Most U.S. homes use 14 AWG wire on 15-amp circuits for lighting and 12 AWG wire on 20-amp circuits for outlets — but HVAC equipment, water heaters, and EV chargers demand dedicated circuits with heavier wire ranging from 10 AWG to 2/0 AWG. Getting the wire size wrong isn't just a code violation — it's a fire hazard that kills an estimated 46,700 home fires per year according to the Electrical Safety Foundation International (ESFI).
This guide covers everything you need to know about residential electrical wiring in 2026: wire gauges, breaker sizing, circuit types, NEC code requirements, and practical wiring for every major home system including HVAC, water heating, and electric vehicle charging.
How Home Electrical Wiring Works
Your home's electrical system is a network of circuits that carry power from the utility company to every switch, outlet, and appliance. Understanding the basics prevents costly mistakes.
The path of electricity in your home:
- Power enters through the meter at 240V (split-phase)
- The main breaker panel distributes power across individual circuits
- Each circuit has a breaker sized to match its wire gauge
- Wires carry current to outlets, switches, and hardwired appliances
Every component in this chain must be sized correctly. An undersized wire carrying too much current overheats. An oversized breaker fails to trip before the wire reaches dangerous temperatures. The NEC (National Electrical Code) exists specifically to prevent these mismatches.
Understanding Wire Gauge (AWG)
The American Wire Gauge (AWG) system measures wire diameter — and it works backwards from what you'd expect. Smaller AWG numbers mean thicker wire that carries more current.
| AWG Gauge | Diameter (inches) | Copper Ampacity (60°C) | Copper Ampacity (75°C) | Common Use |
|---|---|---|---|---|
| 14 AWG | 0.0641 | 15A | 20A | Lighting circuits |
| 12 AWG | 0.0808 | 20A | 25A | General outlets |
| 10 AWG | 0.1019 | 30A | 35A | Dryers, AC units |
| 8 AWG | 0.1285 | 40A | 50A | Ranges, sub-panels |
| 6 AWG | 0.1620 | 55A | 65A | Large AC, sub-panels |
| 4 AWG | 0.2043 | 70A | 85A | Sub-panels, feeders |
| 3 AWG | 0.2294 | 85A | 100A | Service entrance |
| 2 AWG | 0.2576 | 95A | 115A | Service entrance |
| 1/0 AWG | 0.3249 | 125A | 150A | 150A service |
| 2/0 AWG | 0.3648 | 145A | 175A | 200A service |
| 4/0 AWG | 0.4600 | 195A | 230A | 200A service (long runs) |
NEC Table 310.16 is your bible for wire sizing. The ampacity values above apply to copper conductors in standard NM-B (Romex) cable at 30°C ambient temperature. Aluminum wire requires upsizing by approximately 2 AWG sizes for equivalent ampacity.
Key AWG Rules to Remember
Each 3-gauge decrease roughly doubles the wire's cross-sectional area. Going from 14 AWG to 8 AWG gives you about 4× the copper and 2.7× the current capacity. This matters when you're deciding whether to upsize wire for future-proofing — the cost of copper increases proportionally.
The insulation temperature rating also matters. Most residential NM-B cable is rated at 60°C, but THHN wire used in conduit is rated at 75°C or 90°C. Higher temperature ratings allow more current through the same gauge — but NEC 240.4(D) caps 14 AWG at 15A, 12 AWG at 20A, and 10 AWG at 30A for branch circuits regardless of insulation rating.
Wire Types for Residential Use
Not all wire is the same. The cable type you need depends on where it's installed and what it's powering.
| Cable Type | Description | Typical Use | Where Installed |
|---|---|---|---|
| NM-B (Romex) | Non-metallic sheathed, 2-3 conductors + ground | General indoor wiring | Dry interior walls, attics, crawlspaces |
| UF-B | Underground feeder, moisture resistant | Outdoor circuits, underground | Direct burial or outdoor conduit |
| THHN/THWN | Single conductors, thermoplastic insulation | Individual runs in conduit | EMT, PVC, or rigid conduit |
| MC Cable | Metal-clad with aluminum armor | Commercial, some residential | Exposed locations, garages |
| SE Cable | Service entrance cable | Service feeders, sub-panels | Between meter and panel |
| USE-2 | Underground service entrance | Underground service laterals | Direct burial |
Understanding Cable Naming
When you see "10/2 NM-B," here's what it means:
- 10 = Wire gauge (10 AWG)
- 2 = Number of insulated conductors (black hot + white neutral)
- NM-B = Cable type (non-metallic sheathed, B-rated insulation)
- There's always an additional bare copper ground wire not counted in the number
So 10/2 NM-B has three total wires: one black (hot), one white (neutral), and one bare copper (ground). A 10/3 cable adds a second hot wire (red) for 240V circuits that also need a neutral — like an electric dryer or range.
