Whether you're planning a project, checking an electrician's quote, or want to know how your home's wiring works, below are the essentials: wire sizes, breakers, circuit types and the code rules that keep them safe. The figures come from the electrical chapters of the 2021 International Residential Code[2], which cite the matching National Electrical Code (NEC) sections in brackets.
Electrical wiring is safety-critical work. The Electrical Safety Foundation International (ESFI) counts about 51,000 home electrical fires a year[1], with about 500 deaths[1], more than 1,400 injuries[1] and $1.3 billion in property damage[1]. Most of the work itself needs a permit[4].
Copper 14 AWG wire takes at most a 15-amp breaker[2], 12 AWG a 20-amp and 10 AWG a 30-amp[2], and NM-B (Romex) cable is held to its 60°C ampacity[2]. Size the wire to carry the current and the breaker to protect the wire, and give continuous loads 125% headroom[2]. HVAC equipment follows its nameplate: the wire must meet the marked minimum circuit ampacity and the breaker must match the marked rating[2].
How home electrical wiring works
Your home's power flows through a simple chain:
- Power enters through the utility service and meter.
- The main breaker panel distributes it across individual branch circuits.
- Each circuit has a breaker sized to protect its wire, feeding outlets, lights or a single appliance.
Every link has to be sized correctly. A wire carrying more current than it's rated for overheats, and a breaker rated above the wire won't trip before the wire gets hot. The code rules below exist to prevent exactly those two mismatches.
Wire gauges and ampacity
The American Wire Gauge (AWG) system runs backwards from what you'd expect: smaller numbers mean thicker wire that carries more current. Ampacity also depends on the insulation's temperature rating, which is why the code table has 60°C, 75°C and 90°C columns[2].
| Copper wire | 60°C ampacity (NM-B cable) | 75°C ampacity | 90°C ampacity (THHN) | Largest breaker for small wire |
|---|---|---|---|---|
14 AWG | 15 A | 20 A | 25 A | 15 A |
12 AWG | 20 A | 25 A | 30 A | 20 A |
10 AWG | 30 A | 35 A | 40 A | 30 A |
8 AWG | 40 A | 50 A | 55 A | Not capped |
6 AWG | 55 A | 65 A | 75 A | Not capped |
4 AWG | 70 A | 85 A | 95 A | Not capped |
2 AWG | 95 A | 115 A | 130 A | Not capped |
1/0 AWG | 125 A | 150 A | 170 A | Not capped |
2/0 AWG | 145 A | 175 A | 195 A | Not capped |
4/0 AWG | 195 A | 230 A | 260 A | Not capped |
Three rules decide which column you can actually use:
- NM-B cable uses the 60°C column. Its conductors are rated 90°C, but the code says the allowable ampacity of NM cable "shall not exceed that of 60°C (140°F) rated conductors"[2].
- Terminations set the column too. For circuits of 100 amps or less[2], or terminals marked for 14 AWG through 1 AWG[2], equipment terminals are sized on the 60°C column[2] unless the equipment is marked otherwise; above 100 amps, the 75°C column applies[2].
- Small wire is capped. Whatever its insulation, copper 14 AWG gets a breaker of at most 15 amps, 12 AWG 20 amps and 10 AWG 30 amps[2] (NEC 240.4(D)).
Aluminum carries less current than copper of the same size, so it's sized up: 12 AWG aluminum is limited to a 15-amp breaker[2] and 10 AWG aluminum to 25 amps[2]. For the full breakdown by wire type, see our wire gauge chart, and for 240-volt circuits our wire for 220V guide.
Breaker sizing: protect the wire, not the appliance
The breaker's job is to trip before the wire overheats, so on general circuits its rating can't exceed the wire's allowable ampacity[2]; air-conditioning and heat pump circuits follow their nameplate instead (below). Putting a bigger breaker on a circuit to stop "nuisance tripping" removes the wire's protection and turns an annoyance into a fire risk.
