Flex duct, in the words of the Department of Energy's Building America Solution Center (BASC), is "a plastic inner liner attached to a metal wire helix (or coil)," with fiberglass blanket insulation already attached and "covered and protected by a polyethylene or foil vapor barrier"[1]. Rigid duct is solid sheet metal or fiberglass duct board[3].

Neither material wins on its own; installation decides. Flex is "essentially seamless along its length and at bends," so it leaks only at connections, and a correctly designed flex system "can provide efficient air delivery for many years"[3]. But compressed flex loses airflow fast: Lawrence Berkeley National Laboratory found that moderate compression, "typical of that often seen in field installations," could raise its pressure drop by a factor of four[4].

Diagram of two flex duct runs, one pulled taut and strapped every 4 feet, one compressed and sagging, with LBNL's finding that compression can raise the pressure drop up to four times, or close to ten.
Same duct, same run: the installation decides how much air reaches the room.

How they compare

Sheet metalFiberglass duct boardFlex duct
Construction
Solid metal, joined at seams and fittings
Fiberglass panels
Plastic liner on a wire helix, fiberglass insulation, poly or foil jacket
Where it can leak
Seams along its length and at fittings
Seams along its length and at fittings
Only at connections, unless torn or punctured
Insulation
Added where the duct runs outside conditioned space
Part of the panel
Built in; typically R-4, R-6 or R-8
Airflow
Depends on design and sealing
Depends on design and sealing
Efficient when pulled taut; compression can raise pressure drop by a factor of four or close to ten
If it gets wet or moldy
Hard-surface ducts can be cleaned
Wet or moldy insulated duct should be removed and replaced
Inspect for tears and crushing; a crushed duct can fail and leak
Typical role
Trunks and fittings
Trunks, plenums and boxes
Connections from the trunk to supply outlets, or the whole system
Sources: DOE Building America Solution Center (flex duct construction, insulation values, seams, connections, support and failure modes); Lawrence Berkeley National Laboratory, LBNL-49012 (compression); EPA, Should You Have the Air Ducts in Your Home Cleaned? (duct types and cleaning). Read DOE's flex duct guide.

The EPA notes that many modern duct systems are fiberglass duct board or sheet metal lined with fiberglass, and that flexible duct, generally lined with plastic, has become common[5]. On cleaning, it says to consider it for substantial visible mold in hard-surface ducts, while wet or moldy insulated duct "cannot be effectively cleaned and should be removed and replaced"[5].

Why flex duct has to be pulled tight

BASC: "Duct runs should be as short and straight as possible and flex duct should be stretched taut before connecting for maximum efficiency and air flow volume."[1] Pulled taut, flex "greatly reduces the amount of friction caused by the ducting," while "Compressing the duct or using excessive length will noticeably increase friction losses."[1]

LBNL's tests on 6, 8 and 10 inch[4] flex ducts measured how much. Moderate compression could raise the pressure drop by a factor of four, and further compression by "factors close to ten," and the lab found that "the available published references tend to underestimate the effects of compression"[4].

BASC installation ruleLimit
Duct length against the measured span
No more than 4% longer
Bend radius
At least the duct's diameter
Sag between supports
No more than 1/2 inch per foot (2.5 inches per 5 feet)
Support spacing, horizontal runs
Every 4 feet or closer
Support spacing, vertical runs
No more than 6 feet apart
Hanger strap width
At least 1.5 inches
Saddle support width
More than 5.5 inches along the duct
Extra length
Cut it off; don't loop it, and use balancing dampers to limit a room's airflow
Sources: DOE Building America Solution Center, No Excessive Coiled or Looped Flex Ducts and Support at Intervals for Flex Ducts (citing ADC and ICC-ES for strap and saddle widths). Read DOE's flex duct support guide.

Supports matter as much as length. When straps are too narrow or too tight, "the metal helix or plastic inner liner of the flex duct can be crushed or damaged, restricting air flow and compromising the insulation," and "Crushed ducts can eventually fail causing air leakage and large energy losses."[2] BASC also places a support at each connection between flex and rigid metal duct[2].

Looping flex to cut airflow to a room is a known shortcut. BASC says balancing dampers or proper duct sizing should be used "instead of looped or coiled ductwork"[1].

Sealing each type

  • Flex duct: at a collar, pull the core at least 2 inches[3] past the raised bead, tighten a nylon draw band with a tensioning tool, cover it with mastic, then pull the insulation and jacket over and seal them with UL-181 foil tape and mastic[3]. "Do not use a draw band to secure the flex duct insulation," because compressing it can create cold spots and condensation[3].
  • Sheet metal: seal the seams with mastic or UL-181 metal tape[6], and bridge wider gaps with fiberglass mesh tape and mastic[6].
  • Never cloth duct tape: "Regular cloth-backed duct tape should not be used because it can dry out and fail quickly."[3] ENERGY STAR says the same, calling duct tape not long-lasting[7].

Leakage costs the same whatever the material

ENERGY STAR says that in a typical house about 20 to 30 percent[7] of the air moving through the ducts "is lost due to leaks, holes, and poorly connected ducts"[7]. DOE puts duct air loss at about 30 percent[8] of a cooling system's energy use.