For 240V HVAC equipment like central air conditioners: You typically need 10/2 cable, not 10/3. Most AC condensers don't need a neutral conductor — just two hots and a ground. Using 10/3 works but wastes money on an unused neutral wire. See our 10/2 or 10/3 Wire for AC guide for details.
Breaker Sizing: The Complete Guide
The breaker is your circuit's safety valve. It must be sized to protect the wire — not the appliance. This is the single most misunderstood concept in residential wiring.
The Fundamental Rule
NEC 240.4: The overcurrent protection device (breaker) shall not exceed the ampacity of the conductor it protects.
In plain English: the breaker amp rating must be equal to or less than what the wire can safely carry.
| Wire Gauge | Maximum Breaker Size | Maximum Continuous Load (80%) |
|---|---|---|
| 14 AWG | 15A | 12A |
| 12 AWG | 20A | 16A |
| 10 AWG | 30A | 24A |
| 8 AWG | 40A | 32A |
| 6 AWG | 50A–60A | 40A–48A |
| 4 AWG | 70A | 56A |
| 3 AWG | 100A | 80A |
The 80% Rule for Continuous Loads
NEC 210.20 requires that conductors and breakers for continuous loads (running 3+ hours) be rated at 125% of the load — which effectively means you can only load a standard breaker to 80% of its rating continuously.
A 30-amp breaker on a continuous-use AC unit should only carry 24 amps continuously. If your AC draws 26 amps, you need to upsize to a 40-amp breaker with 8 AWG wire, even though 10 AWG wire is technically rated for 30 amps.
Dedicated Circuits Required by Code
The NEC requires dedicated circuits for specific appliances. A dedicated circuit serves only one appliance with its own breaker.
| Appliance | Typical Circuit | Wire Gauge | Breaker |
|---|---|---|---|
| Central AC (2–3 ton) | 240V, 1-phase | 10 AWG | 30A |
| Central AC (4–5 ton) | 240V, 1-phase | 8 AWG | 40A–50A |
| Heat pump | 240V, 1-phase | 10–8 AWG | 30A–50A |
| Electric furnace | 240V, 1-phase | 8–4 AWG | 40A–70A |
| Electric water heater (4500W) | 240V | 10 AWG | 30A |
| Electric water heater (5500W) | 240V | 10 AWG | 30A |
| Electric dryer | 240V | 10 AWG | 30A |
| Electric range/oven | 240V | 6 AWG | 50A |
| EV charger (Level 2, 40A) | 240V | 8 AWG | 50A |
| EV charger (Level 2, 48A) | 240V | 6 AWG | 60A |
| Dishwasher | 120V | 12 AWG | 20A |
| Garbage disposal | 120V | 12 AWG | 20A |
| Microwave | 120V | 12 AWG | 20A |
| Bathroom outlets | 120V GFCI | 12 AWG | 20A |
| Kitchen counter outlets | 120V GFCI | 12 AWG | 20A |
| Garage outlets | 120V GFCI | 12 AWG | 20A |
| Laundry outlet | 120V | 12 AWG | 20A |
Voltage Drop: The Hidden Wire Sizing Factor
Wire gauge tables tell you the maximum current a wire can safely carry without overheating. But there's another factor that often forces you to upsize: voltage drop.
Every wire has resistance. The longer the run, the more voltage you lose. The NEC recommends (but doesn't require) no more than 3% voltage drop on branch circuits and 5% total from service entrance to the farthest outlet.