The standard pairings for copper NM-B cable follow from the table above: a 15-amp breaker on 14 AWG[2], 20-amp on 12 AWG[2], 30-amp on 10 AWG and 40-amp on 8 AWG[2], while 6 AWG NM-B carries 55 amps[2].
The continuous-load rule: a continuous load runs for 3 hours or more[7], and the code requires an ampacity of at least "the noncontinuous load plus 125 percent of the continuous load"[2]. So a 40-amp continuous load needs a 50-amp circuit (40 × 1.25 = 50), and the DOE notes that an EV charger is a continuous load under the NEC[6].
Service and feeder sizes
The wire bringing power into the house has its own table. For a single-phase dwelling service, the code allows these conductor sizes when no correction factors apply:
| Service or feeder rating | Copper | Aluminum |
|---|---|---|
100 A | 4 AWG | 2 AWG |
125 A | 2 AWG | 1/0 AWG |
150 A | 1 AWG | 2/0 AWG |
200 A | 2/0 AWG | 4/0 AWG |
400 A | 400 kcmil | 600 kcmil |
For a service upgrade, see our panel upgrade cost guide and how many amps a house uses.
Common residential circuit types
The code sets a few circuits every home needs:
- Kitchen and dining receptacles: "A minimum of two 20-ampere-rated branch circuits"[2] for the countertop and dining-area outlets.
- Laundry: at least one 20-ampere branch circuit[2] serving only the laundry-area outlets.
- General lighting and outlets: 15- or 20-amp circuits[2] on 14 or 12 AWG copper[2], within the small-wire caps above.
- 240-volt circuits: dryer, range, water heater, air conditioner or heat pump and EV charger, each sized to its appliance.
Required protection: GFCI and AFCI
Two kinds of protective device are required in specific places:
- GFCI (ground-fault circuit interrupter) protects people from shock. The residential code requires it for 125- through 250-volt receptacles[3] in bathrooms, garages, outdoors, crawl spaces, basements, kitchen countertops, near sinks and in laundry areas[3] (NEC 210.8).
- AFCI (arc-fault circuit interrupter) guards against fires from arcing. It's required on 120-volt, 15- and 20-amp circuits[3] feeding kitchens, family rooms, dining rooms, living rooms, bedrooms, sunrooms, closets, hallways, laundry areas and similar rooms[3] (NEC 210.12).
These rules apply to new work, and extending or modifying an existing branch circuit can bring AFCI protection with it[3]. An electrician can also add both to an older home.
Wiring for HVAC and major appliances
HVAC equipment doesn't follow the general table alone: for air-conditioning and heat pump equipment, the code sets conductor ampacity at "not less than the minimum circuit ampacity marked on the equipment" and the breaker at "the size and type marked on the appliance"[2] (NEC 440). Read the nameplate's MCA and maximum breaker before choosing wire.
- Central AC or heat pump: a circuit at the nameplate voltage, sized to its MCA and maximum overcurrent rating[2]. See our wire for 220V guide.
- Electric or heat pump water heater: ENERGY STAR says a 240-volt heat pump water heater typically uses a 30-amp breaker[5] and 10-gauge wire[5], "just like a standard electric storage water heater." See our water heater wire size guide.
- EV charger: sized by the continuous-load rule[6], so a charger drawing 40 A needs a 50 A circuit (40 × 1.25) and one drawing 48 A needs a 60 A circuit (48 × 1.25).
Size the circuit to the equipment's marked ratings, not to a general rule of thumb.
Permits, and when to call an electrician
Under the residential code, an owner or owner's agent who intends to install, alter, repair or replace an electrical system "shall first make application to the building official and obtain the required permit"[4]. The exemptions are narrow: temporary plug-in decorative lighting, reinstalling plug receptacles (not adding outlets), replacing a breaker of the required size in the same spot, wiring under 25 volts[4] and 50 watts[4], and minor repairs like replacing lamps.
