NEW

What Wire Size for 30 Amp Circuit? (NEC Code Guide 2026)

For a 30-amp circuit, use 10 AWG copper or 8 AWG aluminum wire per NEC 240.4(D). Complete guide covering 30-amp wire sizing for AC units, water heaters, dryers, and long runs with voltage drop calculations.

HVAC Base TeamUpdated February 5, 202616 min read

A 30-amp circuit requires 10 AWG copper wire or 8 AWG aluminum wire — this is mandated by NEC 240.4(D), which sets the maximum overcurrent protection for 10 AWG conductors at exactly 30 amps. Using 12 AWG wire on a 30-amp breaker is a code violation and fire hazard, full stop.

The 30-amp circuit is the workhorse of residential HVAC and water heating. It powers most central air conditioners (2–3.5 tons), standard electric water heaters (up to 5,500W), and electric dryers. Here's everything you need to know to wire it safely and to code.

Quick Answer: 30-Amp Wire Size Chart

Wire Run LengthCopper Wire SizeAluminum Wire SizeCable TypeNotes
0–50 feet10 AWG8 AWG10/2 or 10/3 NM-BStandard installation
50–80 feet10 AWG8 AWG10/2 or 10/3 NM-BVoltage drop 1.6–2.5% — acceptable
80–100 feet10 AWG (marginal)8 AWG10/2 or 10/3 NM-BVoltage drop 2.5–3.1% — consider upsizing
100–150 feet8 AWG6 AWG8/2 or 8/3 NM-BUpsize required to stay under 3% drop
150–200 feet6 AWG6 AWG6/2 or 6/3 NM-BUpsize for voltage drop compliance
200+ feet6 AWG or larger4 AWGTHHN in conduitCalculate individually
Important

NEC 240.4(D) is absolute: 10 AWG wire = 30A maximum breaker. You cannot put 10 AWG wire on a 40A or 50A breaker for general branch circuits. The only exception is motor circuits under NEC Article 440, where the equipment nameplate MOP may specify a larger breaker than the wire's ampacity rating.

What the NEC Says About 30-Amp Wire Sizing

NEC Section 240.4(D) provides the definitive wire-to-breaker relationship for small conductors:

Wire Gauge (Copper)Maximum Overcurrent Protection
14 AWG15 amps
12 AWG20 amps
10 AWG30 amps

These limits apply regardless of the wire's insulation temperature rating. Even though 10 AWG THHN (90°C) has an ampacity of 40A per NEC Table 310.16, the branch circuit breaker is still capped at 30A.

Why 10 AWG for 30 Amps?

At 60°C insulation rating (standard NM-B/Romex), 10 AWG copper wire has an ampacity of exactly 30 amps per NEC Table 310.16. This means the wire can safely carry 30 amps of current continuously without exceeding its temperature limit.

The 30-amp breaker protects this wire by tripping before the current exceeds what the wire can handle. The breaker is sized to the wire — never the other way around.

30-Amp Circuit: 10/2 vs. 10/3 Cable

This is one of the most common wiring questions. The answer depends on what you're powering.

CableConductorsUse ForExamples
10/2 NM-B2 hots + ground (or 1 hot + 1 neutral + ground for 120V)240V loads without neutralCentral AC, heat pump, water heater, well pump
10/3 NM-B2 hots + neutral + ground240V loads with 120V componentsElectric dryer, certain sub-panels

For AC units and water heaters: Use 10/2 cable. These appliances operate on pure 240V — they don't have any 120V components, so they don't need a neutral conductor. The two insulated wires in 10/2 serve as the two hot legs, and the bare wire is the equipment ground.

For electric dryers: Use 10/3 cable. Dryers have a 240V heating element but also a 120V motor and drum light. The third insulated conductor (white) serves as the neutral for these 120V components.

Pro Tip

Cost difference: 10/2 NM-B costs approximately $0.65–$1.00/ft, while 10/3 NM-B costs $0.85–$1.30/ft. For a typical 50-foot run, 10/3 costs about $10–$15 more. Don't waste money on 10/3 if you don't need the neutral — but also don't cheap out and use 10/2 where a neutral is required.

Voltage Drop at 30 Amps: Distance Limits

Wire gauge tables only tell you the minimum safe wire size. Voltage drop determines whether that minimum is actually sufficient for your run length.

