A duct has to carry the air your system moves without losing too much pressure to friction, which the blower has to make up, or moving it too fast: the U.S. Defense Department's noise guide says grille noise rises with the fifth to sixth power of air velocity[8]. Size it from two numbers: how much air it carries, in cubic feet per minute (CFM), and how much pressure you can afford to lose along the duct, the friction rate.

At the calculator's default friction rate of 0.08 inches of water per 100 feet (an assumed design value), 400 CFM (roughly one ton of cooling[3]) needs a round duct about 10.1 inches across in this page's calculator, and 1,000 CFM needs about 14.3 inches. Round up to the next standard size, then check the air speed.

Duct Sizing Calculator

Round and rectangular duct size from airflow and a design friction rate.

1

Airflow

Enter CFM directly, or size it from tonnage

CFM
2

Design friction rate

Static pressure lost per 100 ft of duct

in. w.c./100 ft
Enter your values and click Calculate, press Enter in any field.
Four-step diagram of the duct calculator: airflow in CFM, a friction rate of 0.08 inches of water per 100 feet, solve the diameter and round up to a standard size, then check air speed; 400 CFM needs 10.14 inches, so a 12-inch duct at about 509 fpm.
The calculator's method, using the 400 CFM row from the chart below.

How the calculator works

  1. Airflow. Enter CFM, or tons of cooling at the typical design airflow of about 400 CFM per ton[3].
  2. Friction rate. The pressure loss you design for, in inches of water per 100 feet; the calculator's default is 0.08, a calculator assumption. The residential code has duct systems designed to ACCA Manual D, the manufacturer's instructions or another approved method[5], and that design sets the right value for a specific system.
  3. Duct physics. For smooth galvanized steel duct and standard air, the calculator finds the diameter that produces that friction rate, using the Darcy-Weisbach equation with the Swamee-Jain friction factor. It then rounds up to the next standard size and reports the actual speed and friction.

CFM to round duct size chart

Computed with this page's calculator at its default friction rate of 0.08 inches of water per 100 feet (a calculator assumption):

AirflowCalculated diameterNext standard sizeAir speed at that size
100 CFM
6.05 in
7 in
374 fpm
200 CFM
7.83 in
8 in
573 fpm
400 CFM
10.14 in
12 in
509 fpm
800 CFM
13.14 in
14 in
748 fpm
1,000 CFM
14.29 in
16 in
716 fpm
1,200 CFM
15.30 in
16 in
859 fpm
1,600 CFM
17.05 in
18 in
905 fpm
How this was calculated: this page's calculator solves the Darcy-Weisbach equation with the Swamee-Jain friction factor for smooth galvanized steel duct and standard air at 0.08 inches of water per 100 feet, rounds up to the next standard size, and divides the airflow by that size's cross-section for the air speed.

The calculator flags speeds above 900 feet per minute, a calculator assumption meant to keep a home system quiet. Where a size falls just over a standard size, as 6.05 inches does, a designer may accept the smaller size and slightly higher friction.

Three rectangular ducts drawn to scale beside their round equivalents: 8 by 10 inches equals 9.76 inches round, 8 by 14 equals 11.46 inches, and 10 by 12 equals 11.96 inches, by the Huebscher formula.
Each pair carries the same air at the same friction.

Round to rectangular

A rectangular duct carries the same air with the same friction as a round duct of its equivalent diameter, by the Huebscher formula: De = 1.30 × (a × b)^0.625 ÷ (a + b)^0.25, with sides a and b in inches.

Rectangular ductEquivalent round diameter
8 × 10 in
9.76 in
8 × 14 in
11.46 in
10 × 12 in
11.96 in
How this was calculated: the Huebscher equivalent-diameter formula stated above, De = 1.30 times (a times b) to the 0.625 power divided by (a plus b) to the 0.25 power, applied to each rectangular size

The calculator lists the smallest rectangular sizes, at heights of 6, 8, 10 and 12 inches (a calculator assumption), that match the round size you need.

