An electric water heater's circuit follows from its wattage, and the National Electrical Code (NEC) sets each step: the current, the 125 percent margin for a storage tank[1], the breaker and the wire. The tables below run that math for common tank ratings, give the current for tankless units and cover heat pump water heaters.

Wiring a 240-volt circuit is dangerous work. If you aren't sure of any step, have a licensed electrician do it or check it.

ENERGY STAR says a standard electric storage water heater typically uses a 30-amp breaker and 10-gauge wire[7], and the NEC math agrees for 4,500- and 5,500-watt tanks. A storage water heater is a continuous load, so its circuit is sized at 125 percent of its rating[1]: 23.4 amps for 4,500 watts and 28.6 amps for 5,500 watts (4,500 ÷ 240 × 1.25 = 23.4; 5,500 ÷ 240 × 1.25 = 28.6), both covered by a 30-amp double-pole breaker on 10 AWG copper.

Four steps for a 4,500-watt, 240-volt water heater: 18.75 amps, a 23.4-amp minimum at 125 percent, a 25-amp breaker and 10 AWG copper rated 30 amps, where 12 AWG copper falls short.
The NEC steps from tank wattage to breaker and wire.

Quick reference: wire and breaker by element wattage

A tank's current is its wattage divided by 240 volts. For a storage water heater of 120 gallons or less, the NEC then requires a breaker and conductors of at least 125 percent of that[1], and it caps the breaker at any rating marked on the appliance[1]. With no marked rating, the cap is 20 amps for an appliance of 13.3 amps or less and 150 percent of the rating above that, with the next standard size up allowed[2].

Element rating (240 V)Current125% minimumBreaker rangeCopper NM-B wire
3,000 W
12.5 A
15.6 A
20 A
12 AWG
3,500 W
14.6 A
18.2 A
20 to 25 A
12 AWG on 20 A
4,000 W
16.7 A
20.8 A
25 A
10 AWG
4,500 W
18.75 A
23.4 A
25 to 30 A
10 AWG
5,500 W
22.9 A
28.6 A
30 to 35 A
10 AWG on 30 A
6,000 W
25 A
31.25 A
35 to 40 A
8 AWG
How this was calculated: current = watts ÷ 240; minimum = current × 1.25 (NEC 422.13 and 422.10(A)(3)). The breaker range runs from the smallest standard rating in NEC Table 240.6(A) at or above the minimum to the largest NEC 422.11(E) allows when the nameplate marks no breaker rating. Wire is copper NM-B in the 60°C column of Table 310.16 (12 AWG 20 A, 10 AWG 30 A, 8 AWG 40 A), also held to NEC 240.4(D): 12 AWG on no more than 20 A, 10 AWG on no more than 30 A.

A breaker rating marked on the nameplate overrides the top of that range: the breaker may not exceed it[1]. The wire gauge chart lists every size in Table 310.16.

The NEC math for a 4,500-watt tank

  • Current: 4,500 ÷ 240 = 18.75 amps.
  • Minimum circuit: 18.75 × 1.25 = 23.4 amps, because the NEC treats a storage water heater of 120 gallons or less as a continuous load[1].
  • Breaker: the smallest standard rating at or above 23.4 amps is 25 amps[3]. If the nameplate marks no breaker rating, 30 amps is also allowed: 150 percent of the rating is 28.1 amps (18.75 × 1.5 = 28.1), and the NEC permits the next standard size up[2].
  • Wire: NM-B cable uses the 60°C column[5], where 10 AWG copper carries 30 amps[4], and the NEC lets 10 AWG copper sit on a breaker of up to 30 amps[6]. 12 AWG copper is capped at a 20-amp breaker[6], below the 23.4-amp minimum (18.75 × 1.25 = 23.4).

A 5,500-watt element runs the same way: 5,500 ÷ 240 = 22.9 amps, and 22.9 × 1.25 = 28.6 amps, so the smallest standard breaker is 30 amps on 10 AWG copper. A 35-amp breaker at the top of its range would need 8 AWG, since 10 AWG copper is capped at 30 amps[6].

Two elements, one circuit

A tank with two heating elements isn't automatically a double-size load. DOE's water heater test procedure covers both designs: units with two or more elements that "do not operate simultaneously" and units whose elements "all operate simultaneously"[8].