Voltage Drop Formula
VD = (2 × L × I × R) / 1000
Where:
- VD = voltage drop (volts)
- L = one-way wire length (feet)
- I = current (amps)
- R = wire resistance per 1,000 feet (ohms)
| AWG | Resistance (Ω/1000 ft, copper) | Max Length at 3% Drop, 120V, 15A | Max Length at 3% Drop, 240V, 30A |
|---|---|---|---|
| 14 | 3.14 | 38 ft | — |
| 12 | 1.98 | 61 ft | — |
| 10 | 1.24 | 97 ft | 97 ft |
| 8 | 0.778 | 154 ft | 154 ft |
| 6 | 0.491 | 245 ft | 245 ft |
| 4 | 0.308 | 390 ft | 390 ft |
Long runs kill efficiency. If your AC condenser is 100 feet from the panel, 10 AWG copper wire at 30 amps drops 7.4V — that's a 3.1% drop on a 240V circuit. Marginal, but add in the service entrance drop and you may exceed 5% total. In that case, upsize to 8 AWG.
Real-World Example: AC Condenser 150 Feet From Panel
Scenario: You're installing a 3-ton AC condenser that draws 18 amps at 240V. The condenser pad is 150 feet from the panel.
Step 1: Minimum wire per breaker — 10 AWG for a 30A breaker (NEC 240.4(D)).
Step 2: Calculate voltage drop with 10 AWG at 150 ft and 18A: VD = (2 × 150 × 18 × 1.24) / 1000 = 6.7V → 2.8% on 240V
Step 3: That's under 3%, but add 2% for the service entrance feeder and you're at 4.8% — close to the 5% total limit.
Decision: 10 AWG technically works, but 8 AWG provides margin. A professional would likely recommend 8 AWG for this run.
HVAC-Specific Wiring Requirements
HVAC equipment has unique wiring requirements because of motor starting currents and continuous operation.
Reading the Equipment Nameplate
Every HVAC unit has a data plate with critical electrical specs:
- MCA (Minimum Circuit Ampacity): Determines minimum wire size. Wire must be rated for at least MCA.
- MOP (Maximum Overcurrent Protection): Determines maximum breaker size. Breaker cannot exceed MOP.
- RLA (Rated Load Amps): Normal running current of the compressor.
- LRA (Locked Rotor Amps): Startup surge current (3–6× RLA).
- FLA (Full Load Amps): Maximum continuous current at rated conditions.
Example Nameplate — 3-Ton Condenser:
- Voltage: 208/230V, 1-phase, 60Hz
- MCA: 19.6A
- MOP: 30A
- RLA: 14.2A
- LRA: 78A
Wiring decision: Wire must handle ≥19.6A → 10 AWG (rated 30A). Breaker must not exceed 30A → 30A double-pole breaker. Done.
Common HVAC Circuit Sizing
| Equipment | Typical MCA | Typical MOP | Wire Gauge | Breaker | Cable Type |
|---|---|---|---|---|---|
| 1.5-ton AC | 11–14A | 20A | 12 AWG | 20A | 10/2 NM-B or THHN |
| 2-ton AC | 13–17A | 25A | 12–10 AWG | 25A | 10/2 NM-B or THHN |
| 2.5-ton AC | 15–19A | 25–30A | 10 AWG | 25–30A | 10/2 NM-B or THHN |
| 3-ton AC | 17–22A | 30–35A | 10 AWG | 30A | 10/2 NM-B or THHN |
| 4-ton AC | 22–28A | 35–45A | 8 AWG | 40A | 8/2 NM-B or THHN |
| 5-ton AC | 28–35A | 45–60A | 6–8 AWG | 50A | 6/2 THHN in conduit |
| Mini-split (9k BTU) | 6–8A | 15A | 14 AWG | 15A | 14/2 NM-B |
| Mini-split (18k BTU) | 11–15A | 20A | 12 AWG | 20A | 12/2 NM-B |
| Mini-split (36k BTU) | 19–24A | 30A | 10 AWG | 30A | 10/2 NM-B |
| Electric furnace (10kW) | 45A | 60A | 6 AWG | 60A | 6/2 THHN |
| Electric furnace (15kW) | 65A | 80A | 4 AWG | 80A | 4/2 THHN |
| Electric furnace (20kW) | 87A | 100A | 3 AWG | 100A | 3 AWG THHN |
Disconnect Requirements
NEC 440.14 requires a disconnect switch within sight of HVAC equipment and within 50 feet. This is typically a pull-out disconnect mounted on the wall near the condenser.