Trunk lines and branch ducts

The main trunk carries the system's total airflow, and each branch carries one room's share. Room airflow comes from a room-by-room load calculation, and the 2021 International Residential Code has duct systems installed to ACCA Manual D, the appliance manufacturer's instructions or another approved method[5]. Use this calculator to size individual runs once you know their airflow.

Flexible duct needs its own numbers: the DOE's Building America guidance notes that compressing flex duct or using excess length noticeably increases friction losses, and points to Manual D for flex duct design[6]. In Lawrence Berkeley National Laboratory tests, moderate compression typical of field installations could raise the pressure drop by a factor of four[7].

Leaky ducts also waste energy: the DOE puts duct air losses at about 30% of a cooling system's energy[2]; see duct leakage testing.

BTU to CFM: airflow from capacity

A system's capacity is rated in BTU per hour, but ducts are sized by airflow in CFM, so converting one to the other is the step between choosing the equipment and sizing the ducts.

The sensible heat formula

For air at standard conditions, BTU per hour = 1.08 × CFM × temperature difference (°F). The 1.08 comes from the density and specific heat of air, times 60 minutes. Rearranged, CFM = BTU per hour ÷ (1.08 × ΔT).

Cooling: CFM per ton

Air conditioners are designed around a target airflow across the indoor coil, typically about 400 CFM per ton[3], where one ton is 12,000 BTU per hour[4]:

SystemCooling capacityAirflow at 400 CFM per ton
2 tons
24,000 BTU/hr
800 CFM
3 tons
36,000 BTU/hr
1,200 CFM
4 tons
48,000 BTU/hr
1,600 CFM
How this was calculated: tons times 12,000 BTU per hour for capacity and tons times 400 CFM per ton for airflow, the figures stated above

ACCA's example figures are 350 CFM per ton for hot, humid climates and 450 for drier ones[3].

Heating: temperature rise

Heating airflow uses the same formula. For example, an 80,000 BTU per hour output needs about 1,481 CFM for a 50°F rise (80,000 ÷ (1.08 × 50)), or 1,058 CFM for a 70°F rise. Check the furnace's installation instructions for the temperature rise it allows, and keep the airflow high enough to stay inside it.

Frequently asked questions

What size duct do I need for 400 CFM?

This page's calculator gives about 10.1 inches round at its default 0.08 inches of water per 100 feet, so a 12-inch duct among its standard sizes. A 10-inch duct would run slightly above that friction rate.

How many CFM per ton?

About 400 CFM per ton[3] is the typical design airflow; ACCA's example figures are 350 CFM per ton for hot, humid climates and 450 for drier ones[3]. The equipment's specifications give its design range.

How do I convert round duct to rectangular?

Use the Huebscher formula above, or the calculator's rectangular list: for example, a 10 × 12 inch duct is equivalent to about a 12-inch round duct (11.96 inches).

What friction rate should I use?

It depends on the pressure your fan can supply after filters, coils and grilles take their share. The calculator's default is 0.08 inches of water per 100 feet, a calculator assumption; a Manual D design sets the right value for a specific system.

How do I convert BTU to CFM?

For heating or sensible cooling, CFM = BTU per hour ÷ (1.08 × temperature difference). For cooling equipment, multiply tons by about 400 CFM[3].

How many CFM does a 3-ton AC need?

About 1,200 CFM (3 tons × 400 CFM per ton[3]).

About these figures

The 400 CFM per ton design airflow[3] and the 350-to-450 CFM humid-and-dry range[3] come from an ACCA article on design airflow. The duct-loss figure is from the DOE's Energy Saver 101 home cooling guide[2], and NIST's guide to SI units puts one ton at 12,000 BTU per hour[4].

The rectangular-to-round conversion is the Huebscher (1948) equivalent-diameter equation. We couldn't check it against a freely available primary copy, so treat the round equivalents as this calculator's method.

Related Articles