BASC works an example: a 2.5-ton[3] system moving 1,000 CFM[3] with 10% leakage[3], which it calls "typical in code-built homes," loses 100 CFM[3]. At 30 Btu per hour for each CFM[3], that is 3,000 Btu per hour of conditioned air sent outdoors (100 × 30 = 3,000). Duct leakage testing covers how a contractor measures it.

Insulation and condensation

Ideally, ducts sit inside conditioned space[2]. Where they run through a vented attic or crawl space, the 2021 IECC requires supply and return ducts to be insulated to "not less than R-8"[9] for ducts 3 inches in diameter and larger[9], and "not less than R-6"[9] for smaller ones.

Flex comes in R-4, R-6 and R-8[1], so in an attic under that code, check the R-value printed on the jacket. In humid and mixed-humid climates, BASC says ducts can't simply be laid on an insulated ceiling because of condensation on the outside of the ducts, unless they are first sealed, insulated and encapsulated in at least 1.5 inches[2] of closed-cell spray foam.

Sizing both

Our ductwork sizing calculator sizes smooth sheet-metal duct from the airflow and friction rate. For flex, BASC points to ACCA's Manual D, which "sets standards for flex duct design and installation"[1], and LBNL found that the pressure-drop correction for compressed flex depends on the duct size[4].

The 2021 International Residential Code requires duct systems to be sized and installed to ACCA Manual D, the manufacturer's installation instructions or other approved methods[10].

Frequently asked questions

Is flexible duct as good as rigid?

When it is pulled taut, supported and sealed at its connections, BASC says a correctly designed flex system "can provide efficient air delivery for many years"[3]. Compressed or sagging, it can lose much of its airflow: moderate compression can raise its pressure drop by a factor of four[4].

How long can a flex duct run be?

BASC says runs "should be as short and straight as possible," cut so the duct is no more than 4% longer[1] than the span it covers. Manual D sets the design limits[1].

Why is one room colder or hotter than the rest?

ENERGY STAR names "Improper equipment operation, duct problems or inadequate insulation" as possible causes[11]. BASC adds that sagging, twisted or crushed ducts "can severely limit air flow"[1], so check the flex runs in the attic or crawl space.

Does flex duct need to be insulated?

It comes insulated, typically at R-4, R-6 or R-8[1]. Outside conditioned space, the 2021 IECC requires R-8 for ducts 3 inches[9] and larger, so pick the R-value to match.

Is flex duct code-approved?

The 2021 International Residential Code accepts duct systems designed to ACCA Manual D, the manufacturer's installation instructions or other approved methods[10], and your local building official enforces the code in force where you live.

Can you use flex duct for a return?

DOE's guidance says flex can make up "the entire duct system"[1], and the same rules apply on the return side: pulled taut, supported and sealed at every connection[3]. Size the return path with Manual D; see cold air return vents.

How long does flexible duct last?

No federal source gives a lifespan. BASC says a properly connected system "can provide efficient air delivery for many years"[3], and that crushed ducts "can eventually fail causing air leakage and large energy losses"[2], so inspect attic and crawl space runs for tears, sags and loose connections.

Sources & References

  1. U.S. DOE Building America Solution Center: No Excessive Coiled or Looped Flex Ducts (updated 2022-09-30) (flex construction and R-values; short, straight, taut runs; compression and extra length raise friction; length within 4% of the span; bend radius; sag limit; balancing dampers, not loops; Manual D)
  2. U.S. DOE Building America Solution Center: Support at Intervals for Flex Ducts (updated 2022-12-02) (ducts ideally in conditioned space; supports every 4 feet, sag under 1/2 inch per foot, vertical runs 6 feet; straps 1.5 inches, saddles over 5.5 inches; crushed ducts fail; humid-climate condensation and 1.5 inches of closed-cell foam)
  3. U.S. DOE Building America Solution Center: Sealed and Insulated Flex Ducts (updated 2022-09-30) (flex seamless along its length; collar, draw band, mastic and UL-181 tape; no cloth duct tape; 2.5-ton leakage example)
  4. Lawrence Berkeley National Laboratory: Abushakra, Walker and Sherman, Compression Effects on Pressure Loss in Flexible HVAC Ducts (LBNL-49012, HVAC&R Research, 2004)
  5. EPA: Should You Have the Air Ducts in Your Home Cleaned? (duct board, lined sheet metal and flexible duct; hard-surface ducts; wet or moldy insulated duct)
  6. U.S. DOE Building America Solution Center: Sealed and Insulated Metal Ducts (mastic, UL-181 tapes, mesh tape over wider gaps)
  7. ENERGY STAR: Duct Sealing (about 20 to 30 percent of duct air lost in a typical house; never duct tape)
  8. U.S. DOE: Energy Saver 101, Home Cooling (PDF) (duct air loss about 30 percent of a cooling system's energy use)
  9. ICC: 2021 International Energy Conservation Code, R403.3.1 duct insulation (R-8 at 3 inches and larger, R-6 smaller, outside conditioned space)
  10. ICC: 2021 International Residential Code, M1601.1 duct design (ACCA Manual D, manufacturer's instructions or other approved methods)
  11. ENERGY STAR: When is it time to replace? (rooms too hot or too cold)
  12. ACCA: Technical manuals (Manual D)

Related Articles