The disconnect must be rated for at least the equipment's MCA and must be able to interrupt the LRA. For most residential units under 40A, a standard 60A non-fused disconnect works. For larger units, a fused disconnect matching the MOP provides additional protection.
120V vs. 240V Circuits
Understanding the difference between 120V and 240V circuits is essential for proper wiring.
120V circuits use one hot wire (black), one neutral (white), and one ground (bare/green). They connect to a single-pole breaker. These power most household devices: lights, standard outlets, small appliances.
240V circuits use two hot wires (black and red), and one ground (bare/green). They connect to a double-pole breaker. These power heavy equipment: central AC, electric water heaters, dryers, ovens. Many 240V loads don't need a neutral because they don't have any 120V components.
240V circuits with neutral use two hots, one neutral, and one ground (4 wires total). Electric dryers and ranges need this configuration because they have both 240V heating elements and 120V controls/lights.
| Circuit Type | Hots | Neutral | Ground | Cable | Breaker |
|---|---|---|---|---|---|
| 120V, 15A | 1 (black) | Yes (white) | Yes (bare) | 14/2 NM-B | 15A SP |
| 120V, 20A | 1 (black) | Yes (white) | Yes (bare) | 12/2 NM-B | 20A SP |
| 240V, 30A (AC) | 2 (black, red) | No | Yes (bare) | 10/2 NM-B | 30A DP |
| 240V, 30A (dryer) | 2 (black, red) | Yes (white) | Yes (bare) | 10/3 NM-B | 30A DP |
| 240V, 50A (range) | 2 (black, red) | Yes (white) | Yes (bare) | 6/3 NM-B | 50A DP |
Grounding and Safety
Proper grounding saves lives. The ground wire provides a low-resistance path for fault current to flow back to the panel and trip the breaker.
GFCI Protection (NEC 2023/2026)
Ground-Fault Circuit Interrupters detect current leaks as small as 4–6 milliamps and shut off power within 1/25 of a second. The NEC has expanded GFCI requirements significantly in recent code cycles.
GFCI required locations (NEC 210.8):
- Bathrooms (all outlets)
- Kitchens (within 6 feet of sink)
- Garages and accessory buildings
- Outdoors
- Crawlspaces and unfinished basements
- Laundry areas
- Within 6 feet of any sink
- Boathouses
- Indoor damp/wet locations
AFCI Protection (NEC 2023/2026)
Arc-Fault Circuit Interrupters detect dangerous electrical arcs from damaged wires or loose connections. NEC 210.12 now requires AFCI protection on virtually all 120V, 15A and 20A branch circuits in dwelling units, including:
- Bedrooms, living rooms, dining rooms
- Kitchens, laundry rooms, hallways
- Closets, sunrooms, recreation rooms
Dual-function breakers combine AFCI and GFCI protection in one unit. At $35–$55 per breaker, they simplify compliance in areas requiring both protections — like kitchens and laundry rooms.
NEC 2023 and 2026 Code Updates
The NEC updates on a 3-year cycle. As of 2026, most jurisdictions are adopting or have adopted NEC 2023, with NEC 2026 in the development pipeline.
Key NEC 2023 Changes Affecting Homeowners
Expanded GFCI requirements (210.8): GFCI protection now required for all 240V outlets rated 150V-to-ground or less and 50 amps or less. This affects 240V outlets for dryers, ranges, and EV chargers.
Surge protection (230.67): All dwelling unit services must have a Type 1 or Type 2 surge protective device (SPD). This protects sensitive HVAC electronics, smart thermostats, and other equipment.
Rapid shutdown for solar (690.12): Updated requirements for rapid shutdown of rooftop solar systems, affecting homes with solar-connected HVAC systems.
EV-ready requirements (NEC 625): Many jurisdictions now require new construction to include EV-ready wiring or at minimum an available circuit in the garage for future EV charger installation.