Whether a homeowner may do the work under that permit is up to your state and local building department, so ask before you start. The code also says an exemption never authorizes work done in violation of the code[4].
Before you touch a wire, turn the breaker off and confirm the circuit is dead with a voltage tester. A permit also brings inspections of the work[4].
Frequently asked questions
What wire gauge do I need for a circuit? It depends on the circuit's amperage and the wire type. For copper NM-B cable: 14 AWG for 15 amps[2], 12 AWG for 20 amps and 10 AWG for 30 amps[2].
Heavier loads need heavier wire from the 60°C column, and HVAC equipment follows its nameplate MCA[2].
How do I size a breaker? On general circuits the breaker protects the wire, so it can't exceed the wire's allowable ampacity[2]; HVAC equipment follows its nameplate. For continuous loads, the circuit needs 125% of the continuous load[2].
Never install a larger breaker to stop nuisance tripping; that removes the wire's protection.
Can I do my own electrical wiring? The residential code requires a permit for electrical installation and alteration work, with only narrow exemptions such as reinstalling receptacles or swapping a breaker of the same rating[4]. Whether a homeowner may do the work under that permit depends on your state and city.
What's the difference between GFCI and AFCI? A GFCI protects people from shock and is required in bathrooms, at kitchen countertops, in garages, outdoors, in basements and in laundry areas[3]. An AFCI guards against arcing fires and is required on 15- and 20-amp circuits[3] in most living spaces and bedrooms.
Why does my wire need to match my breaker? Because the breaker's job is to trip before the wire overheats. If the breaker is rated higher than the wire can carry, the wire can reach dangerous temperatures without the breaker tripping.
What size wire does a 200-amp service need? The residential code's dwelling-service table gives 2/0 AWG copper or 4/0 AWG aluminum for 200 amps[8], when no correction factors apply.
Sources & References
- ESFI: Home Electrical Fires (about 51,000 fires, about 500 deaths, more than 1,400 injuries and $1.3 billion in property damage a year)
- 2021 International Residential Code, Chapter 37: Branch Circuit and Feeder Requirements (Table E3705.1 ampacities; Table E3705.5.3 small-conductor overcurrent limits, NEC 240.4(D); E3705.4.1, E3705.4.2 and E3705.4.4 termination and NM cable rules; E3701.2.1 continuous load; E3703.2 and E3703.3 kitchen and laundry circuits; E3702.11 air-conditioning and heat pump equipment)
- 2021 International Residential Code, Chapter 39: Power and Lighting Distribution (E3902 GFCI locations, NEC 210.8; E3902.17 and E3902.18 AFCI protection, NEC 210.12)
- 2021 International Residential Code, Chapter 1: Scope and Administration (R105.1 permits required; R105.2 electrical work exempt from permit; R109 inspections)
- ENERGY STAR: Heat Pump Water Heater Installation Guide (PDF) (a 240 V unit typically uses a 30-amp breaker and 10-gauge wire)
- U.S. DOE Alternative Fuels Data Center: Plug-In Electric Vehicle Handbook for Electrical Contractors (PDF) (EVSE is a continuous load under the NEC)
- IAEI Magazine, Focus on the Code, November/December 2012 (NEC Article 100: a continuous load is one where the maximum current is expected to continue for 3 hours or more)
- 2021 International Residential Code, Chapter 36: Services (Table E3603.1.1 single-phase dwelling services and feeders, NEC Table 310.12; 83 percent rule)
Related Articles
Wire Gauge Chart: AWG Wire Sizes and Ampacity
Reference • 15 min read
Wire Size for 220V/240V Circuits (30, 40 & 50 Amp): NEC Reference & the 4 Factors That Change It
Guide • 12 min read
How Many Amps Does a House Use? (Service Size and Load)
Explainer • 10 min read
Water Heater Wire & Breaker Size Chart: AWG Gauge & Amps
Reference • 12 min read
Electrical Panel Upgrade Cost: 100 to 200 Amp
Cost guide • 11 min read