Voltage Drop Table: 10 AWG Copper at 30 Amps

Distance (one-way)Voltage Drop (240V)Percentage DropAcceptable?
25 ft1.9V0.8%✅ Excellent
50 ft3.7V1.6%✅ Good
75 ft5.6V2.3%✅ Acceptable
100 ft7.4V3.1%⚠️ Marginal — consider upsizing
125 ft9.3V3.9%❌ Upsize to 8 AWG
150 ft11.2V4.7%❌ Upsize to 8 AWG
200 ft14.9V6.2%❌ Upsize to 6 AWG

Voltage Drop Table: 8 AWG Copper at 30 Amps (Upsized)

Distance (one-way)Voltage Drop (240V)Percentage DropAcceptable?
50 ft2.3V1.0%✅ Excellent
100 ft4.7V2.0%✅ Good
150 ft7.0V2.9%✅ Acceptable
200 ft9.3V3.9%⚠️ Marginal
250 ft11.7V4.9%❌ Upsize to 6 AWG
Warning

Voltage drop matters for HVAC equipment. A compressor running at 5% below rated voltage draws more current, runs hotter, and has a significantly shorter lifespan. Low voltage is one of the leading causes of premature compressor failure. Many manufacturers void the warranty if voltage is more than 10% below nameplate rating.

30-Amp Applications: Wiring Details

Central Air Conditioner (Most Common 30A Load)

Typical setup: 2–3.5 ton central AC condenser on a dedicated 30A/240V circuit.

Wiring requirements:

  • Wire: 10/2 NM-B from panel to disconnect box
  • Whip: 10 AWG THHN in flexible conduit from disconnect to condenser
  • Breaker: 30A double-pole
  • Disconnect: Non-fused 60A pull-out (rated above MCA)
  • Run length: Typically 20–60 feet

Step-by-step:

  1. Install 30A double-pole breaker in main panel
  2. Run 10/2 NM-B cable to disconnect location near condenser
  3. Mount disconnect box on exterior wall within sight of condenser (NEC 440.14)
  4. Connect NM-B to line side of disconnect
  5. Run flexible metal conduit ("whip") with 10 AWG THHN from disconnect to condenser
  6. Verify connections match unit's wiring diagram
Real-World Example

Real example — Carrier 24ACC636: 3-ton, 16 SEER2. Nameplate: MCA 19.0A, MOP 30A. Wire: 10 AWG copper minimum (handles 30A, well above 19A MCA). Breaker: 30A maximum per MOP. Run: 40 feet. Voltage drop: (2 × 40 × 19 × 1.24) / 1000 = 1.89V = 0.8%. Perfect installation.

Electric Water Heater

Typical setup: 40–80 gallon tank water heater, 4,500W–5,500W, on a dedicated 30A/240V circuit.

Wiring requirements:

  • Wire: 10/2 NM-B
  • Breaker: 30A double-pole
  • Junction box: At or near water heater
  • Flexible conduit: Short run from junction box to water heater
  • No disconnect required (breaker serves as disconnect if within sight)

Load verification:

  • 4,500W at 240V = 18.75A
  • Continuous load (water heater runs 3+ hours): 18.75A × 1.25 = 23.4A
  • 30A breaker handles 23.4A continuous → ✅ Code compliant
  • 10 AWG wire rated 30A → 18.75A operating load → ✅ Code compliant

Electric Dryer

Typical setup: Standard residential electric dryer, 5,000W max, on a dedicated 30A/240V circuit.

Wiring requirements:

  • Wire: 10/3 NM-B (NOT 10/2 — dryer needs neutral for 120V motor)
  • Breaker: 30A double-pole
  • Receptacle: NEMA 14-30R (4-prong)
  • No disconnect required (cord-and-plug serves as disconnect)

Load verification:

  • 5,000W at 240V = 20.8A (heating element on 240V)
  • 120V motor: ~3A on one leg
  • Total: ~24A max draw
  • 30A breaker → ✅ Adequate
  • 10/3 NM-B (10 AWG, 30A rating) → ✅ Code compliant

EV Charger (24A Continuous)

Typical setup: Level 2 EV charger set to 24A output, dedicated 30A/240V circuit.

Wiring requirements:

  • Wire: 10/2 NM-B
  • Breaker: 30A double-pole
  • Receptacle: NEMA 6-30R or 14-30R (depends on charger)
  • GFCI protection required (NEC 2023)

Load verification:

  • 24A continuous × 1.25 = 30A required breaker capacity
  • 30A breaker at 80% continuous duty = 24A max continuous → ✅ Exactly at limit
  • This is the maximum continuous load allowed on a 30A circuit
Good to Know

Why not size up the charger? A 24A charger on a 30A circuit adds roughly 25–30 miles of range per hour. Upgrading to a 48A charger on a 60A circuit adds 40–48 miles per hour — nearly double. If your panel has capacity, the 50-amp circuit option with a 48A charger provides significantly faster charging.

Common 30-Amp Wiring Mistakes

Mistake 1: Using 12 AWG Wire on a 30A Breaker

Why it's wrong: 12 AWG copper is rated for 20A max overcurrent protection per NEC 240.4(D). Putting it on a 30A breaker means the breaker won't trip until the wire is carrying 50% more current than it's designed for. The wire overheats inside the wall before the breaker ever trips.

The fix: Always use 10 AWG for 30A circuits. No exceptions.

Mistake 2: Using 10/3 Cable for an AC Unit

Why it's wasteful: Most AC condensers don't use a neutral wire. The white conductor in 10/3 cable sits unused — you've paid $10–$15 extra per run for a wire that serves no purpose.