Electrical Panel: The Heart of Your System
Your electrical panel distributes power to every circuit in your home. Its size determines how much total power you can use simultaneously.
| Panel Size | Total Capacity | Typical Home Size | Suitable For |
|---|---|---|---|
| 100A | 24,000W at 240V | <1,500 sq ft | Gas heat, gas water heater, no EV |
| 125A | 30,000W at 240V | 1,500–2,000 sq ft | Gas heat, some electric appliances |
| 150A | 36,000W at 240V | 2,000–2,500 sq ft | Mix of gas/electric |
| 200A | 48,000W at 240V | 2,500+ sq ft | All-electric, heat pump, EV charger |
| 320A | 76,800W at 240V | Large homes | All-electric + high loads |
| 400A | 96,000W at 240V | Very large homes | Multiple HVAC zones, pool, shop |
Most homes built since 2000 have 200A service. If you're adding a heat pump, electric vehicle charger, or electric water heater to an older home with 100A service, you'll likely need a panel upgrade.
Load Calculation (NEC Article 220)
Before adding circuits, verify your panel has capacity. The NEC Standard Method for residential load calculation:
- General lighting and receptacles: 3 VA per square foot of living space
- Small appliance circuits: 1,500 VA per circuit (minimum 2 required)
- Laundry circuit: 1,500 VA
- Apply demand factors: First 10,000 VA at 100%, remainder at 40%
- Add fixed appliances at nameplate ratings (with demand factors)
- Add largest motor at 125% of nameplate
- Add HVAC (use largest of heating or cooling, not both)
Example: 2,000 sq ft home load calculation
- General lighting: 2,000 × 3 = 6,000 VA
- Small appliance circuits (2): 3,000 VA
- Laundry: 1,500 VA
- Subtotal: 10,500 VA → First 10,000 at 100% + 500 at 40% = 10,200 VA
- Electric range: 8,000 VA (per Table 220.55) = 8,000 VA
- Dishwasher: 1,500 VA
- Water heater (4,500W): 4,500 VA
- AC (3-ton, 30A × 240V): 7,200 VA
- Total: 31,400 VA ÷ 240V = 130.8A → 150A or 200A service
Wiring for Specific HVAC Equipment
Central Air Conditioner
Most residential central AC units (2–5 tons) require a dedicated 240V circuit. The exact requirements come from the unit's nameplate.
Typical installation:
- 10/2 NM-B from panel to disconnect
- Whip (flexible conduit with THHN) from disconnect to unit
- 30A double-pole breaker
- Non-fused 60A disconnect within sight of unit
Heat Pump
Heat pumps wire identically to AC units — with one addition. The supplemental electric heat strips in the air handler may need their own circuit. A 3-ton heat pump with 10kW strip heat might require two circuits: one 30A for the condenser and one 60A for the air handler with strips.
Mini-Split Systems
Mini-splits are simpler. Most single-zone units under 18,000 BTU need only a dedicated 120V or 240V 20A circuit. Multi-zone units typically need a 240V, 30A circuit. Always check the installation manual — some brands require a dedicated circuit even for small units.
Electric Furnace
Electric furnaces are among the most power-hungry HVAC appliances. A 20kW electric furnace draws approximately 83 amps at 240V, requiring 3 AWG copper wire and a 100A breaker. Some large electric furnaces need a dedicated sub-panel.
Common Wiring Mistakes and How to Avoid Them
Mistake 1: Oversized Breaker
The problem: A homeowner's 20A breaker keeps tripping, so they replace it with a 30A breaker on the same 12 AWG wire.
The danger: 12 AWG wire is only rated for 20A. A 30A breaker won't trip until the wire is carrying 50% more current than it's designed for. The wire overheats, insulation melts, and a fire starts inside the wall where you can't see it.
The fix: If a breaker trips repeatedly, find and fix the cause — too many devices on the circuit, a short circuit, or a ground fault. Never upsize the breaker without upsizing the wire.
Mistake 2: Wrong Wire Type Outdoors
The problem: Using indoor-rated NM-B (Romex) cable to run power to an outdoor AC condenser through underground conduit.
The danger: NM-B isn't rated for wet locations. Moisture penetrates the sheathing, degrades insulation, and causes ground faults or shorts.
The fix: Use UF-B cable for direct burial or THWN conductors in conduit for outdoor runs. If running through conduit outdoors, use wet-rated individual conductors.
Mistake 3: Ignoring Voltage Drop on Long Runs
The problem: Running 10 AWG wire 200 feet to a detached garage for a sub-panel.