The NEC sizes the conductors to the appliance's marked rating, including the marked rating of an appliance with combined loads[1], so read the nameplate and size to it. Two 4,500-watt elements running together would draw 37.5 amps (9,000 ÷ 240 = 37.5), a 46.9-amp minimum at 125 percent (37.5 × 1.25 = 46.9), which takes a 50-amp breaker[3] and 6 AWG copper, rated 55 amps in the 60°C column[4].

Electric tankless water heaters

A tankless unit heats water as it flows, so its current runs far above a 4,500-watt tank's 18.75 amps (4,500 ÷ 240 = 18.75). At 240 volts:

RatingCurrent at 240 V
8 kW
33.3 A
11 kW
45.8 A
13 kW
54.2 A
18 kW
75 A
24 kW
100 A
27 kW
112.5 A
36 kW
150 A
How this was calculated: current = kilowatts × 1,000 ÷ 240. The ratings are examples; size to your unit's nameplate.

The continuous-load rule in NEC 422.13 is written for storage-type water heaters[1]. For any appliance, the conductors must carry at least the marked rating and the breaker may not exceed a marked breaker rating[1], so size every circuit a tankless unit needs to its nameplate.

A whole-house unit can take a large share of a home's service: a 27 kW unit draws 112.5 amps (27,000 ÷ 240 = 112.5), more than half of a 200-amp service's rating (112.5 ÷ 200 = 0.56). Our guide to how many amps a house uses runs the NEC load calculation, and what size tankless water heater covers sizing by flow.

Heat pump water heaters

ENERGY STAR's installation guide says a 240-volt heat pump water heater typically uses a 30-amp breaker[7] and 10-gauge wire[7], "just like a standard electric storage water heater." Some makers also offer plug-in 120-volt models[7] designed to replace gas water heaters, and those differ in whether they need a dedicated or a shared circuit[7].

A heat pump water heater uses less than half the energy[9] of a standard electric storage water heater, ENERGY STAR says. See our heat pump water heater guide for sizing and placement.

The rules that keep it safe

  • Size from the nameplate. Conductors can't be smaller than the appliance's marked rating, and the breaker can't exceed a marked breaker rating[1].
  • Match the wire to the breaker. 12 AWG copper goes on no more than 20 amps and 10 AWG on no more than 30[6]. A bigger breaker on a smaller wire breaks that limit.
  • Leave the circuit to the water heater. At 125 percent, a 4,500-watt element alone takes 23.4 of a 30-amp circuit's amps (18.75 × 1.25 = 23.4).
  • Ask about permits first. Your local building department sets whether the work needs a permit and inspection.

Energy and incentives (2026)

The federal 25C credit no longer applies: it isn't allowed for property placed in service after December 31, 2025[10]. Rebates from the Inflation Reduction Act run through state programs, available in select states[14].

  • High-Efficiency Electric Home Rebates (HEEHR): up to $1,750 for a heat pump water heater[11], covering up to the full cost below 80 percent of area median income[11] and half of it from 80 to 150 percent[11]. Under a DOE notice effective May 29, 2026[12], these rebates apply only to upgrades from existing electric equipment[12].
  • HOMES: whole-home rebates based on modeled energy savings of at least 20 percent[13].
  • State and utility rebates: check the DSIRE database for your area, and see our HVAC tax credit and rebate guide.

Frequently asked questions

What size wire does a water heater need? For a 4,500- or 5,500-watt tank, 10 AWG copper on a 30-amp breaker: the NEC's 125 percent minimum is 23.4 or 28.6 amps (4,500 ÷ 240 × 1.25 = 23.4; 5,500 ÷ 240 × 1.25 = 28.6), and 10 AWG copper NM-B carries 30 amps[4]. A 3,000- or 3,500-watt tank fits 12 AWG on a 20-amp breaker (3,500 ÷ 240 × 1.25 = 18.2). Size to the rating on your unit's nameplate[1].

What size breaker for a 4,500-watt water heater? At least 25 amps, and up to 30 amps if the nameplate marks no lower breaker rating. The element draws 18.75 amps, the NEC's 125 percent minimum is 23.4 (18.75 × 1.25 = 23.4), and the cap is 150 percent with the next standard size up allowed, 28.1 rounding up to 30 amps (18.75 × 1.5 = 28.1)[2].

