. NFPA 70: National Electrical Code (NEC): the standard that defines these wire sizes (Table 310.16, 240.4(D), 210.19)
  2. Mike Holt Enterprises: Electrical Exam Preparation (2020 NEC), Unit 8.6 (the Code's informational notes recommend voltage drop of no more than 3% for a branch or feeder and 5% combined)
  3. NFPA: 2026-edition National Electrical Code First Draft report, Code-Making Panel 6 (Table 310.16 ampacities: copper 12 AWG 20/25/30 A, 10 AWG 30/35/40 A, 8 AWG 40/50/55 A, 6 AWG 55/65/75 A, 4 AWG 70/85/95 A, 3 AWG 85/100/115 A at 60/75/90°C; aluminum 4 AWG 55/65/75 A)
  4. NFPA: 2026-edition National Electrical Code First Draft report, Code-Making Panel 2 (210.19(A)(1) and 210.20(A): conductors and breakers sized at the noncontinuous load plus 125 percent of the continuous load)
  5. IAEI Magazine, Focus on the Code, November/December 2012 (NEC Article 100 defines a continuous load as one where the maximum current is expected to continue for 3 hours or more)
  6. U.S. DOE Alternative Fuels Data Center: Plug-In Electric Vehicle Handbook for Electrical Contractors (EV supply equipment is a continuous load under the NEC)
  7. Cerrowire: Ampacity Charts (NEC Table 310.16; NM-B cable is in the 60°C column)
  8. Encore Wire: Wire Ampacity Size Table (NEC 240.4(D): overcurrent protection no more than 20 amperes for 12 AWG and 30 amperes for 10 AWG copper)
  9. Michigan State University: Electrical Tech Note 212, Conductor Properties, Table 212.1 (stranded copper dc resistance at 75°C: 10 AWG 1.24, 8 AWG 0.778, 6 AWG 0.491, 4 AWG 0.308 ohms per 1,000 feet)
  10. ExpertCE: How to Use NEC Table 310.16 (a 30-amp dryer circuit typically uses 10 AWG copper)
  11. IAEI Magazine, L. Keith Lofland, Air-Conditioning Equipment Installations (July/August 2017): the nameplate's minimum supply circuit ampacity sets the minimum branch-circuit conductor size; its maximum fuse or circuit breaker size is the largest permitted
  12. North Carolina Office of State Fire Marshal: Air-Conditioning and Refrigerating Equipment Branch Circuit Ampacity and Protection (June 28, 2017): Articles 440 and 430 modify the general rules of Article 240; the nameplate maximum can't be exceeded
  13. ENERGY STAR: Heat Pump Water Heater Installation Guide (a 240 V unit typically uses a 30-amp breaker and 10-gauge wire)

Related Articles