The danger: At 30A, 10 AWG wire drops 14.9V over 200 feet on a 240V circuit — a 6.2% voltage drop. Your HVAC compressor runs hot and inefficiently, the motor life shortens, and equipment may fail prematurely.
The fix: Use the voltage drop formula and upsize wire for runs over 50 feet. For a 200-foot, 30A run, 6 AWG copper limits voltage drop to 3.7%.
Mistake 4: Missing Equipment Ground
The problem: Using old 3-wire dryer or range cables (no separate ground) and assuming the neutral doubles as ground.
The danger: This was legal before NEC 1996 but is now prohibited for new installations. If the neutral breaks, the equipment chassis becomes energized at 120V.
The fix: All new 240V installations require a 4-wire connection: two hots, neutral, and separate equipment ground. Upgrade old 3-prong dryer outlets to 4-prong when replacing appliances.
Aluminum vs. Copper Wiring
| Property | Copper | Aluminum |
|---|---|---|
| Ampacity (per size) | Higher | ~78% of copper |
| Weight | Heavier | ~30% of copper weight |
| Cost per amp | Higher | 40–60% cheaper |
| Thermal expansion | Lower | Higher (creep risk) |
| Connection issues | Minimal | Requires anti-oxidant, rated connectors |
| Common sizes | 14 AWG – 4/0 AWG | 6 AWG – 4/0 AWG (feeders) |
| Residential use | Branch circuits | Service entrance, feeders |
Modern aluminum wire (AA-8000 alloy) is safe and code-compliant for feeders and service entrance cable. It's standard for 100A+ service conductors because copper at those sizes is prohibitively expensive. A 200A copper service entrance cable costs $4–$6/ft vs. $1.50–$3/ft for aluminum.
1960s–1970s aluminum branch circuit wiring (AA-1350 alloy) is a known fire hazard due to oxidation and thermal expansion at connections. If your home has aluminum branch wiring, have an electrician inspect connections and install approved CO/ALR-rated devices or COPALUM crimp connectors.
Permit and Inspection Requirements
When You Need a Permit
Most jurisdictions require electrical permits for:
- New circuits
- Panel upgrades or replacements
- Adding sub-panels
- Hardwired appliance installations (HVAC, water heaters)
- Service entrance changes
- Any work inside the panel
You typically do NOT need a permit for:
- Replacing outlets or switches (like-for-like)
- Replacing light fixtures
- Replacing a breaker with same-size replacement
Homeowner Permits
Many states allow homeowners to pull their own electrical permits for work on their primary residence. However, the work must still pass inspection. Common requirements:
- Apply for permit at local building department ($50–$200)
- Complete work according to NEC and local amendments
- Schedule rough-in inspection (before walls are closed)
- Schedule final inspection
- Inspector verifies wire sizes, connections, grounding, GFCI/AFCI protection
Pro tip: Even if your jurisdiction allows homeowner electrical work, consider hiring a licensed electrician for panel work and 240V circuits. The permit and inspection process ensures safety, and proper documentation protects your home's resale value and insurance coverage.
Key Takeaways
- Match wire to breaker, breaker to wire: Never put a 30A breaker on 14 AWG or 12 AWG wire
- Always check the equipment nameplate: Use MCA for wire sizing and MOP for breaker sizing on HVAC equipment
- Account for voltage drop: Upsize wire on runs over 50 feet, especially for 240V HVAC equipment
- Use dedicated circuits for all major appliances: AC, heat pump, water heater, dryer, range, EV charger
- GFCI and AFCI protection is required on nearly all residential circuits under NEC 2023
- 200A service is the modern standard — upgrade from 100A if adding heat pumps or EV chargers
- Copper for branch circuits, aluminum for feeders — both are safe when properly installed
- Pull permits and get inspections — it protects your home, your insurance, and your family
Frequently Asked Questions
Related Articles
10/2 or 10/3 Wire for AC? (Why 10/3 Is Overkill)
KEEP+ • 14 min read
3-Phase Power Calculator: kW to Amps, Amps to kW (2026)
KEEP+ • 16 min read
Electrical Panel Upgrade Cost: 100 to 200 Amp (2026 Pricing)
NEW • 17 min read
Water Heater Amps: How Many Amps Does a Water Heater Use? (2026)
KEEP+ • 10 min read