Do tankless water heaters need special wiring? They need far more current: an 18 kW unit draws 75 amps at 240 volts (18,000 ÷ 240 = 75), against 18.75 for a 4,500-watt tank (4,500 ÷ 240 = 18.75). Size the wire and breakers to the nameplate, which the NEC makes the limit for both[1], and check that the home's service can carry the load.

Can I use 10/3 wire instead of 10/2 for a water heater? Yes; the extra conductor doesn't change the wire size the circuit needs, 10 AWG copper for a 30-amp tank circuit[6]. Check the unit's wiring diagram: if it shows no neutral connection, the extra conductor goes unused.

Do I need a permit to install a water heater circuit? Permit rules are local, so ask your building department before you start. If you aren't sure of any step, have a licensed electrician do the work or check it.

Sources & References

  1. NFPA: 2026-edition National Electrical Code First Draft report, Code-Making Panel 17 (422.13: fixed storage-type water heaters of 450 L (120 gal) or less are a continuous load, replacing the 2023 text that required a breaker and conductors of not less than 125 percent of the water heater's rating; 422.10(A)(1): conductors not less than the marked rating, including an appliance with combined loads; 422.10(A)(3): 125 percent branch-circuit rating for a continuous load; 422.11(A): breaker not over a rating marked on the appliance)
  2. NFPA: 2026-edition National Electrical Code Second Draft report, Code-Making Panel 17 (422.11(E): with no marked rating, a breaker not over 20 amperes for an appliance of 13.3 amperes or less and not over 150 percent of the rated current above that, the next higher standard rating permitted)
  3. NFPA: 2026-edition National Electrical Code First Draft report, Code-Making Panel 10 (Table 240.6(A) standard ampere ratings: 10, 15, 20, 25, 30, 35, 40, 45, 50, 60 A and up)
  4. NFPA: 2026-edition National Electrical Code First Draft report, Code-Making Panel 6 (Table 310.16 ampacities: copper 12 AWG 20/25/30 A, 10 AWG 30/35/40 A, 8 AWG 40/50/55 A, 6 AWG 55/65/75 A at 60/75/90°C)
  5. Cerrowire: Ampacity Charts (NEC Table 310.16; NM-B cable is in the 60°C column)
  6. Encore Wire: Wire Ampacity Size Table (NEC 240.4(D): overcurrent protection no more than 15 amperes for 14 AWG, 20 amperes for 12 AWG and 30 amperes for 10 AWG copper)
  7. ENERGY STAR: Heat Pump Water Heater Installation Guide (a 240V heat pump water heater typically uses a 30-amp breaker and 10-gauge wire, just like a standard electric storage water heater; plug-in 120V models for replacing gas water heaters; dedicated vs. shared circuit)
  8. 10 CFR Part 430, Subpart B, Appendix E, Uniform Test Method for Measuring the Energy Consumption of Water Heaters (electric water heaters with elements that do not operate simultaneously and with elements that all operate simultaneously), via LII
  9. ENERGY STAR: Heat pump water heater fact sheet (less than half the energy of a standard electric storage water heater)
  10. IRS: FAQs for modification of sections 25C, 25D and others under Public Law 119-21 (FS-2025-05): 25C not allowed for property placed in service after December 31, 2025
  11. 42 U.S.C. 18795a (High-Efficiency Electric Home Rebate Program: 100% of cost below 80% of area median income, 50% from 80% to 150%; item caps including $1,750 heat pump water heater)
  12. U.S. DOE: Program Notice 26-2, High-Efficiency Electric Home Rebate (HEEHR) Program (effective May 29, 2026): rebates only from existing electric equipment to more efficient electric equipment
  13. 42 U.S.C. 18795 (Home Owner Managing Energy Savings (HOMES) rebates: modeled savings of at least 20%; larger amounts below 80% of area median income; available through Sept 30, 2031)
  14. U.S. DOE: Home Energy Rebates (available in select states; the State or Territory Energy Office has status and eligibility)
  15. DSIRE: Database of State Incentives for Renewables & Efficiency

Related Articles