The fix: Use 10/2 NM-B for AC condensers and water heaters. The black and white wires serve as the two hot legs (mark the white wire with black tape at both ends to indicate it's used as a hot, per NEC 200.7).

Mistake 3: Running 10 AWG Wire 150+ Feet Without Upsizing

Why it's problematic: At 150 feet and 30 amps, 10 AWG copper drops 11.2V on a 240V circuit — a 4.7% voltage drop. Your AC compressor runs below rated voltage, draws excess current, and overheats.

The fix: For runs over 100 feet at 30 amps, upsize to 8 AWG. For runs over 200 feet, use 6 AWG. The wire cost increase is minimal compared to a burned-out compressor.

Mistake 4: Using Indoor-Rated Cable Outdoors

Why it's wrong: NM-B (Romex) is not rated for wet locations. Running it outside exposed to weather or through underground conduit invites moisture damage, ground faults, and eventual failure.

The fix: Use UF-B cable for direct burial, THWN conductors in outdoor conduit, or run NM-B only through dry interior spaces and switch to THHN in conduit where the run goes outdoors.

Cost of 30-Amp Circuit Installation (2026)

ComponentDIY CostProfessional CostNotes
30A double-pole breaker$8–$20Included$12–$25 for GFCI breaker
10/2 NM-B cable (50 ft)$33–$50IncludedPrices vary by region
10/3 NM-B cable (50 ft)$43–$65IncludedFor dryer circuits
Pull-out disconnect (60A)$15–$30IncludedFor AC installations
NEMA 14-30R receptacle$10–$20IncludedFor dryer outlet
NEMA 6-30R receptacle$8–$15IncludedFor 240V equipment
Flexible conduit + fittings$15–$35IncludedAC whip connection
Permit and inspection$50–$150$50–$150Required in most jurisdictions
Total (DIY, AC circuit)$130–$300Materials + permit only
Total (Professional, AC circuit)$300–$800Labor + materials + permit
Total (Professional, dryer circuit)$250–$600Shorter typical run

Real-World Examples

Example 1: New Construction AC Circuit

Scenario: New 2,400 sq ft home, 3-ton AC condenser 35 feet from panel.

  • Wire: 10/2 NM-B, 35 ft
  • Breaker: 30A DP
  • Disconnect: 60A non-fused, mounted near condenser
  • Voltage drop: (2 × 35 × 20 × 1.24) / 1000 = 1.74V → 0.7% ✅
  • Cost: $180–$250 in materials

Example 2: Replacing Water Heater in Basement

Scenario: Replacing gas water heater with electric 50-gallon tank, panel is in same basement, 15 feet away.

  • Wire: 10/2 NM-B, 15 ft
  • Breaker: 30A DP (need 2 open spaces in panel)
  • Voltage drop: Negligible at 15 ft
  • Cost: $100–$150 in materials, $250–$500 professional install

Example 3: Adding a Dryer Circuit to Existing Home

Scenario: Laundry room 45 feet from panel, running through ceiling joists.

  • Wire: 10/3 NM-B, 45 ft (need neutral for dryer)
  • Breaker: 30A DP
  • Receptacle: NEMA 14-30R (4-prong)
  • Voltage drop: (2 × 45 × 24 × 1.24) / 1000 = 2.68V → 1.1% ✅
  • Cost: $150–$220 in materials, $350–$700 professional install

Example 4: Long Run to Detached Workshop Water Heater

Scenario: Electric water heater in a workshop 130 feet from main panel.

  • Wire at 10 AWG: VD = (2 × 130 × 18.75 × 1.24) / 1000 = 6.05V → 2.5% ✅
  • This is under 3% on the branch circuit. But if the feeder to the workshop already drops 2%, the total is 4.5% — close to the 5% limit.
  • Decision: Upsize to 8 AWG for safety margin. (2 × 130 × 18.75 × 0.778) / 1000 = 3.79V → 1.6%.
  • Cost difference: 8/2 vs. 10/2 for 130 ft ≈ $72 more. Worth it.

Key Takeaways

Key Takeaway
  • 10 AWG copper is the standard wire for 30-amp circuits — this is set by NEC 240.4(D) and is non-negotiable
  • 8 AWG aluminum is the equivalent for aluminum installations (rare for 30A branch circuits)
  • Use 10/2 cable for AC condensers, water heaters, and well pumps (240V-only loads)
  • Use 10/3 cable for electric dryers and any 240V load with 120V components
  • Upsize to 8 AWG for wire runs over 100 feet to keep voltage drop under 3%
  • Never put 12 AWG on a 30A breaker — it's a code violation and fire hazard
  • Typical installation cost: $300–$800 for a professional, $130–$300 DIY (materials only)
  • Always verify with the equipment nameplate — the MCA and MOP determine final wire and breaker sizing

Frequently Asked Questions

Related Articles